HomeMy WebLinkAbout0141_001MINUTES
COMMITTEE OF THE WHOLE
JUNE 13, 1989
I. ROLL CALL
The meeting was called to order at 7:34 p.m. Present at the meeting were:
Mayor Gerald L. Farley; Trustees Ralph Arthur, Mark Busse, Timothy
Corcoran, Leo Floros, George Van Geem and Theodore Wattenberg. Also
present were John Fulton Dixon, Village Manager, and David M. Clements,
Director of Planning and Zoning. Representatives of local newspapers were
also present.
II. MINUTES
The Minutes of the Committee of the Whole meeting of May 23, 1989 were
accepted and approved.
The following residents addressed the Committee, and objected to McBride's
on Rand Road, specifically, noise from the establishment, speeding cars and
location of dumpsters:
Kathy Lee, 700 Windsor; Douglas and Laura Huff, 708 Windsor; and Michael
Wexler, 606 North Windsor.
These residents submitted a petition with 35 names of other residents
objecting to conditions at McBride's.
They eked that the beer garden be eliminated, that employees dump bottles
during the day, that durapsters be reheated and signs pasted advising patrons
that there are homes nearby. They also asked for a Neighborhood Committee
to meet with Village staff and McBride's ownership.
Mayor Farley suggested that these homeowners, the Police Department, and
management of McBride's meet to discuss these issues. Manager Dixon stated
that he would arrange this meeting.
A representative of the JayCee's advised the Committee that the Farmers
Market would operate downtown from July 16 to October 15.
Mayor Farley thanked the JayCees's, and read a proclamation honoring the
Mount Prospect J;yCe's and declaring St Jude's Hospital Day in Mount
Prospect.
Committee of the Whole Minutes June 13, 1989
Mayor Farley introduced this item, and Don Weibel, Chairman of the
Constitutional Bicentennial Commission. Mr. Weibel discussed the evenings
activities.
A Cub Scout Den presented and posted the colors. The Pledge of Allegiance
was recited.
The Choir from Trinity Methodist Church led the singing of the National
Anthem.
Earl Lewis presented a narrative for the Parade of Flags, a review of 13 flags
presented to the Committee.
The Choir sang "America the Beautiful."
Mayor Farley thanked Mr. Weibel and the Commission for their presentation.
Mayor Farley introduced this item to the Committee on the appropriate way
to display the U. S. Flag. The Committee unanimously approved the
Resolution.
V1. REYIEW OF REQI= FOR, PROPOSAL, EQR EA
D,Q)5M
STUDY Q)YN, RLKING
Mayor Farley introduced this item to the Committee, and Dave Clements
provided a summary of, the proposed Request for Proposal. He stated that
this was fora corridor study of major land -uses along Emerson Street. Mr.
Clements stated that this corridor study, along with a parking inventory
completed by the staff last summer, would provide a complete look at
downtown parking.
A representative of First Chicago Bank and the Mount Prospect Library
indicated support of the study.
The Committee generally discussed this item. The proposed corridor study
was complete, but several Board members believed the Request for Proposal
should be expanded to include the entire Central Business District. Trustees
Arthur and Van Geem felt like the scope of the study should be expanded.
Trustee Corcoran inquired about an approximate cost.
-2-
Committee of the Whole Minutes
June 13, 1989
After discussion about the impact, scope and value of the parking study, the
Committee directed staff to revise the Request for Proposal to provide for an
Alternative A Downtown Parking Study and an Alternative B Emerson Street
Corridor Study.
VII. ADJOURNMENT
DMC:hg
There being no further business to come before the Committee of the Whole,
the meeting was adjourned at 9:15 p.m.
