HomeMy WebLinkAbout8.1 Motion to Accept Bid for Booster Station 5 East Tank Rehabilitation6/5/2019 BoardDocs® Pro
Agenda Item Details
Meeting Jun 04, 2019 - REGULAR MEETING OF THE MOUNT PROSPECT VILLAGE BOARD - 7:00 p.m.
Category 8. VILLAGE MANAGER'S REPORT
Subject 8.1 Motion to accept bid for Booster Station 5 East Tank Rehabilitation in an amount not to
exceed $511,390.
Access Public
Type Action
1,referred Date Jun 04, 2019
Absolute Date Jun 04, 2019
r--iscal Impact Yes
Pollar Amount 511,390.00
0 1W 0 a
Budget Source Water and Sewer Enterprise Fund
Recommended Action Accept the lowest -cost, responsive bid for the Booster Station 5 East Tank Rehabilitation Project
as submitted by V&T Painting, LLC of Farmington Hills, MI in an amount not to exceed
$511,390.
Public Content
Booster Pumping Station 5 is a potable water pumping facility with two (2) 1 -million gallon, ground -level, welded steel
water storage reservoirs situated at 112 East Highland Street. These tanks ("north" and "east" tanks), in conjunction with
their adjacent booster pumping station, help satisfy peak water demand and fire flow requirements. The attached
map depicts this facility.
These tanks are two (2) of seven (7) in the Village -owned water distribution system. In total, these tanks provide 8.8
million gallons of water storage capacity. The Village"s average daily demand for water is 3.5 million gallons.
Each of these tanks is routinely inspected by a qualified engineer to assess structural condition, corrosion control, coating
adhesion, and safety compliance.
The east tank at Booster Station 5 is slated for rehabilitation this year. The other tank at this facility, the north tank, was
repaired and recoated last year (2018).
Booster Station 5's east tank was inspected in 2017 by engineers from Tank Industry Consultants (TIC) of Indianapolis,
Indiana. TICs, complete report is attached (see Addendum 1). This tank was originally constructed in 1966 and last
rehabilitated in 1999.
In summary, the TIC report finds that the tank requires, at minimum, a bare -metal blast and recoat of the wet interior, a
high pressure wash of the exterior followed by spot steel repairs, safety equipment upgrades, and a topcoat of the exterior
r.urface (base bid).
The bid documents also included three (3) optional items. These optional items are a bare -metal blast and recoating of the
exterior surface (Alternate 1.a), partial replacement and seam -welding of interior rafter beams (Alternate 1.b), as well
as complete replacement and seam -welding of interior rafter beams (Alternate 1.c).
https://go.boarddocs.com/il/vomp/Board.nsf/Private?open&login# 1/3
6/5/2019
BoardDocs® Pro
To facilitate this work, a detailed set of technical specifications and bid documents were prepared by Burns & McDonnell of
Downers Grove, Illinois, the Village's engineering consultant for this project. In addition to preparation of bid documents
and specifications, Burns & McDonnell will also monitor and inspect the proposed contractor's work A complete set of the
bid documents is attached. The project is expected to last 6-7 weeks.
The bid documents were sent to several area firms with experience in water reservoir rehabilitation projects. The work was
also publicly advertised as required.
3fLaMM.M
On May 13, 2019, bids were publicly opened and read aloud as required by Village Code. Five (5) bids were submitted.
The results - as follows:
All bids were reviewed to ensure that the documents had requisite signatures and appropriate bid security. A
bidders properly submitteded documents,and signatures.
The lowest -cost, responsivebidder is V & T Painting of • •Michigan.i, T Painting has notperformed work
existingfor the Village in the past. However, the firm provided an extensive list of completed contracts that are similar to this
proposed project's scope of work. Staff reached out to five (5) references. All indicated that V&T performed quality work,
completed tasks on schedule, and completed work under budget. It is the opinion of staff that V&T Painting is qualified to
successfully complete this proposed project.
The roof rafter system on r joined to the steel• • plates with spotwelds.
spaces between the spot welds are filled with sealant to prevent water intrusion and to limit the onset of corrosion.
Unfortunately, this roof system is prone to corrosion over time due to difficulties inherent to applying sealant to thousands
of of • jointsat ••! angles. To correct this problem,and reduce structural••corrosion, staff
(replacerecommends replacing all interior roof rafter beams and continuously welding all the rafter/roof plate joints instead of
applying sealant. A welded seam is considerably more effective at resisting water intrusion and corrosion.
Staff recommends that the project award to include the base bid and alternative 1.c ((Base Bid) $401f900.00 + (Alternate
'. $63,000.00 = $464,000.00). Staff is als• requesting a 10%• • ($$46,490.00) to address
of • - --n issues or quantity variances• • they arise. The total recommended project $511,390.00
($464,000 recommended award 1% contingency of $46,,490-00).
1. Accept the lowest cost, responsive bid to rehabilitation a 1 million gallon water storaget n (east tank) at Booster
Station 5.
2. Action at discretion of Village Board.
MM • 71 -1 r4 •i . f
Staff recommends that the Village Board accept the lowest -cost,, responsive bid for the Booster Station 5 East Tank
Rehabilitation P• submitted by V&T Painting, LLC of ! !n Hills, MI in an amount notto exceed $511,390.
https://go.boarddocs.com/il/vomp/Board.nsf/Private?open&login# 2/3
Alternate
Alternate
Recommended
• •r
1.a
1. b
Alternate 1.c
Total(Base
Bid
V&T Painting, LLC
$401,900.00
$90,,000.00
$48,,000.00
'►• 111 /1
"4 •4 •11 11
- •,
$310f535.00
$$154,050.00
$226f310.00
$536f845.00
Worldwide Industries Corp.$363f725.00
$ 120.00
$98f721.00
$190,410.00
$554f 135.00
Era Valadivia Contractors$439f8OO.00
J$125f000.00
111 11'
$247,000.00
'686 i11 11
Services,Utility •
$493f7OO.00
1$305flOO-00
$337.,200.00
'.4+• •11.11
$983f300-00
All bids were reviewed to ensure that the documents had requisite signatures and appropriate bid security. A
bidders properly submitteded documents,and signatures.
The lowest -cost, responsivebidder is V & T Painting of • •Michigan.i, T Painting has notperformed work
existingfor the Village in the past. However, the firm provided an extensive list of completed contracts that are similar to this
proposed project's scope of work. Staff reached out to five (5) references. All indicated that V&T performed quality work,
completed tasks on schedule, and completed work under budget. It is the opinion of staff that V&T Painting is qualified to
successfully complete this proposed project.
The roof rafter system on r joined to the steel• • plates with spotwelds.
spaces between the spot welds are filled with sealant to prevent water intrusion and to limit the onset of corrosion.
Unfortunately, this roof system is prone to corrosion over time due to difficulties inherent to applying sealant to thousands
of of • jointsat ••! angles. To correct this problem,and reduce structural••corrosion, staff
(replacerecommends replacing all interior roof rafter beams and continuously welding all the rafter/roof plate joints instead of
applying sealant. A welded seam is considerably more effective at resisting water intrusion and corrosion.
Staff recommends that the project award to include the base bid and alternative 1.c ((Base Bid) $401f900.00 + (Alternate
'. $63,000.00 = $464,000.00). Staff is als• requesting a 10%• • ($$46,490.00) to address
of • - --n issues or quantity variances• • they arise. The total recommended project $511,390.00
($464,000 recommended award 1% contingency of $46,,490-00).
1. Accept the lowest cost, responsive bid to rehabilitation a 1 million gallon water storaget n (east tank) at Booster
Station 5.
2. Action at discretion of Village Board.
MM • 71 -1 r4 •i . f
Staff recommends that the Village Board accept the lowest -cost,, responsive bid for the Booster Station 5 East Tank
Rehabilitation P• submitted by V&T Painting, LLC of ! !n Hills, MI in an amount notto exceed $511,390.
https://go.boarddocs.com/il/vomp/Board.nsf/Private?open&login# 2/3
6/5/2019
BoardDocs® Pro
Tank 5E—Bid Package.pdf (2,330 KB) bid documents.pdf (872 KB) Location Map 1.pdf (1,451 KB)
Tank 5E Addendum No 1.pdf (9,801 KB) Tank 5E Addendum No 2.pdf (225 KB)
Administrative Content
Executive Content
Motion & Voting
Accept the lowest -cost, responsive bid for the Booster Station 5 East Tank Rehabilitation Project as submitted by V&T
Painting,, LLC of Farmington Hills, MI in an amount not to exceed $511,390.
Motion by Michael Zadel, second by Richard Rogers.
