Loading...
HomeMy WebLinkAboutOrd 5338 06/17/2003ORDINANCE NO. 5338 AN ORDINANCE AMENDING CHAPTER 24 (FIRE PREVENTION) OF THE VILLAGE CODE OF MOUNT PROSPECT Passed and approved by the President and Board of Trustees the 17th day of June, 2003 Published in pamphlet form by authority of the corporate authorities of the Village of Mount Prospect, Illinois, the 18th day of June, 2003 ORDINANCE NO. 5338 AN ORDINANCE AMENDING CHAPTER 24 OF THE VILLAGE CODE OF MOUNT PROSPECT BE IT ORDAINED BY THE PRESIDENT AND BOARD OF TRUSTEES OF THE VILLAGEOF MOUNT PROSPECT, COOK COUNTY, ILLINOIS: SECTION 1: Chapter 24 entitled "Fire Prevention Code" of the Village Code of Mount Prospect shall be amended by deleting Article I, Sections 24.101 through 24.105 in their entirety and adding new Sections 24.101 through 24.105 which shall be and read as follows: 24.101: APPLICATION: The intent of this code is to prescribe minimum requirements necessary to establish a reasonable level of fire safety and property protection from the hazards created by fire and explosion. This code applies to both new and existing conditions unless specified otherwise. (Ord. 4513, 1-15-1993; Ord. 4894, 10-7-1997) 24.102: ADOPTION OF FIRE PREVENTION CODE: The 2000 edition, National Fire Prevention Code (NFPA 1), The International Fire Code, 2000 and Article 7 from the 2000 Property Maintenance Code, Standard for the Installation of Automatic Sprinklers (NFPA 13) 2002 edition, and The National Fire Alarm Code (NFPA 72) 2002 edition in their entirety and as amended hereafter in this chapter is hereby adopted as the Fire Prevention Code of the Village of Mount Prospect for the control of fire in buildings and structures. The appendices of all NFPA standards adopted by Village of Mount Prospect are considered as part of each standard and are mandatory requirements and not advisory information. B. Performance based computer code analysis are not permitted. Co Enforcement of The Fire Prevention Code: the Fire Prevention Bureau of the Mount Prospect Fire Department shall enforce the Fire Prevention Code. The Fire Prevention Bureau is hereby established and shall be operated under the supervision of the Fire Chief. The Chief of the Fire Department shall be designated as the Fire Official and shall appoint such members necessary to enforce the provisions of this code. Whenever the title "code official" is used in the text of the fire prevention codes adopted herein, the term shall be changed to "Chief of the Mount Prospect Fire Department". The "Village of Mount Prospect" shall be inserted in place of all text "Name of Jurisdiction". A copy of the codes adopted herein by reference shall be on file in the office of the Village Clerk. (Ord. 4513, 1-5-1993; Ord. 4656, 7-5-1994; Ord. 4894, 10-7- 1997) 24.103: FIRE LANES: The Fire Official shall require and designate a sufficient number of public or private fire lanes as deemed necessary for the efficient and effective use of all fire and or emergency medical apparatus. The Fire Official shall consider the anticipated operation of the Fire Department's equipment for any emergency incident that might occur at the location being considered as requiring a fire lane. The fire official shall take into consideration the need for requiring additional fire lanes when automatic sprinklers protect the building(s). Fire lanes shall be provided for all buildings when any part of the building is set back more than one hundred fifty feet (150') from a public road or for buildings which exceed thirty feet (30') in height and set back over fifty feet (50') from a public road, access road, or private road. All fire lanes shall be minimum of twenty feet (20') in width and shall be constructed to meet the requirements of subsection 16.403B 1 b of this Code. Split fire lanes and fire lanes constructed of paved blocks shall not be permitted. Those areas deemed as fire lanes shall be capable of structurally supporting fire apparatus. A minimum of thirteen feet (13') of vertical clearance must be continuously maintained for all fire lanes. Fire lanes shall not be configured to create a dead-end road, access drive or street (public or private) greater than three hundred feet (300'). Any dead-end fire lane with a dead-end distance in excess of three hundred feet (300') shall be provided with a turnaround sufficient in size to accommodate the largest fire apparatus. All fire lanes shall be maintained as specified by the Fire Official for emergency use for the life of the building or structure. Every fire lane shall be posted as such with a sufficient quantity of signs as deemed appropriate by the Fire Official. The Fire Official may also require painting and striping of the fire lane when deemed as necessary. The cost of the signs, markings and installation shall be the responsibility of the building owner. Go It shall be unlawful for any person or object to block or obstruct wholly or partially any fire lane. Gates or other barriers shall not be installed on any new or existing fire lane without written approval from the Fire Official. All gates permitted by the Fire Official desired to be locked in the closed position shall be provided with a locking device approved by the Fire Official. Electrically operated gates shall have a key operated switch approved by the Fire Official. Where deemed necessary by the Fire Official, electric gates installed on fire lanes are required to be provided with an electronic device that will automatically open upon activation of Mount Prospect emergency vehicles traffic pre- eruption signal. (Ord. 4894, 10-7-1997) 24.104: KEY BOXES: Ao A Knox Box shall be installed on all buildings having an automatic fire alarm or fire suppression system that is supervised by a listed supervising agency and/or in those buildings, which contain a passenger elevator. Keys shall be provided to allow access to all areas of the building necessary to mitigate any foreseen emergency condition that the Fire Department may be called upon to protect. This includes, but is not limited to, keys to unlock all fire