-3-
Respectfully submitted,
DAVID M. CLEMENTS,
Director of Planning and
Zoning
Village of Mount Prospect
Mount Prospect, Illinois
INTEROFFICE MEMORANDUM
TO: MAYOR GERALD L. FARLEY AND BOARD OF TRUSTEES
FROM: ASSISTANT VILLAGE MANAGER
DATE: JUNE 23, 1989
SUBJECT: PUBLIC SAFETY FACILITY REPORT
The subject of the adequacy of the Village's various public facilities has been the subject
of study and debate for many years. Since 1980, at least four separate studies have been
undertaken by both outside consultants and Village staff. These studies have focused in
varying degrees on individual buildings or Departments and two have been comprehensive
reviews of all Village facilities. These studies can be identified as:
1980 Derning Report - Police Facility
1981 Pairitz Report - Capital Facilities (all public buildings)
1986 Dahlquist Report - Renovation Study (all public buildings)
1986/198" Staff/Donohue Report - Public Works Building
Except for the Public Works Report, little has been done in terms of taking long-range
corrective action.
This current review of the Public Safety Building was precipitated in large part by
recently completed Police Department Accreditation process. As part of the overall
preparation for on-site review, an attempt was made to bring our jail cells up to some
minimum level of compliance with State regulations. That project, which cost $55,188.05,
was presented to the Village Board as a temporary measure at the time. It was
recognized then that further review regarding the facility would have to be undertaken.
Again, during Budget Hearings for the Police and Fire Departments, reference was made
for a need to look at the present condition of the Public Safety Building.
Out of these discussions, the Village Manager created a Staff Committee whose charge
was to issue a report outlining the current status of the Public Safety Building and to
make recommendations for further action. The goal of the Committee has been to make
recommendations that would result in the best possible facility for Police and Fire
operations while at the same time remaining cognizant of the realities of public opinion,
past Board policy and budgetary constraints. To that end, the Committee has focused
on the achievement of two critical elements - functional efficiency and the ability to
accommodate modest expansion.
One of the first tasks undertaken by the Committee was to review existing facility
reports. While methodologies and overall scope may have differed from report to report,
one common element stands out. Each report has come to the same basic conclusions;
i.e., the present Public Safety facility has inadequate space, poor functional layout,
obsolete utilities, minor structural problems and inadequate parking. It was the consensus
of the Committee that another such study would result in little, if any, changes in those
conclusions (for informational purposes, reports from several Departments are included
which outline some of the more obvious Code violations which exist). Rather, it was felt
that there was a need to move beyond this aspect of the problem and develop answers
to the questions previously identified.
While Village staff possesses the requisite expertise to identify Code violations at the
facility, it is notcomfortable with making similar assessments regarding the functional
efficiency and layout of the building.
It is for that reason the Committee felt the most prudent and cost-effective way to
progress would be to solicit input from outside professionals who have extensive
background in assessing the space/need requirements of Fire and Police Departments.
From there, reasoned judgments regarding space requirements and functional layout could.
e made. Past attempts by staff to undertake this type of analysis have met with some
resistance and skepticism from the Board.
This process is not unlike that which was undertaken as part of the Public Works Facility
review. This initial space/need analysis would be a stand alone item that need not
require the Board to make further commitments of a policy or financial nature.
If the Mayor and Board of Trustees concur with the Committee's recommendation,
consultants will be solicited regarding this tyle of review. The information to be derived
from it will be helpful in making the critical judgments necessary in seeking a long-term
solution to the problems of the Public Safety Building.
The Public Safety Facility Committee would be in a position to make a formal
presentation by the time the responses to the RFP had been received. At that time, the
Mayor and Board of Trustees would presumably have all the information they would.
require to make a knowledgeable and well -reasoned decision regarding future action.
Therefore, staff seeks input from the Board regarding the language of the RFP and
direction to solicit responses thereto.
MEJ/rcw
attachments
ONIS
VILLAGE OF MOUNT PROSPECT
REQUEST FOR PROPOSALS: PUBLIC SAFETY BUILDING
Date
Dear
The Village of Mount Prospect is seeking proposals from selected consultants to provide
professional services to assist the Village in analyzing and determining its space and
facilities requirements for the Departments of Police and Fire. This subject is scheduled
to undergo extensive public debate by the Village's elected officials over the next 60-90
days. The consultant's final report and recommendations will be discussed publicly
through a process of energetic examination. The consultant will exercise absolute
professional standards and objectivity.
The Public Safety Building, located at 112 East Northwest Highway, was built in 1945
and originally housed all municipal functions except Public Works. In 1975, the Village
purchased the old " "o, unt ."rospect State Bank building at 100 South Emerson and moved
all municipal functions then at the site, except Police and Fire, to the new location.