Final Resolution: Motion Carries
Yea: William Grossi, Eleni Hatzis, Paul Hoefert, Richard Rogers, Colleen Saccotelli, Michael Zadel
https://go.boarddocs.com/il/vomp/Board.nsf/Private?open&login# 3/3
Bid Request For
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
OPTIONAL PRE-BID: May 6, 2019 — 10:00 A.M. Local Time
BID OPENING: May 13, 2019 — 1:00 P.M. Local Time
Mount Prospect Public Works Department
1700 W. Central Road, Mount Prospect, Illinois 60056-2229
Village of Mount Prospect, Illinois
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage 'I anK
DOCUMENT 000107 — INDEX AND CERTIFICATION TIO PAG
SPECIFICATION TI l SEX
D C MEN
DIVISION DESCRIPTION
N
000100 to 007330 Table of Contents through
Affidavit T Bid Certification
Division I General Requirements
Division 5 Metals
Division 9 Finisbes
Division 32 - Extefior Improvements
Division 33 utilities
CERTIFICATION
Expires: November ember 3 , 2019
Biped: - - —
Randall L. Patchett, P.E.
INTRODUCTORY INFORMATION
000100
001115
BIDDING REOUIREMENTS
001116
001153
002050
004000
004005
004015
004035
Table of Contents
Notice to Bidders
Invitation to Bid
Bidder's Qualification Statement
Instructions to Bidders
Bid Submittal Checklist
Bid Form
Bid Sheet
Bid Security Form
CONTRACTING REOUIREMENTS
005000
Contract
005005
Required Owner / Contractor Forms
006100
Performance Bond
006111
Labor and Material Payment Bond
007200
General Conditions
007300
Supplemental Conditions
LABOR RELATED REOUIREMENTS
007310
Prevailing Wage Rates
007315
Certification Requirements
007330
Affidavit — Bid Certification
DIVISION I
GENERAL REQUIREMENTS
011100
Summary of Work
012000
Measurement and Payment
012500
Substitutions
013100
Project Coordination and Meetings
013200
Construction Progress Schedules and Reports
013300
Submittals
014200
Definitions and Standards
015700
Temporary Barriers and Controls
016000
Equipment and Materials
017800
Contract Closeout
017836
Warranties
DIVISION 5
METALS
051000
Structural and Miscellaneous
DIVISION 9
FINISHES
099000
Protective Coatings
DIVISION 32
EXTERIOR IMPROVEMENTS
329200
Lawns
Village of Mount Prospect Section 00015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
Page 1 of 2
DIVISION 33
331313
APPENDIX A
UTILITIES
Water Storage Tank Disinfection
ELECTRICAL DETAILS
Village of Mount Prospect Section 00015
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
Page 2 of 2
April 2019
Section 001115
NOTICE TO BIDDERS
Bid for
Rehabilitation of 1,000,000 Gallon Station SE Ground Storage Tank Project
Sealed bids will be received until 1:00 p.m. on May 13, 2019 in the office of the Village Manager, 3rd
Floor, 50 S. Emerson Street, Mount Prospect, Illinois 60056, in a separate, sealed envelope please submit
bid clearly marked "Sealed Bid for Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage
Tank Project". The project includes, but is not limited to the following bid items: Complete blast and
recoat of the wet interior, high pressure wash the exterior followed by spot repair and topcoat of the
exterior. The project also includes various improvements to the Tank's safety measures, steel work, seam
sealing, foundation repair, electrical work in the valve vault, disinfection, and site restoration. The Work
shall be constructed in accordance with the Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage
Tank bid documents dated April 2019.
The work includes a Base Bid plus pricing for Optional Work that the Village of Mount Prospect may
require the Contractor to perform during the contract period.
Specifications may be obtained at the Village of Mount Prospect's Onvia Demandstar website
using the following link www.mounlprospect.org/bids.
bids.
All work under this Bid and the resulting contract shall comply with the Illinois Prevailing Wage
Act, 820 ILCS 130/0.01 et seq. and the other applicable laws and ordinances.
Offers may not be withdrawn for a period of ninety (90) days after the bid date without the consent of the
Board of Trustees.
Any Bid submitted unsealed, unsigned, sent via email or fax or received subsequent to the
aforementioned date and time, will be disqualified and returned to the bidder.
The Village reserves the right in its sole discretion, to reject any and all bids or parts thereof, to waive any
irregularities technicalities and informalities in bid procedures and to award the contract in a manner best
serving the interests of the Village.
Village Manager
Michael Cassady
END OF SECTION 001115
Village of Mount Prospect Section 0011 15 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 1
Section 001116
INVITATION TO BID
Bid Let Date: April 16, 2019
Project Name: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Project Location: Village of Mount Prospect
Owners: Village of Mount Prospect
The project includes, but is not limited to the following bid items: Complete blast and recoat of the
wet interior, high pressure wash the exterior followed by spot repair and topcoat of the exterior. The
project also includes various improvements to the Tank's safety measures, steel work, seam sealing,
foundation repair, electrical work in the valve vault, disinfection, and site restoration. The Work shall
be constructed in accordance with the Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage
Tank dated April 2019.
Bid Documents available from: www.mountprospect.or__/�.
Question Cut Off: 4:00 p.m., May 9, 2019
Bids Due: 1:00 p.m., May 13, 2019
Bids submitted to: Village of Mount Prospect
Village Manager's Office, Third Floor
50 S. Emerson
Mount Prospect, Illinois 60056-2229
(847) 870-5640
Questions to:
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
Burns &McDonnell Engineering Co., Inc.
Stephen Crede / (630) 724-3214
Email• screde@burnsmcd.com
END OF SECTION 001116
Section 001116
Page 1 of 1
April 2019
Section 001153
BIDDER'S QUALIFICATION STATEMENT
Project Name: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SUBMITTED TO:
Village of Mount Prospect
Village Manager's Office, Third Floor
50 S. Emerson
Mount Prospect, IL 60056-2229
SUBMITTED BY:
Company
Name
Address
Principal Office
Corporation, partnership, individual, joint venture, other
Contractor license number and state
EXPERIENCE STATEMENT
1. Bidder has been engaged as a General Contractor in construction for years and
has performed work of the nature and magnitude of this Contract for years.
Bidder has been in business under its present name for years.
2. Bidder now has the following bonded projects under contract: On a separate sheet, list
project name, owner, engineer/architect, amount of contract, surety, and estimated
completion date.
3. Bidder has completed the following three (3) contracts consisting of work similar to that
proposed by this Contract: On a separate sheet, list project name, owner,
engineer/architect, amount of contract, surety, and date of completion and percentage of
the cost of the Work performed with Bidder's own forces.
4. Has Bidder ever failed to complete any project? If so, state when, where, and why.
5. Bidder normally performs the following work with his own forces:
6. Construction experience of key individuals in the organization is as follows (continued on
attached sheets if needed) :
7. In the event the Contract is awarded to Bidder, the required surety Bonds will be
furnished by the following surety company including name and address of agent:
Village of Mount Prospect Section 001153 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 2
SECTION 001153 — BIDDER'S QUALIFICATION STATEMENT: continued
FINANCIAL STATEMENT
Bidder possesses adequate financial resources as indicated by the following:
a. Assets and Liabilities: Attach a financial statement, audited if available, including
Bidder's latest balance sheet and income statements showing the following items:
(1) Current assets (cash, joint venture accounts, accounts receivable, notes
receivable, accrued income, deposits, materials inventory, and prepaid
expenses).
(2) Net fixed assets.
(3) Other assets.
(4) Current liabilities (accounts payable, notes payable, accrued expenses,
provision for income taxes, advances, accrued salaries, and accrued payroll
taxes).
(5) Other liabilities (capital, capital stock, authorized and outstanding shares par
values, earned surplus, and retained earnings).
(6) Name of firm preparing financial statement and date thereof:
If financial statement is not for identical organization named herein, explain relationship and financial
responsibility of the organization furnished.
8. Current Judgments: The following judgments are outstanding against Bidder:
Judgment CreditorsWhere Docketed and DateAmount
a. $
b. $
Bidder hereby represents and warrants that all statements set forth herein are true and correct.
Date 120
(OFFICIAL SEAL)
Name of Organization:
Title
(If Bidder is a partnership, the partnership name shall be signed, followed by the signature of at least one
of the partners. If Bidder is a corporation, the corporate name shall be signed, followed by the signature
of a duly -authorized officer and with the corporate seal affixed).
END OF SECTION 001153
Village of Mount Prospect Section 001153 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 2
Section 002050
INSTRUCTIONS TO BIDDERS
1) Bid. Bid forms are furnished by the Village. All bids must be submitted on the forms provided,
complete and intact, properly signed in ink in the proper spaces, and submitted in a sealed envelope.
All bids shall be delivered to the office of the Village Manager, Village Hall, 3rd Floor, 50 S.