system control devices, elevator equipment rooms, electrical rooms, storage rooms and other areas required by the fire official. C. All required keys should be labeled as to what they serve. In areas, which utilize other methods of security instead of keyed locks, sufficient information and/or equipment shall be provided in the Knox box for Fire Department use. This includes, but is not limited to, card keys, security codes, etc. It shall be the responsibility of the property owner to notify the Fire Department if there are any changes with the building or structure that would require the contents of the Knox box to be modified. F. All required Knox Boxes shall be located as required by the Fire Official. A sufficient number of Knox Boxes shall be provided as deemed necessary by the Fire Official. (Ord. 4894, 10-7-1997) Multiple tenants. A single Knox Box may be provided to serve multiple tenants provided the Knox Box can be installed in a location to accommodate fire department operations and the Knox Box is large enough to accommodate all keys for each tenant space. 24.105: FIRE EXTINGUISHERS: In the International Fire Code, Section 906. 1 and the accompanying exception shall be deleted and shah be replaced with: "portable fire extinguishers shall be provided in every occupancy as well as those areas specified in NFPA 1, 2000 edition, International Fire code, 2000 edition and the International Building Code, 2000 edition. EXCEPTION: Individual dwelling units in all use group-R classifications." All new fire extinguishers shall be of an approved type with a minimum rating of 3A-40-BC. Existing fire extinguishers at the time of adoption of this code shall be a minimum rating of 2A-20BC. Every required extinguisher shall be installed in a location visible to occupants and general public and must be easily accessible. All extinguishers shall be securely mounted to the wall or structural member of the building. The top of the fire extinguisher shall not exceed five feet (5') in height above the finished floor and the bottom of the extinguisher shall be a minimum of two feet (2') above the finished floor. Every extinguisher shall be provided with adequate markings indicating the location of the extinguisher. When extinguishers are mounted to structural members of the building, a one foot (1') wide red stripe shall be applied to the structural member a minimum often feet (Iff) above the finished floor. (Ord. 4894, 10-7-1997) SECTION 2: Chapter 24 entitled "Fire Prevention Code" of the Village Code of Mount Prospect shall be amended by deleting Article I, Sections 24.107 in its entirety and adding a new Sections 24.107 which shall be and read as follows: 24.107: EMERGENCY LIGHTING: Emergency lighting circuits shall be provided for all exit signs and emergency lights. In new and existing buildings, emergency lighting shall be provided in all occupancies and in those other areas specified in the International Building Code, 2000 edition, International Fire Code, 2000 edition, and NFPA 1, 2000 edition. In addition, emergency lighting shall be installed in the following areas: 1. All egress corridors 2. All stairwells 3. Basements 4. Rooms for assembly occupancies 5. All public areas of the building (Including restrooms) Rooms containing fire protection equipment such as pumps, control valves, fire alarm panels and remote annunciator. Exception: Individual dwelling units of all use group R occupancies SECTION 3: Chapter 24 entitled "Fire Prevention Code" of the Village Code of Mount Prospect shall be amended by deleting Article I, Sections 24.113 and 24.114 in their entirety and adding new Sections 24.113 and 24.114 which shall be and read as follows: 24.113: OTHER SIGNS: In buildings or occupancies where the point of delivery of the natural gas is provided with two or more shutoff valves, permanently affixed signs shall be provided to clearly indicate the area(s) served by each valve. No installation shall be permitted until the Fire Official has approved the language on the sign. 24.114: ADDRESSES: Addresses shall be provided in both the front and rear of tenants in new and existing strip shopping centers. The address letters or numbers shall be a minimum of four inches in height and their color shall contrast with the surface on which they are affixed. SECTION 4: Chapter 24, entitled "Fire Prevention Code" of the Village of Mount Prospect shall be amended by renumbering current Section 24.113 entitled Prohibited Acts to Section 24.115. SECTION 5: Chapter 24, entitled "Fire Prevention Code" of the Village Code of Mount Prospect shall be amended by deleting Sections 24.201 through 24.204 and 24.206 in their entirety and inserting in lieu thereof the following new Sections 24.201 through 24.204 and 24.206 which shall be and read as follows: 24.201: AUTOMATIC DETECTION AND/OR EXTINGUISHMENT OF FIRE: Authority is hereby conferred upon the Chief of the Fire Department to adopt and promulgate rules based upon the standards of any nationally recognized organization embodying details for the installation and construction of automatic sprinkler equipment and/or automatic fire detection equipment in such instances where, based upon the standards contained herein, any building or part thereof, because of its size, construction, occupancy or lack of suitable protective equipment, shall be deemed by the said Fire Chief or his duly authorized agent to constitute a special fire hazard to life or property or an excessive burden upon the fire extinguishing facilities of the Fire Department. The Fire Official shall be responsible for the enforcement of the requirements related to the installation, testing, maintenance and modification of all fire detection, fire suppression and standpipe systems. All automatic sprinkler equipmento~.~...~um~'~ ~...~"~:"~.