Since that time, the building at 1.12 East Northwest Highway has functioned as the
Village's Public Safety facility housing all Police functions (administration/operations) as
well as serving as the main headquarters for the Fire Department administrative staff and
as its main Fire Station (Station 1). The Fire Department also operates two other Fire
Stations; one of which houses the Bureau of Fire Prevention.
The building at 11.2 east Northwest Highway, as originally constructed, contained
approximately 10,708 square feet. In 1954, an additional 1,440 square feet were added
and in 1961, a second addition added 10,032 square feet. In 1972, the Village acquired
the two story frame building immediately to the west of the main structure. It contains
4,100 square feet and currently houses an 11 -man Investigative Unit, locker room and
shower facilities, roll call room, photo processing lab and miscellaneous storage. It is
commonly referred to as the "Police Annex."
Directly behind the Annex is a concrete block building (75'x22') containing 1,650 square
feet and housing shared storage for Police/Fire equipment as well as a shared training
oom. Each of these buildings stands alone and is not physically connected to the other
buildings.
The balance of the site consists of a 68 space parking lot with modest east side and
south front yards.
-- lia-i
Total building area is approximately 27,930 square feet. The entire site contains 53,360
square feet on an irregular shaped lot.
The Mount Prospect Police Department has a current authorized strength of 70 which
includes one Police Chief, two Deputy Chiefs, four Commanders, nine Sergeants, seven
Investigators, two Tactical Officers and 35 Patrol Officers. The Department also has 20
full-time civilians and 20 part-time civilians. Total Departmental strength including full
and part-time employees is 110.
The Police Department has two Divisions; administration and field operations. Within
those Divisions there are components that include the following: Patrol Section,
Investigative Section, Adult Investigative Unit, Youth Investigative Unit, Tactical Unit,
Records Section, Auxiliary Services Section and Crime Prevention Unit.
The Department utilizes 18 vehicles and operates on a 24-hour a day, seven day a week
program. Calls are dispatched to the vehicles from a central dispatch facility :located in
Arlington Heights. Firearms training takes place in the Police Department range located
in the basement of Fire Station #2 at Golf and Busse Roads. The reports generated
from an average 30,000+ calls for service per year are handled by a computerized
records section located in the Public Safety Building.
The Fire Departmeat ha:�' a current authorized strength of 72 which includes the Fire
chief, two Deputy Chiefs, four Captains and nine Lieutenants. Total Departmental
strength includes three civilian fire prevention personnel, three full-time clerical
personnel, two civilian mechanics and 20 paid -on-call Firefighters.
From the Public Safety Building, the Fire Department provides a full range of emergency
services which includes fire suppression, emergency medical service; hazardous material
response and emergency service and disaster operations. The fire Department also
maintains a back-up Communication Center at this location.
The Fire Station located at the Public Safety Building (Station #1) operates at a full
shift strength of seven (7) ;Firefighters including shift command staff, one engine, one
aerial ladder truck, one ambulance and a shift command vehicle. Also located at this
Station are a reserve squad vehicle and pumper.
While housed together, the Police and Fire Departments operate as autonomous entities
and there are no current plans to combine the two Departments into a unified operation.
There is a growing recognition among the Village's elected officials that the present
Public Safety Building may be functionally inadequate and as a result could be causing
operating inefficiencies in both the Police and Fire Departments.
Over the past several years, various studies have been undertaken by both Village staff
and outside consultants looking at both the functional layout of the building and its
structural integrity. All have come to the same basic conclusion that the existing building
has inadequate space, poor functional layout, obsolete utilities, minor structural problems
and inadequate parking.
Several options appear to be viable:
1. Rehabilitate and expand the existing Public Safety Building for continued
use by both Police and Fire Departments.
2. Rehabilitate and/or expand the existing Public Safety Building for use by
one of the Departments along with the construction of a new facility (or
the rehabbing of an existing structure) for the other Department.
3. Construction of a new, combined facility at a suitable location.
presentThe
correctlyanalysis to benefits of each alternative. Therefore, it is in the
Villagebest interest of the professional,independent
perform this work.