Emerson Street, Mount Prospect, Illinois 60056, not later than 1:00 p.m. on May 13, 2019.
Envelopes shall be plainly marked, "Sealed Bid for Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank" and with the following information: company's name, address, date and
time of opening. Bids must be signed by an authorized official of the organization submitting the bid
with the name of the official and his/her title typed below the signature.
2) Pre -Bid Conference. There will be an optional pre-bid conference at 10:00 a.m. on May 6, 2019 at the
Village of Mount Prospect Public Works Department, 1700 West Central Road, Mount Prospect,
Illinois 60056.
3) Bid Deposit; Surety. A bid deposit in the amount of ten percent (10%) of the total bid amount,
payable to the Village, is required, unless otherwise stated in the bid package. The deposit must be in
the form of a bid bond, certified check, or a bank cashier's check. All bid performance deposit
checks will be retained by the Village until the bid award is made, at which time the checks will be
promptly returned to the unsuccessful bidders. The bid performance deposit check of the successful
bidder will be retained until surety bonding requirements have been satisfied and proof of insurance
coverage is provided.
4) Alternate Multiple Bids/Specifications
The Specifications describe the services that the Village feels is necessary to meet the performance
requirements of the Village. It is not the desire or the intent to eliminate or exclude any bidder from
bidding because of minor deviations, alternates or changes.
Bidders desiring to bid on services which deviate from these Specifications, but which they believe
are equivalent, are requested to submit alternate bids. However, alternate bids must be clearly
indicated as such, and deviations from the applicable Specifications should be plainly noted. The bid
must be accompanied by complete Specifications for the services offered. Bidders wishing to submit
a secondary bid must submit it as an alternate bid. There is to be only one bid per envelope. The
Village shall be the sole and final judge unequivocally as to whether any substitute is of equivalent or
better quality. This decision is final and will not be subject to recourse by any person, firm or
corporation.
If the bidder wishes to qualify its bid or make special stipulations thereto, such qualifications or
stipulations shall be stated on standard letterhead size sheets of paper, all attached to the bid form.
5) Erasures. All erasures or revisions of the bid must be initialed by the person signing the bid.
6) Receiving Of Bids. Bids received prior to the time of opening will be securely kept, unopened. The
Village Clerk or his/her designee, whose duty it is to open the bids, will decide when the specified
time has arrived, and no bid received thereafter will be considered. No responsibility will be attached
to the Village or its representatives for the premature or non -opening of a bid not properly addressed
and identified, except as otherwise provided by law.
Village of Mount Prospect Section 002050 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 5
SECTION 002050 — INSTRUCTIONS TO BIDDERS: continued
7) Late Bids. Bids arriving after the specified time, whether sent by mail, courier, or in person, will not
be accepted. These bids will either be refused or returned unopened. It is the bidder's responsibility
for timely delivery regardless of the method used. Mailed bids which are delivered after the specified
hour will not be accepted regardless of post marked time on the envelope.
8) Bids By Email And Fax. Email and Facsimile machine transmitted bids will not be accepted.
9) Error In Bids. When an error is made in extending total prices, the unit bid price will govern.
Otherwise, the bidder is not relieved from errors in bid preparation.
10) Withdrawal Of Bids. A written request for the withdrawal of a bid or any part thereof may be
granted if the request is received by the Director of the requesting Department prior to the specified
time of opening. After the opening, the bidder cannot withdraw or cancel his bid for a period of
ninety (90) calendar days, or such longer time as stated in the bid documents.
11) Bidders Qualifications. All bidders shall complete and submit Section 001153—Bidder's Qualification
Statement.
12) References; Background Check. Upon request of the Village bidders must provide the names of three
(3) references regarding its financial qualifications and three (3) references regarding its
qualifications by experience, ability, personnel and equipment to undertake work of the nature and
extent contemplated by the bid and Specifications. References must include company name, address,
contact person, and telephone number. The Village reserves the right to reject a bid if the bidder does
not provide produce the requested references.
All Bidders, as a condition of and prior to entry into a contract, agree that a complete background
investigation of the principals of the Bidder and all employees who will work on the project may be
made. Bidders agree to cooperate with the appropriate Village personnel to supply all information
necessary to complete these investigations. The Village in its complete discretion may disqualify any
Bidder, including a low Bidder, and may void any contract previously entered into based upon its
background investigation.
13) Consideration Of Bid And Contract. No bid will be accepted from or contract awarded to any person,
firm or corporation that is in arrears or is in default to the Village upon any debt or contract, or that is
a defaulter, as surety or otherwise, upon any obligation to the Village or had failed to perform
faithfully any previous contract with the Village within two (2) years prior to the date of the invitation
to bid.
14) Conditions. Bidders are responsible to become familiar with all conditions, instructions and
Specifications governing this bid. The bidder is responsible to visit a site if necessary and its bid is
based upon the knowledge of all information readily available at the site of such a visit. Once the bids
have been opened, the failure to have read and understood all conditions, Specifications and
instructions shall not be cause to alter the original bid or to request additional compensation. No extra
compensation will be allowed the successful bidder for failure to inform or familiarize itself prior to
bidding.
Village of Mount Prospect Section 002050 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 5
SECTION 002050 — INSTRUCTIONS TO BIDDERS: continued
15) Interpretation Of Bid Documents. Any bidder in doubt as to the true meaning of any part of the
Specifications or other bid documents may submit a written request for interpretation to the Village,
as provided in the Specifications. Bidders will acknowledge receipt of any addendum issued by so
noting on the bid sheet. Oral explanations are not binding.
16) Prices. Unit prices shall be shown for each unit on which there is a bid, and shall include all packing,
crating, freight, and shipping charges, and cost of unloading at the destination unless otherwise stated
in the bid.
Unit prices shall not include any local, state or federal taxes. The Village is exempt, by law, from
paying state and village retailer's occupation tax, service occupation tax, and federal excise tax. The
Village will supply the successful bidder with its tax exemption number.
Cash discounts will not be considered in determining overall price, but may be used in an overall
evaluation.
17) Qualifications of Contractors. Factors: It is the intention of the Village to award the Contract only to
a bidder who furnishes satisfactory evidence that it has the requisite experience, ability, capital
facilities, plant organization and staffing to enable it to perform the work successfully and promptly,
and to complete the work within the time set forth in the Bid Documents. The Village shall consider
the following factors:
a. The lowest responsible bid.
b. The ability, capacity, and skill of the bidder to perform the contract to provide the service
required.
c. Whether the bidder can perform the contract or provide the service promptly, or within the time
specified, without delay or interference.
d. The character, integrity, reputation, judgment, experience, and efficiency of the bidder.
e. The quality of performance of previous contracts of services.
f. The previous and existing compliance by the bidder with laws and ordinance relating to the
contract or service.
g. The sufficiency of the financial resources and ability of the bidder to perform the contract or
provide the service.
h. The quality, availability, and adaptability of the supplies or contractual service to the particular
use required.
i. The ability of the bidder to provide future maintenance and service for the use of the subject of
the contract.
j. The number and scope of conditions attached to the bid.
k. Whether the bidder has a place of business in the Village.
1. Responsiveness to the exact requirements of the invitation to bid.
m. Ability to work cooperatively with the Village and its administration.
n. Past records of the bidder's transactions with the Village or with other entities as evidence of the
bidder's responsibility, character, integrity, reputation, judgment, experience, efficiency and
cooperativeness.
o. Any other factor that the Village may legally consider in determining the bid that is in the best
interests of the Village.
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
Section 002050
Ground Storage Tank Page 3 of 5
April 2019
SECTION 002050 — INSTRUCTIONS TO BIDDERS: continued
18) Award Or Rejection. The Village, at its sole discretion, reserves the right to reject any and all bids or
parts thereof, to waive any irregularities, technicalities and informalities, and to award a bid in the
best interests of the Village. Any bid submitted will be binding for ninety (90) calendar days after the
date of the bid opening.
Bidders shall make all investigations necessary to thoroughly inform themselves regarding the
equipment or supplies to be furnished in accordance with the bid. No plea of ignorance by the bidder
of conditions that exist or that may hereafter exist as a result of failure or omission on the part of the
bidder to make the necessary examinations and investigations will be accepted as a basis for varying
the requirements of the Village or the compensation to the bidder.
Any bidder's exceptions to the terms or conditions, or deviations from the written Specifications must
be shown in writing and attached to the bid form. No verbal exceptions or agreements with
employees of the Village will be considered valid. Such exceptions or deviations can be cause for
rejection of the bid proposal. Any exceptions not taken by the bidder shall be assumed by the Village
to be included.