~ shall be inspected at least once a year as is specified herein below, and at all times maintained in proper operative condition by the owner or occupant of such building. The occupant(s) of such buildings containing such equipment shall promptly notify the Fire Prevention Bureau of the Fire Department in case such Sprinkler system or any other fire protection equipment .... :~'~'~ ~' ~" ' ut, .............is withdrawn from such building, or the use of such equipment therein is interrupted, curtailed or altered. Whether the building is occupied or not, it shall be the responsibility of the owners of all buildings having interior fire alarm (including single station smoke detectors) and suppression systems both existing and those which are to be constructed, to provide for the continuous maintenance of such systems through no less than an annual inspection and testing of the systems. Written certification of each annual inspection and testing of the fire alarm and suppression systems shall be provided to the Fire Prevention Bureau upon completion of such test. The Fire Prevention Bureau shall be notified in writing prior to any other activities requiring full flowing of the fire pump, including but not limited to the full flow fire testing of any fire pump required per NFPA 20. A minimum of 48 hours written notice must be made to the Fire Prevention Bureau prior to such activity. Failure to have a member of the Mount Prospect Fire Prevention Bureau present will result in a written warning to both the testing agency and building owner. After the written warning has been delivered, every failure thereafter by either the owner of the property or testing agency to notify the Fire Prevention Bureau to witness the fire pump test will result in a fine minimum of $500. The imposition of a fine upon the second failure of an individual or entity to notify the Fire Prevention Bureau shall not be dependent on the offense(s) taking place at the same location which initiated the written warning. This code section shall be posted on all new and existing fire pump control panels for the life of the building. A "certificate of occupancy" and/or "business license" as defined in this Code, shall not be issued and no movement of supplies and/or equipment into the building shall be permitted until the fire suppression and/or fire alarm system is functional, certified by a testing agency and monitored by a listed agency. 24.202: AUTOMATIC SPRINKLER AND SUPPRESSION SYSTEMS: The provisions of this section shall specify where fire protection systems, standpipes and detection systems are required to be installed and shall apply to the design, installation and maintenance of all such systems. Where a conflict exists between any of the adopted codes, the most restrictive provision shall apply. (Ord. 4513, 1-5-1993; Ord. 4894, 10-7-1997) Where Required: Automatic sprinkler systems shall be installed and maintained in full operating condition in all buildings/areas specified in the International Fire Code, 2000 edition, International Building Code 2000 edition, and NFPA 1, 2000 edition and the following occupancies and areas: Automatic sprinkler systems shall be provided in all newly constructed buildings, structures or portions thereof regardless of occupancy classification, construction or square footage. This requirement shall also apply to manufactured homes or buildings. o In existing structures when an automatic fire suppression system would be required if new, then an automatic fire suppression system shall be provided throughout the building when: The fire area is increased regardless of the square footage. For the purpose of determining fire areas that require the installation of automatic sprinklers, a "fire area" shall be defined as those areas bound by concrete or masonry fire walls constructed in accordance with section 705 of the International Building Code, 2000 edition. Exceptions: Existing buildings with a use group classification of B or M with a total fire area of five thousand (5,000) square feet or less. 2. Single family attached and detached homes, town homes, and manufactured homes. There is a change in use group classification as outlined in the International Building Code, 2000 edition. Exceptions: When an occupancy classification change is made to or from an existing Use Group B or M to a new occupancy classification of B or M in existing buildings or structures with a total fire area of five thousand (5,000) square feet or less. Existing single-family homes used as residential board and care facilities complying with all provisions of NFPA 101, 2000 edition. Additions, repairs, alterations, remodeling is in excess of fifty percent (50%) of the valuation of the property. Exceptions: Existing buildings or structures with a use group classification of B or M and within a building with the total fire area less than five thousand (5,000) square feet. 2. Single family attached and detached homes, town homes and manufactured homes There is an addition to the structure regardless of square footage of the addition. Exception: Buildings of Use Group B and/or M when the addition does not increase the building's total fire area to five thousand (5,000) square feet or greater. 2. Covered porches or stoops. 3. Single family homes, town homes and manufactured homes System Installation: All automatic sprinkler systems shall be installed in accordance with NFPA 13 Standard for the Installation of Sprinkler Systems, 4-994-~tit4-~, 2002 edition unless otherwise modified hereafter. NFPA 13D systems shall be permitted in single-family attached and detached homes, town homes and manufactured occupancies. NFPA 13R, designed systems shall not be permitted. Omission Of Sprinklers From Rooms Or Spaces: Sections 903.1.1 and 903.3.1.1.1 of the International Fire Code, 2000 edition shall be deleted. When sprinkler protection is required, sprinklers shall be provided throughout all areas of the building in every room or space regardless of use or occupancy contents. Combustible concealed spaces shall be protected as required per NFPA 13, 2002 edition. When sprinkler protection is required in single-family homes, town homes or manufactured homes, sprinklers may not be omitted from garages. Eo Exception: Upon written approval from the Fire Official, sprinklers