The consultant will assist the Mayor, Board of Trustees and staff in assessing existing
information, review work already performed by staff, develop
1i analysis as
deemed necessary by the consultant,•comprehensive
viable options and prepare a final report to present publicly to the Village Board.
At the minimum, the consultant shall:
1. beet with appropriate Village officials and staff to review overall objectives;
discuss the consultant's methodology and timetable; and solicit any
additional information required for the project.
2. Review existing reports and data concerning the Public Safety Building for
completeness and accuracy of base data as well as develop any additional
information needed to undertake the task.
3. Interview appropriate Police and Fire personnel to examine and understand
their respective operations, facilities and procedures, as well as:
a) Determine the operational space requirements for each Department.
b) Determine optimum parking requirements for staff and visitors.
c) Determine future space needs based upon the potential future growth
of the Police and Fire Departments.
4. Develop a preliminary program of space requirements and schematic
layouts. This should include:
a) Efforts to minimize overall space requirements by combining common
functions such as reception areas, restrooms, conference rooms,
training facilities, etc., while maintaining peak operational efficiency.
b) Develop a program of all space requirements for operational areas.
c) Calculate space requirements for public areas, circulation patterns,
mechanical rooms, offices, living quarters, restrooms, etc., and
incorporate these into the written program of space requirements.
d) Prepare schematic block layouts of proposed site plans and floor
plans.
e) Identify handicapped accessibility requirements.
5. Prepare alternate solutions to each of the viable options listed previously,
or any other option deemed appropriate by the consultant.
6. For each option prepare a preliminary written report presenting
recommendations on the relative feasibility and suitability of the alternate
solutions including:
a) Prepare necessary qualitative and quantitative comparisons among and
between the presented alternate solutions and translate that data into
cost/benefit comparisons understandable from the taxpayer's point
of view as well as operating costs savings to the Village.
b) Prepare preliminary cost estimates for:
1) Site acquisition costs (if any).
2) Site improvement costs (including costs for demolition).
3) Professional fees.
4) Building costs.
5) Furnishings and equipment costs.
6) Temporary facility costs.
7. Develop a specific recommendation and justify that recommendation and
cost/benefit analysis.
8. Prepare no less than 30 copies of the final report and recommendation
including all documentation supporting that recommendation.
9• Present the final report to the Mayor and Board of Trustees at a public
meeting (anticipate that a second meeting will be required in order to fully
respond to questions raised at the first meeting.
The consultant's work should produce an end product of sufficient quality and clarity to
assist the Mayor and Board of Trustees in determining the best alternative available.
Time is of the essence in completing this work. The final report with recommendatio
must be presented to the Mayor and Board of Trustees no later than (60-90 days aft
the awarding of the contract). Subsequent review meetings will occur as needed. I
The consultant shall submit fifteen (15) copies of their proposal to the Village Manager
no later than (30 days from the date of solicitation).
The proposal shall include the consultant's approach to planning, organizing and
managing such a project including resumes of key personnel to be assigned to the project
together with a work schedule allocating their assignments and hours to the various
elements of the work plan. References and experience with similar projects must be
included. Of special consideration to the Village is your firm's direct work experience
with evaluation of redevelopment and/or re -use of existing Police and Fire facilities.
The consultant may add items to the SCOPE OF WORK which are required or desired
in the opinion of the consultant. Each such added work element should be identified
in sufficient detail to allow this Village to evaluate its necessity and benefit. Each such
work item should also include an estimate of cost associated with its inclusion in the
project.
The proposal will identify the consultant's expected number of hours assigned to each
major task, the average hourly compensation payable for each task and a total "not to
exceed" figure for the entire project.
Acceptance of the consultant's proposal by the Mayor and Board of Trustees is NO
GUARANTEE of subsequent design projects or further work by the consultant. The
consultant shall estimate the costs of this planning project as a single and complete
assignment.
A J
If the Village requires work beyond the scope of services agreed upon between the
consultant and Village, additional compensation will be made at the hourly rate normally
charged by the consultant for the assigned individual. Therefore, the consultant will
specify hourly chargeable rates for the key personnel assigned.