A contract will be awarded to the lowest responsible bidder complying with the conditions of the bid
documents only when it is in the best interest of the Village to accept the bid. The Village will take
into account the Base Bid as well as each Alternate bid item. The Village reserves the right to award
any combination of the Base Bid and Alternate bid items including but not limited to the Base Bid
plus all of the Alternates and the Base Bid plus no Alternates. The Village shall be the sole judge of
compliance with the Specifications.
19) Other Requirements.
a. New Equipment. The bidder certifies that any equipment to be furnished shall be new, current
model, standard production and fully operable, unless otherwise indicated on the bid form.
b. Material, Equipment and Service Standards. Unless otherwise directed by the Specifications, all
materials, equipment and services provided will meet standards or requirements which would
normally be anticipated in common practice. The bidder guarantees that all applicable federal,
state and local laws, including OSHA, are being complied with in connection with the bid and
any resultant contract or purchase by the Village.
c. Data; Proprietga. Complete and detailed brochures and specifications for vehicles equipment,
materials, goods, supplies and/or services to be furnished must be included with each bid. Any
reservations on the use of data contained in a bid must be clearly stated in the proposal itself.
Unless stated otherwise, information submitted in response to the bid is not proprietary or
confidential.
d. Patented Devices, Materials, And Processes. Contract prices are to include all royalties and costs
arising in the Work. It is the intent that whenever the Bidder is required or desires to use any
design, device, material, or process covered by patent or copyright, the right of such use shall be
provided for by suitable legal agreement with the patent owner.
Village of Mount Prospect Section 002050 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 4 of 5
SECTION 002050 — INSTRUCTIONS TO BIDDERS: continued
20) Requirement Of Bidder. The successful bidder shall, within ten (10) days after notification of the
award of the contract: a) enter into a contract in writing with the Village covering all matters and
things related to its bid; and b) furnish the required certificate of insurance and bonds.
21) Bid Certification Form. All bid submittals must include a signed Bid Certification Form (copy
attached) certifying non -collusion in the bid, and that the bidder is in compliance with Sections 33E-
3 and 33E-4 of the Illinois Criminal Code regarding bid rotating and bid -rigging, 720 ILCS 5/33E-3,
33E-4, compliance with the Illinois Drug Free Workplace Act, 30 ILCS 580/1, et seq., and Substance
Abuse Prevention in Public Works Projects Act, 820 ILLS 265/1 et seq., that it is not delinquent in
the payment of taxes (65 ILCS 5/11-42. 1) and that it has a written sexual harassment policy in place
in full compliance with Section 2-105 of the Human Rights Act, 775 ILCS 5/2-105, as amended,
Sections 33E-3 and 33E-4 states that it is unlawful to participate in bid -rigging and/or bid rotating.
Therefore, all bidders must certify, under oath, that they are not barred from bidding on the contract
as a result of a violation of Sections 33E-3 and/or 33E-4, prohibiting bid -rigging and bid rotation.
Therefore, the Bid Certification Form must be notarized.
22) Interpretation Of Bid Documents. Any bidder in doubt as to the true meaning of any part of the
Specifications or other bid documents shall submit a written request for interpretation to the contact
specified in the Invitation, no later than five (5) calendar days prior to the date set for the opening of
the bid. Any questions received after that time maybe answered at the discretion of the Village.
In the event that the Village finds a question to be adequately addressed in the existing bidding
documents, the question may be answered in writing by directing the requesting bidder to the
applicable provision(s) in the existing bid documents. No further clarifications or interpretations will
be issued.
Bidders will acknowledge receipt of any addendum issued by so noting on the bid sheet. Oral
explanations are not binding.
END OF SECTION 002050
Village of Mount Prospect Section 002050 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 5 of 5
Section 004000
BID SUBMITTAL CHECKLIST
PART 1 — GENERAL
1.1 DESCRIPTION
A. The bid submittal shall consist of one original copy of the following items to be
submitted as required in Section 002050, Instructions to Bidders. Failure to submit all of
the information listed is grounds for bid disqualification.
1. 001153
— Bidder's Qualification Statement
2. 004005
— Bid Form
3. 004015
— Bid Sheet
4. 004035
— Bid Security
5. 007315
— Certification Requirements
6. 007330
—Affidavit — Bid Certification
7. References per 002050
END OF SECTION 004000
Village of Mount Prospect Section 004000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 Of 1
FROM:
Section 004005
BID FORM
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Village of Mount Prospect
Department of Public Works
(hereinafter called "Bidder")
TO: Office of the Village Manager, 3rd Floor
50 South Emerson Street
Mount Prospect, Illinois 60056
(hereinafter called "Village" or "Village of Mount Prospect")
Bid For: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
The bidders have familiarized themselves with the work and probable work conditions required
under this Bid affecting the cost of the work and with the Bid Documents which include:
Notice to Bidders
Table of Contents
Instructions for Bidders
General Conditions and Special Provisions
Specifications
Bid Form
Affidavit — Bid Certification Form
Bid Security
Bid Sheet — Rehabilitation of 1,000,000 Gallon Station 5E Storage Tank
Contract Document
Labor and Materials Payment bond form
Performance Bond Form
Therefore, the Bidder hereby proposes to furnish all supervision, technical personnel, labor,
materials, tools appurtenances, equipment, and services (including all utility and transportation
services) required to construct and complete the Work, all in accordance with the above listed
documents.
Bidder agrees to perform all of the Work and provide the equipment and materials described in
the Bid Documents, as follows:
Bidder has bid on all items and has provided a price for all items.
The Bidder will complete and provide all labor, equipment, materials and mobilization (if
applicable) to perform the Work as incidental to the fixed item price for each item proposed.
Village of Mount Prospect Section 004005 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 3
SECTION 004005 — BID FORM: continued
In submitting this bid, the Bidder understands that the Village of Mount Prospect reserves the
right to add to or subtract from the estimated quantities.
The Village of Mount Prospect intends to award one (1) contract (if at all) for the items bid. If
written notice of award of this bid is mailed, emailed or otherwise delivered to the Bidder at any
time before this bid is withdrawn, the Bidder agrees to execute and deliver the contract in the
prescribed form and furnish payment andperformance bonds, or letter of credit, and the
insurance certificates required by the Bid Documents to the Village within ten (10) days after
receipt.
The Bidder, and as successful bidder/Contractor upon award of the Contract understands and
agrees to the following:
1) The Contractor agrees to provide all Work and items and material to the Village as noted in
the Bid Documents and comply with the requirements of the Bid Documents.
2) The Contractor agrees to comply with all applicable state and federal laws, rules and
regulations, and county and municipal ordinances, as described in the General Conditions.
All Addenda pertaining to this project shall be acknowledged by the Bidder in the spaces
provided below:
Addendum
No.
Addendum
Date
Acknowledgement by Bidder or
Authorized Representative
Date
Acknowled ed
Failure to acknowledge receipt, as provided above, may be considered sufficient grounds for
disqualification of the bidder and rejection of his/her bid submittal. A record of all Addenda and
copies of same will be available to all qualified bidders from the Village of Mount Prospect
Public Works Department, 1700 West Central Road, Mount Prospect, Illinois two (2) days prior
to the letting. It shall be the bidder's responsibility to become fully advised of all Addenda prior
to submitting its bid.
Upon award the contract the Village will send Notice of Award to the successful bidder, the
bidder must then execute the contract and provide the required bonds or letter of credit and
certificate of insurance to the Village within ten (10) days. The Village will then issue a written
Notice to Proceed which starts the performance period. The contractor shall reach substantial
Village of Mount Prospect Section 004005 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 3
SECTION 004005 — BID FORM: continued
completion by 60 calendar days after the date of the Notice to Proceed with final completion
by 75 calendar days after the date of the Notice to Proceed. Substantial completion shall be
defined as the completion of all work except for site restoration. Failure to complete the work in
the designated time frame may result in the Director of Public Works withholding compensation
due the contractor for failure to complete the said work in the designated time frame, calling the
bonds, or taking such other action as may be available.
Security in the sum of ten (10%) percent of the amount bid in form of (check one):
Bid Bond Certified Check Bank Cashier's Check
is attached hereto in accordance with the "Instructions for Bidders".
This Bid Submittal contains the following:
1) Bid Form
2) Affidavit —Bid Certification Form
3) Bid Security
4) Bid Sheet(s) —Rehabilitation of 1,000,000 Gallon Station SE Ground Storage Tank
Respectfully submitted:
Name of Firm/Bidder:
By: _
Title:
Date:
Contact Information:
Official Address:
Telephone:
Email:
(Signature)
ONE (1) SIGNED COPY OF THIS BID FORM AND BID SHEETS ALONG WITH THE
AFFIDAVIT — BID CERTIFCATION FORM, AND BID SECURITY SHALL BE
SUBMITTED IN A SEALED MARKED ENVELOPE.VILLAGE OF MOUNT
PROSPECT
END OF SECTION 004005
Village of Mount Prospect Section 004005 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 3 of 3
Section 004015
BID SHEET
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
UNIT PRICES: For providing, performing, and completing all work, the sum of the products
resulting from multiplying the number of acceptable units by price per Unit.