may be omitted in areas where the products stored or operation within the room is considered to be a water reactive agent as determined by the products Material Safety Data Sheet. In areas where sprinklers are permitted to be omitted, an alternative suppression system approved by the Fire Official shall be installed in accordance with the applicable NFPA standard and International Fire Code. Sprinkler Systems Protecting Multiple Tenants: Where sprinkler systems protect more than one tenant, a separate water flow switch and control valve shall be provided for each tenant space. Exception: Existing buildings protected by automatic sprinklers systems. Sprinkler Control Valves: All new sprinkler control valves shall be located within five feet (5') above the finished floor and shall be UL listed for fire protection systems. All new and existing control valves shall bear a permanently affixed label indicating the area and function the control valve serves. All new and existing control valves shall be electronically supervised and maintained in accordance with this code. Control valves shall be installed in all locations specified in the International Fire and International Building Code, NFPA 1, NFPA 13 and in the following locations: Exception: Existing approved limited area sprinkler systems. Sprinklers protecting electrical rooms shall be provided with a separate control valve located outside the entrance into the electrical room. o A separate control valve shall be required to permit the isolation of each floor or mezzanine protected by automatic sprinklers. Limited Area Sprinkler Systems: New limited area sprinkler systems utilizing a domestic water supply shall meet all of the requirements of this Chapter for the installation of sprinkler systems. Location Of Sprinkler Riser, Fire Pump, System Control Valves And Other Fire Protection Equipment: All new sprinkler risers and associated equipment shall be located in a separate room with a minimum of one-hour construction. Rooms containing fire pumps shall be separated fi.om the remaining portions of the building by a minimum of two (2) hour construction. 2. Rooms containing fire protection control equipment shall be provided with direct access from the exterior and interior of the building. All new and 10 existing entrance doors shall bear a sign on the exterior of the door with four-inch (4") high letters indicating, "sprinkler room". Additional signage may be required in cases where the riser serves more than one tenant. New and existing rooms shall contain emergency lighting. Rooms designated, as sprinkler rooms shall not be used for any other purpose. A minimum of three feet (3') clear space shall be maintained around the circumference of any new or existing fire hydrant, Fire Department connection, fire protection control valve or any other fire protection system component. Inspectors Test Connections And Two Inch Drains: All required inspectors test connections and two inch (2") drains shall discharge directly to the outside. Discharge into a floor drain or sink shall not be permitted. Fire Pump Test Headers: All fire pump test headers shall be provided with a UL listed OS and ¥ valve. Test headers for fire pumps shall be located outside in a location conducive to annual full fire flow testing and in a location approved by the Fire Official. Fire Department Connections: Fire Department connections shall be provided for all sprinkler systems. The Fire Department connection shall consist of a two by two and one-half inch (2 x 2 1/2") Siamese connection and a five-inch (5") stortz connection. Both connections shall contain a check valve. Exceptions: go Sprinkler systems with twenty (20) or fewer sprinklers may be supplied by a single two and one-half inch (2 1/2") connection. b. Sprinkler systems installed in accordance with NFPA 13D. All new Fire Department connections shall be located on the front side of the building within one hundred feet (100') of an accessible Village fire hydrant in a location approved by the Fire Official. All new and existing Fire Department connections shall be accessible at . all times. Trees, shrubs or other landscaping materials shall not be installed to prohibit access to the Fire Department connection. All new and existing Fire Department connections shall be provided with a sign directly above the connection indicating "FIRE DEPARTMENT CONNECTION". Where the building or group of buildings is served by 11 more than one connection, a sign shall also be provided to indicate the area in which the Fire Department connection serves. o A freestanding Fire Department connection shall be installed in accordance with this Section for all new buildings greater than thirty-five feet (35') in height. The connection shall be located a minimum of 20 feet from the building or in a location approved by the fire official. o All new and existing Fire Department connections shall have a white strobe installed directly above the Fire Department connection. The strobe shall be approved for exterior use and operate upon activation of the sprinkler water flow switch and or the building's fire alarm. All new and existing Fire Department connections shall be painted bright red and maintained in this condition by the building owner throughout the life of the system. Exception: Chrome plated or polished brass connections. New fire department connections installed on sprinkler systems with a sprinkler or standpipe demand in excess of 1000 gpm shall supply the sprinkler system with a minimum of six inch piping. Suppression System Alarms: All buildings or areas required to have an automatic suppression system shall contain audible and visual devices installed in accordance with NFPA 72, !993 Edit/on. The devices shall operate upon activation of the suppression system and shall emit sound and illumination levels for fire alarm devices as specified in NFPA 72, ~ ............ All new and existing fire sprinkler suppression systems shall be monitored by a UL listed central station. Exception: Residential occupancies protected in accordance with NFPA 13D shall not be required to be connected to a fire alarm system but shall contain an inside and outside audible bell. The inside bell shall be located on the furnace return air duct. If a return air duct is not provided, the bell shall be located so that it can be easily heard throughout the structure. All new fire suppression systems protecting a kitchen hood located in buildings equipped with a fire alarm system shall have the suppression system connected to the building's fire alarm system. Acceptance Testing: All required acceptance testing shall be conducted in the presence of the Fire Official. At the time of acceptance testing, the contractor shall provide a job copy of the approved installation drawings for use during the testing. A minimum of forty-eight (48) hours' notice to the Fire Official is 12 required. All sprinkler lead-ins shall be flushed in accordance with NFPA 13 and witnessed by the Fire Official prior to connection to the sprinkler riser(s). Testing documentation shall be provided to the Fire Official prior to the issuance of certificate of occupancy. The installing contractor shall furnish all necessary equipment with a sufficient number of personnel to conduct the tests. This shall include, but not be limited to, two-way radios, ladders, sound level measuring equipment, water flow measuring equipment and applicable testing documents. Sprinkler System Design: All new sprinkler systems or modifications to existing systems shall be hydraulically designed with a minimum of a 5 psi safety factor. All system designs shall be based on a seasonal low water flow test provided by the Village. The Fire Official or h/s/her designee shall witness all water flow tests used for the design of sprinkler systems. Exception: Sprinkler systems designed in accordance with NFPA 13D. e Prior to the installation or alteration of any sprinkler or standpipe system, a permit shall be obtained from the Village of Mount Prospect. Equipment cut sheets, engineering drawings, and hydraulic calculations containing details as outlined in the applicable NFPA standard shall be submitted for review and approval prior to the start of any work. On each drawing a copy of the hydraulic nameplate shall be provided. When revised drawings are requested by the Fire Prevention Bureau, the revisions shall include a clouded notation on the revised portion of the drawing with numbers corresponding to the fire department's written review comments. The sprinkler permit issued by the Village of Mount Prospect shall be posted on the front of the building for the entire project. 13 Four (4) sets of calculations, drawings and equipment cut sheets shall be submitted for review and approval prior to the modification or installation of any suppression or fire alarm system. Upon completion of the project, a complete set of as-built documents shall be submitted and approved by the Fire Department prior to the final inspection for certificate of occupancy. Installation Of Backflow Prevention Devices: Any addition or alteration to an automatic sprinkler system shall be in accordance with the appropriate design standard for the system. If the addition of a backflow prevention device decreases the water pressure below the required pressure for the fire safety system, additional measures shall be taken in each such case to restore the pressure to the operating level required by mechanical means (i.e., a fire pump). Before a backflow prevention device is installed retroactively on a fire sprinkler system, a thorough hydraulic analysis shall be performed including: Revised hydraulic calculations for hydraulically calculated systems in accordance with NFPA 13, 2002 edition. Submitted calculations should include the pressure loss anticipated through the backflow prevention device. Revised sprinkler system calculations for the system demand for pipe schedule systems NFPA 13, 2002 edition. Current water supply data based on a water supply test, including a comparison assuring that any additional pipe lengths or fittings necessary to accommodate the proper installation of the backfiow prevention device will not increase the sprinkler system demand beyond the available water supply; and All necessary modifications contributing to the additional friction loss. These items, including a manufacturer's data sheet indicating the expected pressure loss, must be submitted to the Village of Mount Prospect and reviewed by the Fire Prevention Bureau prior to the installation of the backflow prevention assembly. (Ord. 4894, 10-7-1997) 24.203: STANDPIPES Where Required: Buildings two (2) stories or greater and/or those buildings arranged or constructed to exceed one hundred fifty feet (150') from any entrance to the most remote portion to the building shall be provided with standpipes 14 Eo Go Ho throughout the building in accordance with NFPA 14 unless modified within this code. Location Of Standpipes: Standpipes shall be located on the intermediate landings of all stairwells in buildings required to be equipped with standpipes. All areas shall be capable of being reached within one hundred fifty feet (150') from each hose outlet. The distance shall be measured along the normal path of unobstructed travel. Standpipe Control Valves: A separate control valve shall be provided to permit isolating the sprinkler system without interrupting the water supply to the standpipe system. Hose Valves: All hose valves shall be two and one-half inches (2 1/2") with a one and one-half inch (1 1/2") reducer cap. The threads of the hose valve shall be National Standard Thread. Standpipe Flow Switches: All standpipe systems shall be provided with a flow switch monitored by an approved central station. System Design: Standpipes shall be designed in accordance with NFPA 14 unless otherwise amended in this Code. All standpipes shall be hydraulically designed to deliver the required water flow of 500 gpm with 100 psi of residual pressure at the most remote outlet and 250 gpm for each additional outlet not to exceed 1,000 gpm. The sprinkler