The proposal should include an example of the contract proposed between the Village
and the consultant.
The Village will make one interim payment to the consultantduring progress
after receipt of a properly documented•bours worked and eligible
expenses. payment delivery acceptanceand
report.the final
Proposals should be addressed to: Mr. John Fulton Dixon, Village Manager, Village of
Mount Prospect, 100 South Emerson Street, Mount Prospect, Illinois 60056.
JFD/rcw
enclosures
Sincerely yours,
JOHN FULTON DIXON
Village Manager
Ft P; I 'it i
Village of Mount Prospect
Mount Prospect, Illinois
INTEROFFICE MEMORANDUM
TO: Chuck Bencic, Inspection Services Director
FROM:D
Ad an Jakes, Building Coordinator
DATE: June 6, 1989
SUBJECT: INSPECTION OF PUBLIC SAFETY BUILDING AND
ANNEX BUILDINGS
Pursuant to your -request, an inspection was conducted June S, 1989
by Dan Jakes, Bill Amundsen and Mike Frontzak. As a general overview,
all three buildings are antiquated, deteriorated and presents severe
life safety concerns. Major areas of concern listed but not limited
to:
- Capital Development Accessibility Standards Handicapped
Requirements are not met.
- Poor ventilation and lighting conditions.
- Over crowding of office space, occupant per square foot
is in violation.
- Dead end corridors.
- Improper emission control ref. OSHA Standards within bay
areas (F.D. )
- Improper exiting and location of exits.
- Structural deficiencies on the west exterior wall may exist
due to tension bars in the wall. Resting location is unknown.
- Code specifies building of 10,000 sq. ft. must be sprinklered.
- Annex buildings were not designed for i'cs present use.
Intensification of original use group increases life safety
hazards.
- Corridor width in violation.
- Inadequate means of egress exists.
TO: Chuck Benc , Inspection Services Director
FROM: Dan Jakes, Building Coordinator
DATE: June 6, 1989
SUBJECT: INSPECTION OF PUBLIC SAFETY BUILDING AND ANKX BUILDINGS
Page 2
The following itemized lists are discrepancies noted during the inspection:
ELECTRICAL•
- Outside: Overhead service cable frayed and worn. Should
be replaced. Constitutes a fire hazard.
- Boiler Room: Feeder cable to automatic transfer is old and
frayed, should be replaced.
- Boiler Room: Panel "A" (west wall) change panel, interior.
Cannot find replacement breakers. Upon failure, a hazard
exists.
- Second Floor: Improper lighting due to old fixture wiring
which would burn.
ATTIC:
- BX violates code. To be replaced.
.. Poor housekeeping, miscellaneous electrical covers missing.
SECOND FLOOR:
- Electrical panel in hall antiquated breakers; cannot be
replaced.
- No emergency lighting or backup on exit lighting exists.
EAST BAY:
- Wiring in lighting old and worn. Only one half of the lights
are being utilized. Same condition in center bay and west
bay.
- Bay areas also consist of open wiring/door controllers.
POLICE DEPARTMENT:
- Antiquated fixture wiring
TO: Chuck Bencic, Inspection Services Director
FROM: Dan Jakes, Building Coordinator
DATE: June 6, 1989
SUBJECT: INSPECTION OF PUBLIC SAFETY BUILDING AND ANNEX BUILDINGS
Page 3
ANNEX BUILDING:
- First Floor, inadequate exit and emergency lighting.
- Basement: BX must be replaced; no switch at the entrance,
open electrical boxes.
- Between Annex and Fire Department, seal tite run overhead
400 AMP service feeding building not adequate, more power
needed, which will cause a need to change main panel and
sub -panels in building.
- Complete update of electrical components required of all
three structures.
PUBLIC SAFETY BUILDING:
The general condition of the boiler and all heat water piping is
questionable. All exposed pipe is wrapped. There is the possibility
that the pipe wrap is asbestos.
All electric switch gear and service entrance are in the boiler room.
This is a hazardous combination.
Access to the attic area is by a very unstable pull-down stair. The
hallway is wide, and no hand rail exists except for the top 1/2 of
the unit. Loss of balance would mean a fall. Bringing tools and
equipment to the attic area is very difficult.