COMPLETE TABLE AS INDICATED
Item
No.
Description
Unit
Approx.
Qty. of
Units
Price Per Unit
Extension
1
Mobilization
L. Sum
1
Price Per Unit
Extension
2
Interior Coating Rehabilitation
L. Sum
1
3
Exterior Coating Rehabilitation
L. Sum
1
4
Steel Work & Miscellaneous Repairs
L. Sum
1
5
Electrical Work
L. Sum
1
6
Tank Disinfection
L. Sum
1
7
Site Restoration
L. Sum
1
8
Contingency — Man Hours for Additional Work
Hour
40
Total Bid=
1. The Owner has the ability to add any or all of the following alternates to the Total
Bid, or each Bid Item independently. Complete Alternate Bid Items Table as
Indicated:
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 4
Approx.
Item
Item & Description
Unit
Qty. of
Price Per Unit
Extension
No.
Units
Exterior Coating w/ Full Blast: add or deduct
LA
from Base Bid Item 3
L. Sum
1
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 4
SECTION 004015 — BID SHEET: continued
LB
Partial Beam Replacement
L. Sum
1
Dollars and Cents
1.0
Complete Beam Replacement
L. Sum
1
TOTAL ALTERNATE BID PRICE (the sum of extensions of the Bid Sheet):
SUMMARY OF PRICES:
TOTAL BASE BID
TOTAL BASE BID PRICE (the sum of extensions of the Bid Sheet):
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 Of 4
Dollars and Cents
(In writing)
(In writing)
Dollars and Cents
(In figure)
(In figure)
TOTAL ALTERNATE BID
TOTAL ALTERNATE BID PRICE (the sum of extensions of the Bid Sheet):
Dollars and Cents
(In writing)
(In writing)
Dollars and Cents
(In figure)
(In figure)
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 Of 4
SECTION 004015 — BID SHEET: continued
BASIS FOR DETERMINING PRICES
It is expressly understood and agreed that:
1. The approximate quantities set forth in this Bid Sheet for each Unit Price Item are Owner's
estimate only, that Owner reserves the right to increase or decrease such quantities, and that
payment for each Unit Price Item shall be made only on the actual number of acceptable
units of such Unit Price Item installed complete in place, measured on the basis defined in
the Contract.
2. Owner is not subject to state or local sales, use and excise taxes and no such taxes are
included in this Bid Sheet.
Specific cash allowances, if any, are included in the price set forth above and have been computed in
accordance with paragraph 11.02 of the General Conditions.
BIDDER agrees that the Work will be Substantially Completed in 60 consecutive calendar days from the
date of "Notice to Proceed" and Finally Completed in 15 calendar days thereafter.
BIDDER accepts the provisions of the Agreement as to liquidated damages in the event of failure to
complete the Work within the times specified in the Agreement.
The following documents are attached to and made a condition of this Bid:
(a) Required bid security in the amount of ten percent (10%) of the Bid in the form of a bid
bond, cash, certified check, cashiers check or bank money order as stipulated in the
Advertisement for Bids.
(b) A tabulation of subcontractors, suppliers and other persons and organizations required to be
identified in this Bid.
(c) Required BIDDER'S Qualification Statement with supporting data.
Written communications concerning this Bid shall be addressed to:
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 3 of 4
SECTION 004015 — BID SHEET: continued
The terms used in this Bid which are defined in the General and Supplementary Conditions of the
Construction Contract, included as part of the Contract Documents, have the meanings assigned to them
in the General and Supplementary Conditions.
Submitted on
, 2019.
State Contractor License Number (if any)
Contractor Contact Information:
Address:
Telephone:
E-mail:
Signature
END OF SECTION 004015
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 4 of 4
Section 004035
BID SECURITY FORM
Included with this bid is a bank cashier's check, certified check or bid bond in the amount of
being ten percent (10%) of the total amount bid by
the Bidder, in favor of the Village of Mount Prospect. It is hereby agreed
that, should Bidder be awarded the Work contemplated under this bid and fail or refuse to execute a
contract for said Work, or to provide the required payment and performance bonds, or letter of credit, and
certificate of insurance, then this security, in the amount stipulated above, shall be forfeited and may be
retained by the Village of Mount Prospect as liquidated damages and not as a penalty. All bids to remain
firm for a period of ninety (90) days after bid opening date.
SUBMITTED THIS
SEAL (if corporation)
DAY OF 92019.
Bidder:
Bidder's Agent and Agent's Title
Title
Note: If bidder is a partnership, the bid must be signed by at least two of the partners.
Note: If bidder is a corporation, the bid must be signed by an authorized officer of the corporation,
attested and sealed by the secretary or other authorized officer.
If a corporation, note here the state of incorporation:
Incorporated under the laws of the State of
END OF SECTION 004035
Village of Mount Prospect Section 004035 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 1
Section 005000
CONTRACT
THIS Contract (hereinafter the "Contract") is entered into on this day of , 2019, by and
between the VILLAGE OF MOUNT PROSPECT, an Illinois municipal corporation (hereinafter
the "Village"), and , an (hereinafter the `Contractor")
(Village and Contractor sometimes referred to individually as "Party" and collectively as
"Parties"),
WHEREAS, the Village has solicited competitive bids for its "Rehabilitation of
1,000,000 Gallon Station 5E Ground Storage Tank Project"; and
WHEREAS, the Contractor submitted a bid to perform the work associated with the
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank Project (hereinafter the
"Bid"); and
WHEREAS, upon its review of the submitted bids, the Village has awarded the contract
to perform the work associated with the Rehabilitation of 1,000,000 Gallon Station 5E Ground
Storage Tank Project to the Contractor, subject to the execution of this Contract;
NOW, THEREFORE, for and in consideration of their mutual promises, covenants,
undertakings and agreements, the parties agree as follows:
ARTICLE I — CONTRACT DOCUMENTS
This Contract is subject to the terms and conditions set forth in the Contract Documents, which
are incorporated herein as if fully set forth, and include the following Bid Documents with
Bidder's/Contractor's Bid Submittals prioritized to be included in number 6*:
1. Notice to Bidders
2. Table of Contents
3. Instructions to Bidders
4. General Conditions and Special Provisions
5. Specifications
6. Bid Submittals, including Bid Form, Affidavit — Bid Certification Form, Bid
Security, Bid Sheet
(*Bidder's/Contractor's completed Bid Submittals)
7. Other materials or standards provided or noted by the Village
8. Contract
9. Applicable performance and labor and materials payment bonds, or letter of credit.
(Collectively the "Contact Documents")
ARTICLE II — PERFORMANCE BY CONTRACTOR
Village of Mount Prospect Section 005000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 6
1. The Contractor agrees to perform the work, including all labor, materials, equipment and
services, in accordance with the terms and conditions set forth in the Contract Documents
(hereinafter the "Work").
2. The Contractor acknowledges that the Village reserves the right to add to or subtract from
the estimated quantities.
3 . The Contractor certifies that it will comply with all state and federal laws and regulations,
and county and municipal ordinances, as set forth in the General Conditions.
ARTICLE III — PERFORMANCE BY VILLAGE
The Village agrees to pay the Contractor for its performance of the Work in the manner and
amount provided in the Contract Documents.
ARTICLE IV - CONFLICT BETWEEN CONTRACT DOCUMENTS
In the event of a conflict between any Contract Document and the terms of this Contract, the
Contract shall control to the extent of the conflict. In the event of any other conflict between
Contract Documents, the preceding Document shall govern to the extent of the conflict based
upon the order of priority set forth in Article I of this Contract, unless otherwise specifically
stated.
ARTICLE V —COMMENCEMENT AND COMPLETION OF WORK
After the written Notice to Proceed is issued by the Village, which will start the performance
period, the Contractor then has 10 days to commence work. The Contractor shall achieve
substantial performance within sixty (60) consecutive calendar days after the Notice to Proceed
has been issued with final performance fifteen (15) calendar days thereafter.
The Contractor shall commence performance of the Work and complete performance of the
Work, in accordance with the schedule set forth in the Contract Documents, but in no event shall
any Work be performed prior to the Village's receipt of this Contract, executed by Contractor,
and the Village's acceptance and approval of the payment and performance bonds, or letter of
credit, and certificate of insurance required by the Contract Documents.