demand shall be included as part of the overall standpipe system demand. Exception: Buildings two (2) stories or less may base the standpipe design with 150 psi and 1,000 gpm available at the Fire Department connection. The sprinkler system design shall be based on NFPA 13 with an additional 500 gpm added to the required inside hose demand. Automatic Water Supply: An automatic water supply shall be provided for all standpipes. Types Of Systems: Dry standpipes shall only be permitted in those areas subjected to freezing where the installation of heat is not practical due to the operation of the building or structure. Pressure Regulating Devices: The installation of any pressure-regulating device shall be reviewed by the Fire Official prior to installation. The Fire Official will evaluate the need for pressure regulating devices based on available pressure and overall operation of the Fire Department. When pressure-regulating devices are required, the Fire Official shall specify the type of pressure regulating device. It 15 shall be the owner's responsibility to ensure all pressure-regulating devices are maintained for the life of the system in accordance with NFPA 14. Flow Test: A flow test shall be conducted at the hydraulically most remote hose outlet to verify the system is capable of meeting the required flows set forth in this code. (Ord. 4894, 10-7-1997) 24.204: FIRE ALARM SYSTEMS: Where Required: A fire alarm system shall be installed and maintained in full operating condition in all buildings/areas specified in the International Building and Fire Prevention Code, 2000 edition, NFPA 1, and in the following locations listed below. A fire alarm system shall consist of detection devices and manual pull stations plus the components and circuits arranged to monitor the system. In new construction, all buildings or portions thereof classified as Use Group A, B, M, I, E, shall be provided with a fire alarm system. Sprinklered Building Exception: In buildings of Use Group B, M, and A protected throughout by automatic sprinklers in accordance with this code shall not be required to be equipped with automatic detectors. Buildings of Use Group E protected throughout by automatic sprinklers installed in accordance with this code shall install smoke detection devices in all corridors, mechanical rooms, boiler rooms, and storage rooms. In new construction, all buildings of use group classification ofR R I and R 2 shall be provided with a "fire alarm system" as defined above to include smoke detection in the following areas: Exception: Single family attached and detached homes, manufactured and town homes. a. All corridors. b. All storage rooms not within the individual dwelling unit. c. All boiler and mechanical spaces. d. At the top and bottom of all required exit enclosures. Hardwired single station smoke detectors with battery back-up shall be installed and maintained in the following areas: Use Group R, in all sleeping areas including bedrooms, each level including basements, and in the vicinity of each sleeping area. 16 Where more than one detector is required to be installed within an individual dwelling unit, guest room or suite in a Use Group R occupancy, the detectors shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit, guest room or suite. All required hardwired smoke detectors shall be permanently wired into the electrical system and shall not serve any other appliances or circuits. All required hardwired smoke detectors shall be photoelectric. All new and existing required fire alarm systems shall be monitored by an approved central station and transmit both fire and trouble signals. Combination burglar and fire alarm systems, stand alone automatic dialers (including digital), and radio transmitted monitoring signals shall be prohibited in all new or existing use group classifications except single family attached and detached homes, town homes and manufactured homes. Exception: Single or multiple station smoke detectors shall not be required to be monitored. All buildings or structures thirty five feet (35') in height and/or four (4) stories or greater shall be provided with a fire alarm system in accordance with this code and as specified hereafter and those requirements set forth in article 907.2.12.1,907.2.12.2, 907.2.12.2.1,907.2.12.2.2, 907.2.12.2.3 of the International Building Code, 2000 edition. Automatic smoke detectors suitable for the application shall be installed in the following rooms: mechanical equipment; electrical transformers; telephone equipment; elevator machine room, and similar rooms. bo A voice signaling system shall be installed capable of providing one-way and two-way Fire Department communication. Exception: Open Parking Garages. (1) The two-way Fire Department communication system shall provide two-way communication between the fire command station and the following terminal areas: elevators, elevator lobbies, exit access corridors and exit stairways at each level. (2) A one-way public address communication system for the transmission of emergency directions and designed to be 17 heard by all building occupants shall be operable from the central control station. It shall establish on a selective or general basis to the following terminal areas: elevator lobbies, exit access corridors and exit stairways, office areas exceeding one thousand (1,000) square feet, dwelling units; and hotel guest rooms and suites. The two-way Fire Department communication system can be combined with the one-way system. A fire command station shall be provided in accordance with NFPA 72, section 911.1 of the International Building Code, 2000 edition. Exception: Open parking garages. Existing Buildings: In existing structures when an automatic fire alarm system would be required if new, then an automatic fire alarm system shall be provided throughout the building when: The fire area is increased regardless of the square footage. For the purpose of this Section, a "fire area" shall be defined as those areas bound by masonry or concrete firewalls constructed in accordance