Electric wiring in the attic area is totally inadequate and subcode.
Considerable B -X wiring, lamp cord wiring and open junction boxes
exist.
Portions of old roofing exist, some of which is possible asbestos.
Access to portions of the attic area is very hazardous over temporary
"bridges" and steps. Some, steps are concrete block, some wood. Some
bridges are pieces of roof rafter of differenct lengths nailed to
roof framing.
Roof framing in the center portion of the building is in question.
The west portion of the new roof is wood truss. The center area of
roof framing was jury-rigged between the trusses and old existing
pitched roof. An access opening was cut by removing two (2) rafters,
cutting sheathing and roofing and removing a portion of the sheathing.
TO: Chuck Be c, Inspection Services Directo
FROM: Dan Jakes, Building Coordinator
DATE: June 6, 1989
SUBJECT: INSPECTION OF PUBLIC SAFETY BUILDING AND ANNEX BUILDINGS
Page 4
The opening was not headered off and supporting rafters not doubled.
The new rafters bridging the center roof area are very poorly cut
to fit, are not structurally connected to the old existing roof and
add to roof load of the old rafters. The general structural integrity
and weight bearing are in question.
The scuttle opening to the roof is improper and hazardous. The panel
itself is very heavy, there is no type of mechanism to hold the panel
open and it therefore blows shut while in use. Access to scuttle
is by an aluminum ladder resting in place.
In many areas of the building, fresh air and air conditioning are
by window units, in particular in the fire department sleeping
dormitory. Several other office areas are cooled using window units.
This is questionable when considering the quality of the general
building wiring.
The parking garage has no mechanical means of exchanging air quality
when engines are running. The only blowers present are for providing
heat.
The room containing a toilet and a urinal has no exhaust fan.
Concealed areas; between walls, above dropped ceilings and under floor
slabs, are areas where more severe physical problems exist. Heat
pipe supplying hot water, electric wiring and conduit or armored cable
and hot and cold water supply are more than likely in very poor
condition and in need of major maintenance just by virtue of age.
The west wall at both ends, north and south, has been drawn back into
place by use of tension rods. The northwest corner of the parking
garage is showing definate signs of structural ailment by the shearing
off of concrete block just under the second floor. Exterior cracks
are not visible due to recent tuck pointing. The overhead garage
doors are frequently in need of alignment because of building shift.
Lighting in the corridors and some other areas is poor and dim and
antiquated. The fixtures are old, yellowing and inefficient and can
not be replaced because of the very poor condition of the wiring.
The entire second floor is not handicapped access. One ramp leading
from the parking lot to the first floor police area is the only
handicapped access. None of the toilet facilities are handicapped
access.
There appears to be little if any fire stopping within the building.
TO: Chuck 1"� :ic, Inspection Services Direc
FROM: Dan Ja ,4 , Building Coordinator
DATE: June 6, 1989
SUBJECT: INSPECTION OF PUBLIC SAFETY BUILDING AND ANNEX BUILDINGS
Page 5
ANNEX BUILDING:
This building is a converted combination of first floor store fronts
and second floor residence.
The general condition of this structure is poor. Ventilation in this
building is very poor because it is not designed for office use.
The first floor is used as locker rooms and small desk areas. The
second floor was that musty old odor.
The building is not in any way handicapped orientated. All access
is by wooden stairs, even to the first floor.
Electric wiring in this structure is grossly deficient.
The basement is an old cellar type area with low headroom, differing
levels of floor and frequently floods when it rains.
Fire exit signs that exist are not properly placed and show wrong
direction. There is no emergency lighting and little natural light
on the first floor.
The secondary means of egress from the second floor is to an outside
stair that has peeling of several coats of paint. Deterioration of
this type of wooden structure accelerates rapidly. The outside layer
of the door is d' --laminating. The emergency door opener is a
nonconforming paddle type opener rather than the continuous bar type
opener.
A holding or security area behind
with barbed wire. Barbed wire is
the Village.
CONCLUSION:
the building is covered illegally
not permitted for use anywhere in
In the interest of time, if code numbers are required, please advise.