ARTICLE V — NOTICE
Unless otherwise provided, all notices required under this Contract shall be made in writing and
addressed or delivered as follows:
TO THE VILLAGE OF MOUNT PROSPECT -
The Village of Mount Prospect
1700 West Central Road
Mount Prospect, Illinois 60056
ATTN: Director of Public Works
TO CONTRACTOR- at the address set forth on the Bid Form, or:
Village of Mount Prospect Section 005000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 6
Notices shall be deemed effective when received by personal service or registered or certified
U.S. mail, postage prepaid and receipt requested, to the address so specified. Either Party may, by
written notice to the other, change its own mailing address.
ARTICLE VI — PRIOR AGREEMENTS; SUCCESSORS
This Contract supersedes all previous agreements, understandings and representations of any
nature whatsoever, whether oral or written, and constitutes the entire understanding between the
Parties. The terms of this Contract shall be binding upon and inure to the benefit of the parties
and the partners and officials, successors in interest, executors, administrators, assigns and
representatives and their respective successors and assigns, provided, however, that the
Contractor shall not assign, sublet or transfer any rights or interest in this Agreement in whole or
in part without the prior written approval of the Village, except to the extent that the Contract
Documents provide otherwise.
ARTICLE VII - DEFAULT BY CONTRACTOR
If the Contractor fails to begin the Work under the Contract within the time specified, or fails to
perform the Work in accordance with the terms of the approved schedule or performs the Work
in a manner unacceptable to the Village, or neglects or refuses to remove materials or perform
anew such Work as has been rejected by the Village, or if the Contractor shall become insolvent
or be declared bankrupt, or shall make an assignment for the benefit of creditors, or from any
other cause whatsoever shall fail to carry on the Work in a manner required by the Contract, the
Village shall give notice as hereinafter provided to the Contractor and its surety in writing
specifying such failure, delay, neglect, refusal or default, and if the Contractor, within a period of
ten (10) calendar days after the giving of such notice, shall not proceed in accordance therewith,
then the Village shall have full power and authority to declare the this Contract and the
Contractor in default, and to forfeit the rights of the Contractor in this Contract.
Upon declaration of Contractor's default, the Village may, at its option, call upon the surety to
complete the Work in accordance with the terms of this Contract or may take over the Work,
including any materials on the Work site as may be suitable and acceptable to the Village and
may complete the Work by its own forces or on its own account, or may enter into a new contract
or contracts for the completion of the Work, or may use such other methods as shall be required
for the completion of the Work in an acceptable manner as the Village may in its discretion
determine.
All costs and charges incurred by the Village, together with the cost of completing the Work shall
be deducted from any moneys due or which may become due on this to the Contractor under this
Contract. Following any payment due and received by the Village from the Contractor's surety
following default, if the expense so incurred by the Village is less than the sum paid to the
Village by the surety under this Contract for work remaining, the surety shall be entitled to
receive the excess difference paid to the Village. When such Contractor default costs incurred by
the Village exceeds the sum paid to the Village for the work remaining under the Contract the
Contractor and the surety shall be liable and shall pay to the Village the full cost of such
additional expenses.
Village of Mount Prospect Section 005000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 3 of 6
ARTICLE VIII - DEFAULT BY VILLAGE
In the event of a material default by the Village under this Contract, the Village shall have sixty
(60) days, from notice thereof by Contractor, to cure the default prior to Contractor's termination
of this Contract. The failure to pay a contested invoice shall not be considered a material default.
Upon termination, the Village shall be responsible to pay any uncontested payments due for work
performed.
ARTICLE IX — VENUE
The parties hereto agree that for purposes of any lawsuit(s) between them concerning this
Agreement, its enforcement, or the subject matter thereof, venue shall be in Cook County,
Illinois, and the laws of the State of Illinois shall govern the cause of action.
ARTICLE X - SEVERABILITY OF CONTRACT
If any term of this Contract is held by a court of competent jurisdiction to be void or
unenforceable, the remainder of the Contract terms will remain in full force and effect and will
not be affected.
ARTICLE XI - CUMULATIVE REMEDIES
The exercise or failure to exercise any legal rights and remedies associated with any act of default
or breach hereunder by either Party will not constitute a waiver or forfeiture of any other rights
and remedies, and will be without prejudice to the enforcement of any other right or remedy
available by law or authorized by this Contract.
ARTICLE XII - COMPLIANCE WITH LAWS
Each party to this Contract will comply with all applicable state and federal laws and regulations,
and county and municipal ordinances and regulations.
ARTICLE XIII - DISPUTE RESOLUTION
Should a dispute arise between the Village and the Contractor as to the terms and conditions of
the Contract, or the responsibilities, limitations, or working relations of either Party, the
designated project personnel will make every reasonable effort to resolve the difference in
accordance with the terms and conditions of the Contract. If a dispute continues despite these
efforts, it shall be referred to the Parties' Project Managers.
If the above action fails to resolve the dispute, the Parties may, by agreement, elect to resolve the
dispute through a mediation process. Each Party shall bear its own costs in preparing and
conducting mediation, except that the costs, if any, of the actual mediation proceeding shall be
shared equally by the Parties. The mediation process is defined as follows:
The Parties shall select a mutually agreeable mediator from American Arbitration Association
lists or any other agreeable list to aid the Parties in resolving the dispute. The mediator shall not
be an employee or former employee of either Party. The first meeting shall be held at a location
chosen by the Village. At the meetings, each Party may present materials and/or arguments to the
mediator. The mediator's decision shall be not being binding upon either Party.
Village of Mount Prospect Section 005000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 4 of 6
In the event that the foregoing steps fail to resolve the dispute, either Party may bring suit in the
Circuit Court of Cook County, Illinois.
ARTICLE XIV - ASSIGNMENT
No rights or interest in this Contract may be assigned by Contractor without prior written notice
being provided by Contractor to the Village and the Village's written approval. The Village shall
not unreasonably withhold its approval of such assignment. In the event of an assignment, the
Contractor shall not be relieved of its obligations under the Contract unless agreed to by the
Village, at its sole discretion.
ARTICLE XV - RECRUITING
The Parties shall not, without the consent of the other Party, entice, encourage, offer special
inducements, or otherwise recruit employees of the other Party during the period of this Contract
and for a period of one (1) year thereafter. This clause is not intended to restrict any individual's
right of employment but rather is intended to preserve the relationship intended under this
Contract and to prevent the Parties from actively recruiting the employees of the other Party.
ARTICLE XVII - COUNTERPARTS
This Contract may be executed in counterparts, each of which shall be an original and all of
which together shall constitute one and the same agreement.
ARTICLE XVIII - ENFORCEABILITY
If any provision of this Contract is found to be invalid, illegal or unenforceable, that provision
shall be severable from the rest of this Contract and the validity, legality and enforceability of the
remaining provisions will in no way be affected or impaired.
ARTICLE XIX - EFFECTIVE DATE
The effective date of this Contract shall be the date of the last signature executing the Contract
(hereinafter referred to as the "Effective Date").
ARTICLE XX - ADVERTISEMENT
Contractor shall not use, in its advertising, marketing programs, or other promotional efforts, any
data, pictures, or other representation of the Village, except with the specific written
authorization in advance by the Village.
ARTICLE XXI - CAPTIONS; HEADINGS
The paragraph headings which appear herein are included solely for convenience and shall not be
used in the interpretation of this Contract.
ARTICLE XXII — ENTIRE AGREEMENT
This Contract, consisting of the Contract Documents, constitutes the entire agreement between
the Parties for the subject matter hereof and supersedes all prior arrangements, agreements,
representations and undertakings, written or oral. This Contract may not be changed or modified
except by a written instrument duly executed by each of the Parties hereto.
Village of Mount Prospect Section 005000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 5 of 6
IN WITNESS WHEREOF, the Parties hereto have executed this Contract.
Contractor: VILLAGE OF MOUNT PROSPECT
Title:
Date:
ATTEST: ATTEST:
Title:
Date:
0
Title:
Date:
Title:
Date:
END OF SECTION 005000
Village of Mount Prospect Section 005000 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 6 of 6
Section 005005
REQUIRED FORMS FOR
OWNER /CONTRACTOR AGREEMENT
PART 1 — GENERAL
1.01 FORMS REQUIRED PRIOR TO SIGNING CONTRACT
A. Bid Sheet per Section 004015
B. Certificates of Insurance per Supplemental Instructions Section 007300
C. Performance Bond per Section 006100
D. Labor and Material Payment Bond per Supplemental Instructions Section 006111
E. Proof of Current Village Contractor's License
END OF SECTION 005005
Village of Mount Prospect Section 005005 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 1
Section 006100
PERFORMANCE BOND
Bond No. :
Principal Amount:
Contract:
KNOWN ALL MEN BY THESE PRESENTS, that
,as
(hereinafter "Contractor"), and with main
Contractor
Principal
office at
, a corporation of the state of
,as Surety (hereinafter "Surety"), are held and firmly bound unto the Village of
Mount Prospect, an Illinois municipal corporation (hereinafter "Village"), in the penal sum of
Dollars ($ ), lawful money of the United States,
for the payment of which, we bind ourselves, our heirs, executors, administrators, successors and assigns,
jointly and severally, firmly by these presents.