with Section 705 of the International Building Code, 2000 edition. There is a change in use group classification as outlined in the International Building Code, 2000 edition. Additions, repairs, alterations, remodeling in excess of fifty percent (50%) of the valuation of the property; There is an addition to the structure regardless of square footage of the addition. Exception: Covered porches or stoops. Fire Alarm Panel Location And Type: The fire alarm panel capable of performing all necessary functions shall be easily accessible and visibly located within ten feet (10~) from the Fire Department entrance into the building. Because of the number of alarm devices, size of the building and/or hazards associated with the building, the Fire Official may require an addressable fire alarm panel. All new and existing fire alarm control panels shall be provided with written operating instructions to perform the necessary features of the fire alarm panel. The operating instructions, a complete fire alarm zone map, and other applicable information shall be framed and mounted within one foot (1') of the fire alarm 18 Fo control panel. Building contact phone numbers shall be provided inside the alarm panel. All new and existing buildings containing an automatic detection system shall be provided with sufficient zone maps for Fire Department use when required by the Fire Official because of the building's size, interior configuration, hazard, or unique situations. Additional zone maps may be required to be posted or bound in a notebook form. Alarm Activation: Activation of the fire alarm shall produce evacuation signals with audible and visual signals in accordance w/th the International Building Code, 2000 edition and NFPA 72. Zones: Each floor level and tenant space shall be zoned separately and a single zone shall not exceed ten thousand (10,000) square feet. The length of the zone shall not exceed one hundred fifty feet (150') in any direction. A zone indicator panel shall be provided in an approved location in accordance with this code. The visual zone location shall not be canceled by the operation of an alarm silence switch. When provided, the following alarm initiating devices shall be zoned separately: 1. Smoke detectors. 2. Duct detectors. 3. Sprinkler water flow devices. 4. Manual fire alarm device. 5. Other approved types of fire detection devices and/or suppression systems. Exception: Automatic sprinkler system zones shall not exceed the area specified in NFPA 13. Duct Detectors: All required duct detectors shall be provided with a remote testing and reset device located five feet (5') above the finished floor directly below the duct detector. All new and existing HVAC equipment containing smoke detection devices shall be labeled to correspond to the fire alarm annunciation displayed at the alarm panel. The labels shall be clearly visible from the floor level. Corresponding two-inch contrasting numbers shall also be permanently provided on each rooftop unit. In buildings protected throughout by automatic Sprinklers, the duct detector activation may send a supervisory signal to the building's fire alarm panel. (Ord. 4894, 10-7-1997) G. Fire pumps shall be required to be equipped with a low suction alarm. 19 The alarm must sound an audible bell and transmit a signal to a UL listed central station when the available municipal water pressure drops to 20 psi. The alarm shall continue to sound and send a signal until the situation has been corrected. Each low suction aIarm must be provided with a low suction alarm panel monitored by the building's fire alarm system. The low suction alarm panel must be located in the fire pump room in an accessible location. The low suction alarm panel must be monitored by the building's fire alarm system for voltage integrity. The low suction alarm panel must be provided with a visual alarm condition indicator. ALARM SYSTEM ACCEPTANCE TESTING. All required acceptance testing shall be conducted in the presence of the Fire Official. At the time of acceptance testing, the contractor shall provide a job copy of the approved installation drawings for use during the testing. A minimum of forty-eight (48) hours notice to the Fire Official is required. The installing contractor shall furnish all necessary equipment with a sufficient number of personnel to conduct the tests. This shall include, but not be limited to, two-way radios, ladders, sound level measuring equipment, water flow measuring equipment and applicable testing documents. A written record of completion shall be provided to the fire official prior to scheduling the acceptance testing. When the National Fire Alarm Code requires a battery load test, the fire official shall witness the test. The battery load test shall be conducted and approved by the Fire Official prior to the issuance of a certificate of occupancy. 24.206: KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION SYSTEMS: Access Doors. UL listed duct access doors shall be provided in areas required to install an access panel. Hinged Fans. Kitchen exhaust fans shall be provided with a UL listed hinge assembly. 20 C. Residential type range top hoods and fire suppression systems: Where permitted. A residential range top fire suppression system may be permitted in lieu of a Type I hood and suppression system above stovetops used in such a manner that does not produce significant amounts of grease-laden vapors or smoke as determined by the fire official. Residential range top fire suppression systems and hoods may be considered as an acceptable alternative to a Type I hood and fire suppression system in occupancies where the use is not intended for the selling of food products to the general public such as apartment complex clubhouses, schools, offices, churches, or industrial break rooms. ao If a fire alarm system exists in the building, the residential range top fire suppression system must be monitored by the fire alarm system. The cooking appliance (stovetops) are four-burner or less and not exceeding 36" in width. Establishments