According to 1984 BOCA Building, Mechanical, Fire and Plumbing, a
multitude of violations exist.
DJ:rm
John F. Dixon,;«. Manager
Amundsen,Bill «. «
Les Hanneman, Inspector
Mike Frontzak, Inspector
VILLAGE OF MOUNT" �" SOE
ILLINOIS
INTEROFFICE MEMORANDUM
TO: Chief Edward M. Cavello
OM: Deputy Chief Lonnie H. Jackson
DATE: June 8, 1989
r'
ML pmpd In 04L
SUBJECT: INSPECTION CONDUCTED JUNE 6TH, 1989
PUBLIC SAFETY BUILDING AND ANNEX BUILDING
112 E. NORTHWEST HIGHWAY
1. The building in question does not meet the requirements of the Fire
Prevention Codes or Life Safety Code for it's present use which is categorized
as use group "B" (business) under the BOCA Building and Fire Prevention
Code.
PublicThe Building r officers of Department •
Police Department, •• prisoner• spaces,s -•
firemen and a garage for fire and ambulance apparatus.
DEFICIENCIES NEE11 •" 1 •' UPDATING:
A. A sprinkler, system throughout the building (by Village and
BOCA Code, includingattic•.
B. Emergency lighting needs to be installed in all hallways and
stairwells.
C. Fire stopping throughout (attic, stairwells) and installation of
fire rated doors in all areas.
D. Exhaust emission control of garage area as per OSHA (1991).
E. Exiting requirements and egress to grade (Life Safety Code) not
sufficient (corridors not correct for width and some are dead
end). Approved exits are needed.
F. Electrical emergency generator not sufficient to power
communication and emergency lighting throughout the facility.
Needs upgrading with full automatic controls (Police and Fire).
Ventilation of jail cells.
G. Heat and smoke detection system is inadequate, only covers Fire
Department and jail cells and is not installed in the Police office
and records area, and all other areas in the building and attic.
H. Inadequate ventilation in dormitory, weight area and restrooms.
Ventilation must meet table 1601 of the BOCA Code.
I. Stairwells leading to second floor are not provided with
adequate separation. Stairwells are open, needs closing with
approved fire rated doors.
No fire stopping around any penetrations open chaseways above
ceiling unprotected in certain areas.
Improper exiting from second floor. Current fire escapes lack
structural integrity and do not meet current code requirements
for ,-.
L Inadequate electrical throughout.
M. Exits are not clearly marked.
N. Noted possible structural defects on various load bearing walls,
especially the west wall.. 'Tension tie bars were noted.
O. Hood and duct system in the Fire Department kitchen requires
fixed fire suppression.
The following are general comments pertaining to the annex building:
1. Inadequate exits throughout
2. Exits aze not clearly defined
3. Exits do not discharge to grade level
4. Open electrical boxes and insufficient wiring throughout
5. Open stairwell from first floor to the second
6. Improper alarm detection. Certain areas lack detection. Annunciation
to occupants is questionable.
7. Fire escape leading from second floor is on the verge of collapse. Stairs
may not withstand the weight of an individual.
8. Ventilation throughout the building is inadequate - needs smoke
detection and ventilation, shut down by smoke detection.
9. The basement area has low headroom and is showing signs of water
damage. Heating in the basement is questionable.
The previous mentioned items are only surface items. More violations will become
apparent once walls and ceilings are removed. The el °ca plumbing and heating
supplies that are concealed are more than likely in need of repair by virtue of their
age. This inspection was a general overview of obvious fire protection and life safety
concerns. There appear to be numerous code violations throughout. Due to time
restraints, the specific code sections were not cited.
If any questions arise concerning this location, or if a more in depth inspection is
required, pleasej
Prevention Bureau.
LLonnie Jackson
Deputy Chief
LHJ/sp
cc R. Paul Valentine
File
Village ot Mount Prospect
Mount Prospect, Illinois
INTEROFFICE MEMORANDUM
TO: Assistant Village Manager
FROM: Director Public Works
DATE: June 5, 1989
SUBJECT: Public Safety Building Report
On May 25, 1989, you had delegated certain departments to review
past history of the existing Public Safety building. You had
asked the Public Works Department for the following:
a) Inventory of all remedial work, renovation, rehabbing
undertaken in the last ten years.
b) Presence of asbestos.
c) Current configuration of utilities servicing the site.