WHEREAS, Contractor has entered into a written agreement with the Village dated
(hereinafter "Contract"), for the construction of
in
accordance with the drawings and specifications prepared by: (Village of
Mount Prospect or architect/engineer), which Contract is incorporated herein and made a part hereof.
NOW, THEREFORE, THE CONDITION OF THIS OBLIGATION IS SUCH, that if the Contractor
shall fully, promptly and completely discharge the Contract and all duly authorized modifications,
alterations, changes, or additions to said Contract as may hereafter be made, and during the life of any
guaranty required under the Contract, and, if Contractor shall fully secure and protect the Village from all
liability and from all loss or expense of any kind, including all court costs and attorneys' fees made
necessary or arising from the failure, refusal or neglect of Contractor to comply with all obligations
assumed by Contractor in connection with the performance of the Contract and all such modifications,
alterations, changes, or additions, then this obligation shall be null and void; otherwise it shall remain in
full force and effect.
Upon receipt of written notice from the Village that the Contractor is in default, and performance
by the Village of its obligations under the Contract, Surety will promptly (1) remedy the default; (2)
arrange for the performance of Contractor's obligations under the Contract through the use of qualified
contractors acceptable to the Village; or (3) notify the Village that it may hire a contractor to complete
Contractor's obligations under the Contract. Surety will promptly notify, in writing, the Village of which
option it is exercising. Failure of the Surety to elect an option within fifteen (15) days of receipt of the
notice from the Village shall constitute authorization to the Village to complete the improvements at
Surety's expense.
The balance of the contract price shall be credited against the cost of completing and/or
correcting the Contractor's performance under the Contract. If the cost exceeds the balance of the
contract price, the Surety shall pay the excess amount to the Village, up to a maximum of the principal
Village of Mount Prospect Section 006100 April 2019
Rehabilitation of 1,0001000 Gallon Station 5E
Ground Storage Tank Page 1 of 3
SECTION 006100 — PERFORMANCE BOND: continued
amount of this Bond. If the Surety arranges for completion and/or correction or remedies the default, the
balance of the contract price that is required to complete, correct or remedy the default shall be paid by
the Village to Surety. Surety will be responsible, up to the maximum of the principal amount of this
Bond, for payment for correction and completion of the Contract, any additional legal, design
professional or delay costs arising from Contractor's default and/or resulting from action or inaction on
the part of the Surety and liquidated damages, or, if no liquidated damages are provided for in the
Contract, actual damages caused by delayed performance or non-performance by the Contractor or
Surety. The Village shall not be required to pay Surety more than the balance of the contract price.
The term "balance of the contract price" means the total amount payable by the Village to the
Contractor under the contract, and any amendments thereto, less the amounts paid to the Contractor by the
Village.
Any suit under this Bond must be filed before the expiration of two years from the date on which
final payment under the Contract is due or the applicable statute of limitations, whichever is longer. No
right of action shall accrue on this Bond to or for the use of any person or corporation other than the
Village or its heirs, executors, administrators or successors. Any proceeding, legal or equitable, under
this Bond may be instituted in a court of competent jurisdiction in the location in which the work is
located. Notice to any of the parties shall be mailed to the appropriate address listed above.
Surety hereby waives notice of any modifications, alterations, changes, additions or extension of
time in the Contract.
Signed and sealed this day of
Contractor
By:
Signature
Title
ATTEST:
Corporate Secretary (corporations only)
STATE OF
COUNTY OF
I,
certify that
, 201
Surety
By:
Officer Of The Surety
Title
Address:
NOTARV
, a Notary Public in and for said county, do hereby
(Insert Name of Attorney -In -Fact for Surety)
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
Section 006100
Ground Storage Tank Page 2 of 3
April 2019
SECTION 006100 — PERFORMANCE BOND: continued
who is personally known to me to be the same person whose name is subscribed to the foregoing
instrument on behalf of Surety, appeared before me this day in person and acknowledge respectively that
he/she signed, sealed, and delivered said instrument as his/her free and voluntary act for the uses and
purposes therein set forth.
Given under my hand and notarial seal this
Notary Signature:
_day of
My Commission expires:
END OF SECTION 006100
,201
Village of Mount Prospect Section 006100 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 3 of 3
Section 006111
LABOR AND MATERIAL PAYMENT BOND
Bond No. :
Principal Amount:
Contract:
KNOWN ALL MEN BY THESE PRESENTS, that the Village of Mount Prospect, an Illinois
municipal corporation (hereinafter "Village"), has awarded to
(hereinafter "Contractor"), a written agreement with the Village dated
(hereinafter "Contract"), for
accordance with the drawings and specifications prepared by:
as Principal
in
(Village of
Mount Prospect or architect/engineer), which Contract is incorporated herein and made a part hereof; and
WHEREAS, the Contractor is required to furnish a bond in connection with the Contract to
secure the payment of claims of laborers, workmen, mechanics, material suppliers, and other persons as
provided by law;
NOW, THEREFORE, we, the undersigned Contractor and ,
with main office at , as Surety, are held and firmly bound
unto the Village in the penal sum of Dollars ($ ),
lawful money of the United States, for which payment well and truly to be made we bind ourselves, our
heirs, executors, administrators, successors, and assigns, jointly and severally, firmly by these present.
NOW, THEREFORE, THE CONDITION OF THIS OBLIGATION IS SUCH, that if the Contractor
shall fully, promptly pay for all laborers, workmen and mechanics engaged in the work under the
Contract, and not less than the general prevailing rate of hourly wages as required by the Contract and the
Illinois Prevailing Wage Act, 820 ILCS 130/1 et seq., and for all material used or reasonably required for
use in the performance of the Contract, and all duly authorized modifications, alterations, changes or
additions to said Contract as may hereafter be made, then this obligation shall be null and void; otherwise
it shall remain in full force and effect, subject to the following conditions:.
1. A "Claimant" is defined as any person, firm or corporation having contracts with Contractor
or with a subcontractor of Contractor to furnish labor, materials, or both, for use in the
performance of the Contract. "Labor and materials" is construed to include that part of water,
gas, power, light, heat, oil, gasoline, telephone service, rental of equipment, and any other
items for which a mechanic's lien may be asserted.
2. Any person having a claim for labor and materials furnished in the performance of the
Contract shall have no right of action unless he shall have filed a verified notice of such claim
with the Village Clerk within 180 days after the date of the last items of work or the
Village of Mount Prospect Section 006111 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 3
SECTION 006111 — PAYMENT BOND: continued
furnishing of the last item of materials, and filed a copy of that verified notice upon the
Contractor within 10 days after the filing of the notice with the Village Clerk. Filing must be
by personal service or United States Mail, postage prepaid, certified or restricted delivery,
return receipt requested, limited to addressee. The notice shall contain 1) the name and
address of the claimant; 2) the business address of the claimant within the State of Illinois, if
any, or if the claimant be a foreign corporation having no place of business within the State,
the principal place of business of the corporation, and in the case of partnership, the names
and residences of each of the partners; 3) the name of the Contractor for the Village; 3) the
name of the person, firm or corporation by whom the claimant was employed or to whom
such claimant furnished materials; 4) a brief description of the public improvement for the
construction or installation of which the Contract is to be performed; and 5) a description of
Claimant's contract as it pertains to the public improvement describing the work done by the
claimant and stating the total amount due and unpaid as of the date of the verified notice. No
defect in the notice herein provided for shall deprive the claimant of its right of action under
the terms and provision of this Bond unless it shall affirmatively appear that such defect has
prejudiced the rights of an interested party asserting the same.
3. No action shall be brought on this Bond later than one year after the date of the last item of
work or of the furnishing of the last item of materials. Such suit shall be brought only in the
circuit court of the State in the judicial district in which the Contract is to be performed.
4. The Village shall not be liable for the payment of any costs or expenses of any such lawsuit,
and the Village does not have any obligations to any Claimants who make claims on this
Bond. Surety will pay for all such claims, and for all costs and expenses of any such lawsuit,
up to a maximum of the amount of this Bond.
Surety hereby expressly agrees that no extension of time, change, modification, alteration,
deletion, or addition to the undertakings, covenants, terms, conditions, and agreements of the Contract, or
to the work to be performed thereunder, shall in any way affect the obligation of this Bond; and it does
hereby waive notice of any such extension of time, change, modification, alteration, deletion, or addition
to the undertakings, covenants, terms, conditions, and agreements of the Contract, or to the work to be
performed thereunder.