approved for the installation of a residential range top fire suppression system must be equipped with a Class K rated fire extinguisher. Residential range top fire suppression systems are required to be UL Listed. Residential range top fire suppression systems must be capable of providing utility shutoff upon system activation. Detail documentation meeting the installation requirements must be submitted for review and approval by the fire official prior to installation. A written analysis of the production of grease-laden vapors shall be submitted to the fire official in order to determine if the quantity of grease produced is minimal enough to permit a residential type suppression system in lieu of a type I hood and suppression system. The fire official may at any time require the written analysis to be performed after the system has been installed. In those cases where the cooking operation or quantity of grease-laden vapors has changed since the initial installation, the fire official may require a type I hood and suppression system. SECTION 6: Chapter 24, entitled "Fire Prevention Code" of the Village Code of Mount Prospect shall be amended by deleting Sections 24.501 through 24.504 in their 21 entirety and inserting new Sections 24.501 through 24.504 which shall be and read as follows: 24.501: DEACTIVATION OF FIRE SUPPRESSION/FIRE ALARM/OTHER ALARM SYSTEMS: It shall be unlawful for any property owner or occupant of the property to disconnect, deactivate, and/or remove any automatic sprinkler or other fire suppression system or remove any emergency notification, or fire alarm system from service without first having given written notification and received written approval of the fire chief or his designated representative. In the event it is determined by a fully designated representative of the fire chief, in face-to-face situation, that the system deactivation or removal from service is necessary, a written confirmation shall be submitted by the property owner or occupant to the fire chief within twenty four (24) hours of such deactivation or removal from service. (Ord. 4513, 1-5-1993; amd. Ord. 4894, 10-7-1997) 24.502: PENALTY FOR RESPONSE TO FALSE ALARMS False alarms shall be defined as set forth as follows in Section 24.503 of this article. If the fire department responds to more than five (5) false alarms or system malfunctions within a calendar year to the same premises, the property owner or occupant shall pay the village the amounts as set forth in appendix A, division III of this code, within thirty (30) days after the response for which the charge is made. Within five (5) working days after the fire department responds to a false alarm, the fire department shall cause written notification to be given to the property owner or occupant that a false alarm has been charged to the property. In the event that this incident is in excess of the permitted five (5) false alarms within a calendar year, the property owner shall be billed the appropriate amount, as set forth in subsection B of this section. Within fifteen (15) days after the alarm, the property owner or occupant may file with the Fire Chief a written request to reconsider whether such alarm was avoidable. Such request shall include all facts upon which the property owner or occupant bases his opinion. Within ten (10) days after receipt of a written request for reconsideration, the Fire Chief or his designated representative shall determine whether or not the alarm shall be classified as a false alarm and then notify in writing the property owner or occupant of his decision. If it is the determination of the Fire Chief that the alarm shall be classified as a false alarm, the Fire Chief shall notify the prOperty owner, in writing, of his decision and the appropriate charge, as set forth in subsection B of this section, shall be paid in full within thirty (30) days following such 22 notification. (Ord. 4513, 1-5-1993; amd. Ord. 4894, 10-7-1997; Ord. 5189, 5-15- 200I) 24.503: DEFINITIONS: For the purpose of this Article, the following words and terms shall have the following meanings: ALARM SYSTEM: Any device installed for the purpose of alerting others to a fire or other emergency. (This includes but not limited to elevator, and medical alert alarms.) AUTOMATIC TELEPHONE ALARM: A telephone device or telephone attachment, which automatically relays a prerecorded message to report a fire emergency by means of a telephone line, which terminates upon a central switchboard. FALSE ALARM: An alarm system as defined above activated by any one or more of the following causes: A. Mechanical failure; B. Malfunction of the alarm system; C. Improper installation or maintenance of the alarm system; D. Wilful or negligent act of a person; Any other cause not related to a fire emergency; provided, however, that any alarm activated by natural causes including, but not limited to, tornadoes and severe windstorms, or by malicious acts of persons not under the direction or control of the property owner or occupant shall not be considered a false alarm. MUNICIPALITY: Whenever the word "Municipality" is used in this article, it shall be construed to refer to the Village of Mount Prospect. (Ord. 4513, 1-5-1993; amd. Ord. 4894, 10-7-1997) 24.504: PENALTIES Each type of alarm activation shall be categorized by the type of alarm (i.e., elevator, medical emergency, fire). The number of offenses shall be separated by alarm category for the purpose of accessing penalties. Unless specified elsewhere in this article, the penalty for violating the provisions of this article shall be an amount set forth in Appendix A, Division III of this code, for each offense. (Ord. 5189, 5-15-2001) 3 SECTION 7: That this ordinance shall be in full force and effect from and after its passage, approval and publication in pamphlet form in the manner provided by law. AYES: Hoefert, Lohrstorfer, Skowron, Zadel NAYS: None ABSENT: Corcoran, Farley PASSED and APPROVED this 17th day of June, 2003 ~na K.'Wilks, Mayor Pro Tem' ATTEST: Velma ~.~Lo~we~ge C~l~k~°~'~'~