Our street superintendent has compiled some data relative to
these issues and, although we do not have records showing exact
dates or times, they should suffice for approximation purposes.
I do not have '- dollars in labor or materials involved in each
process. The �. .ached report is presented by our street superin-
tendent.
Herbert L. Weeks
HLW/td
6-5-89
During the past ten years much remedial work, renovation and
rehabbing was undertaken at the Public Safety building.
In 1980, the movie screen in the courtroom was moved and re-
wired; new pitched roof and antenna was installed. In the Fire
Department bunk room, new ceiling and carpeting was installed.
In the Fire Department lounge area, the skylight was removed and
new ceiling was installed; added new light fixtures over stair-
way. In the Fire Department captain's office, the door frame
was repaired; replaced carpeting; installed new ceiling and
light fixtures. In the Fire Department administrative office,
carpeting was replaced; installed new ceilings and new light
fixtures. Also, split storage roam into air handling room and
storage area, which included repairs to damaged ceiling tile.
Replaced drapery in building and replaced cooling tower with new
condensing unit and chiller.
In 1982, the radio room and lobby were remodeled and new store-
front type doors were installed, along with new signs over the
front and rear doors.
In 1983/84, all windows throughout the building were replaced.
In 1985, the offices of the police chief and the secretary were
remodeled and new carpeting was installed.
In 1987, new carpeting was installed in the Fire Department
administration office and hallway; tile was replaced in the
upper hallway by the south stairwell; and we replaced the front
concrete apron.
In 1988, the building was tuckpointed, the gutters on the east
half of the building were replaced, and the jail cell area was
remodeled.
Over the past ten years, smaller remodeling projects were also
undertaken, including replacement of various equipment and fur-
nishings:
The conference room, small office space and Deputy Daley's
office were remodeled;
installed -refurbished, and a new sound system was
property
washroomroom, jail cells and
remodeled -garage; the Fire Department kitchen was
photo
dividedroom was converted into a storage room. the second' floor custodi-
al closet was _«_
Pressor, hot water heater and air conditioning chiller were
replaced; and new blinds were installed.
The Fire Department installed new garage doors.
Asbestos is present in various areas of the Public Safety build-
ing including the following:
the floor tile in the jail cells
copier/fan area
lunch room, second floor
pipe wrap in boiler room
all elbows on heating and cooling water pipes
exhaust duct above boiler
Current configuration of utilities:
Edison's service to building - 400 amps
Main disconnect - 600 amps
Electrical is an auto transfer switch for emergency power
rated at 400 amps
Main distribution panel is rated at 120/208 v, 800 amps, 3
phases with 15 subs.
3 sub panels in boiler room: one 100 amps, 2 100 amps
1 sub panel in records - 60 amps
2 sub panels in Fire Department apparatus area - 200 and
100 amps
2 sub panels on second floor - 200 amps each
Draw 160 amps when all air handlers, compressors and con-
denser fans are running per plate rating.
Draw 20 amps on window air conditioners.
2" water service
4" gas service
Marked/noticeable deficiencies
Northwest corner of building is sinking.
Building settling by stairway to Fire Department.
Cloth electrical wire is dry and brittle; some is bare, and some
is not in conduit.
Aluminum wiring in transfer switch is not acceptable and should
be replaced; overheating and it has been subject to fire when
panel overheated.
Plumbing supplies are rusting through and are buried in walls
and ceiling.
waste lines will not allow further addition of washroom facili-
ties. In many cases, cleanouts are not existing or are unus-
able due to many building additions and alterations.
Many light fixtures are obsolete and plastered into ceiling. To
remove them would require knocking out plastic and, in some
cases, extensive rewiring.
First floor heating and cooling was an add-on to original build-
ing and is not designed for present floor plan.
First floor has several layers of ceilings and many different
walls; some floor to ceiling, some floor to decking of second
floor.
Building does not have a fire sprinkling system, nor complete
alarm system, nor washrooms for the handicapped (very costly to
install).