Surety's obligations hereunder are independent of the obligations of any other surety for the
payment of claims of laborers, workmen, mechanics, material suppliers, and other persons in connection
with the Contract; and suit may be brought against Surety and such other sureties, jointly and severally, or
against any one or more of them, or against less than all of them without impairing the Village's rights
against the others. Any payment by the Surety made in good faith pursuant to this Bond shall reduce the
principal amount of this Bond.
Signed and sealed this day of
Contractor
By:
Signature
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
201
Surety
By:
Section 006111
Page 2 of 3
Officer Of The Surety
April 2019
SECTION 006111 — PAYMENT BOND: continued
Title
ATTEST:
Corporate Secretary (corporations only)
STATE OF
COUNTY OF
I,
certify that
Title
Address:
NOTA12V
, a Notary Public in and for said county, do hereby
(Insert Name of Attorney -In -Fact for Surety)
who is personally known to me to be the same person whose name is subscribed to the foregoing
instrument on behalf of Surety, appeared before me this day in person and acknowledge respectively that
he/she signed, sealed, and delivered said instrument as his/her free and voluntary act for the uses and
purposes therein set forth.
Given under my hand and notarial seal this
Notary Signature:
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
day of , 201 .
My Commission expires:
(Attach Surety's Power of Attorney)
END OF SECTION 006111
Section 006111
Ground Storage Tank Page 3 of 3
April 2019
GENERAL CONDITIONS
1) Definition of Terms. In these specifications and the accompanying documents, the several
terms hereinafter defined shall be understood to mean as follows:
The term "Award" shall mean the decision of the Village of Mount Prospect to accept
the bid of the lowest responsible bidder for the work, subject to the execution and
approval of a satisfactory contract therefore, and bond to secure the performance
thereof, and to such other conditions as may be specified or otherwise required by
law.
The term "Bid" shall mean a formal written offer of a bidder to perform the proposed
work in accordance with these specifications.
The term "Bidder" shall mean any individual, firm, or corporation submitting a bid for
the work contemplated.
The phrase "Bid Documents" shall mean the Notice to Bidders, Table of Contents,
Instructions to Bidders, General Conditions and Special Provisions, Specifications,
Bid Form, Affidavit — Bid Certification Form, Bid Security, Bid Sheet, Other Materials
or standards provided or noted by the Village, Contract, Performance Bond form,
and Labor and Materials Payment Bond form.
The term "Board" shall mean the Board of Trustees of the Village of Mount Prospect,
Illinois.
The term "CCDD" shall mean Clean Construction or Demolition Debris.
The term, "Contract," shall mean the written agreement between the Village and the
contractor, or between the owner and the contractor.
The phrase "Contract Documents" shall mean the Bid Documents, bidder's
submitted Bid Form, Bid Security, Bid Sheet, Contract and required bonds or letter of
cred it.
The term "Contractor," as successful bidder, shall mean the individual, firm or
corporation who shall have entered into an agreement or contract to furnish all
necessary labor, equipment, tools and materials for the performance of the work
under its bid and the Bid Documents.
The phrase "Director of Public Works" shall mean the Director of Public Works
representing the Village of Mount Prospect.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 Of 23
SECTION 007200 — GENERAL CONDITIONS: continued
The term "EPR" shall mean the Village's Engineering Project Representative.
The phrase "Final Performance Date" shall mean the date that Substantial
Performance and the punch list items must be completed.
The term "Inspector" shall mean the authorized representative of the Director of
Public Works assigned to make detailed inspection of any or all portions of the work
or materials therefore.
The phrase "Notice of Award" shall mean the written notice of award of the contract
given by the Village to the successful bidder.
The phrase "Notice to Bidders" shall mean the official notice included in the bid
inviting bids for the proposed improvements.
The phrase "Notice to Proceed" shall mean the official notice to the contractor that
will start the performance period/
The phrase "Performance Period" shall mean the time allotted for contractor to
perform the contract from start to Substantial Performance.
The term "Owner" shall mean the Village of Mount Prospect.
The phrases "Payment and Performance Bond" and "Letter of Credit" shall mean the
approved form of security furnished by the contractor and its financial institution as a
guarantee that it will execute the work and pay all material providers and
subcontractors.
The terms "Plans" or Contract Drawings" shall mean all official drawings or
reproductions of drawings pertaining to the work provided in the contract.
The phrase "Project Schedule" shall mean the critical path schedule submitted by
Contractor to the Village, which includes targeted dates of completion through the
Substantial Completion Date.
The term "Punch list" shall mean a list of items to be completed after Substantial
Performance.
The phrase "Special Provisions" shall mean any special directions and requirements
prepared to cover the method or manner of performing work on a particular project,
or cover the quantities or quality of the materials to be furnished under the contract
which are not covered herein. The special provisions included in the contract shall
govern the work and take precedence over the general provisions and STANDARD
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
SPECIFICATIONS noted above wherever they conflict therewith, but they shall not
operate to annul those portions of the general provisions with which they are not in
conflict.
The term "Specifications" shall mean the general and special provisions, instructions
and requirements contained herein, together with written agreements and all other
executed documents which describe the method of performing the work, the
quantities, or the quality of material to be furnished under the contract. Additionally,
the term specifications will refer to standard practices as outlined in the Illinois
Department of Transportation's "STANDARD SPECIFICATIONS FOR ROAD AND
BRIDGE CONSTRUCTION (R&BC), latest revision and the "STANDARD
SPECIFICATIONS FOR WATER AND SEWER MAIN CONSTRUCTION IN
ILLINOIS" prepared by the ISPE, CECT, et al, latest revision.
The term "Subcontractor" shall mean any individual, firm or corporation other than
the contractor supplying labor, equipment, tools and materials for use in the work of
the contract.
The phrase "Substantial Performance" shall mean the date that the entire Project
can be used for the purposes for which it was intended, i.e., only punch list items
remain.
The phrase "Substantial Performance Date" shall mean the date that substantial
performance must be completed.
The term Village shall mean the Village of Mount Prospect, Illinois.
The terms "Village Manager" or "Manager" shall mean the Village Manager of the
Village of Mount Prospect, Illinois or his duly appointed representative.
The terms "Work" and "Project" are used interchangeably and shall mean the
improvement advertised for letting, described in the bid form, indicated on the plans,
and covered in the specifications and contract, and authorized alterations,
extensions and deductions, including labor, tools, equipment, materials and
incidentals necessary for the satisfactory completion of the project.
The term, 1/2 stick" shall mean one-half the standard length of pipe, typically this is
seven (7) feet.
2)Award of contract; Performance; Payment.
a.Award of Contract. The Village will issue a Notice of Award to the successful bidder,
advising that it has been awarded the contract. Within ten (10) days of delivery of the
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 3 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
Notice of Award, by personal service or registered or certified U.S. mail, posted prepaid
and receipt requested, Contractor shall execute the Contract, attached to the Bid
Documents, and furnish the Village with the required bonds and certificate of insurance.
b.Notice to Proceed. Upon the Village's receipt of the executed Contract, required bonds and
certificate of insurance, the Village will issue and send to Contractor a Notice to Proceed,
which will start the performance period.
c. Substantial Performance; Final Completion.
i.The Contract shall be substantially performed within seventy (70) days after the
Notice to Proceed is effective (the Substantial Performance Date"). Substantial
Performance is when the entire Project can be used for the purposes for which it
was intended, i.e., only punch list items remain.
ii.Final completion shall be within thirty (30) days after the Substantial Performance
Date (the "Final Performance Date").
d.Project Schedule. Within ten (10) days after the Contractor executes the Contract,
Contractor shall submit to Village a Project Schedule to include targeted dates of
completion of all construction and other requirements of the Contractor through the
Substantial Completion Date. Contractor shall monitor schedule progress and provide
monthly updates and revisions of the Project Schedule, as needed to Village.
e. Liquidated Damages for Inexcusable Delay.
i. Time is of the essence. The Contractor agrees that all work included in connection
with this project must be completed by the Final Performance Date, or sooner,
after receipt of Notice To Proceed. It is hereby acknowledged and agreed by both
parties that the damages to the Village are not readily ascertainable but that the
failure to timely complete this Work will materially and significantly damage the
safety and well-being of the Village, its staff and the public, and that therefore a
sum of 1,000.00 per day is a fair and reasonable damage estimate to compensate
the Village for any such delay. If the Contractor fails to fully complete the Work
in that time, then and in this event, the Contractor further expressly agrees that,
for each day this Work and this contract shall remain uncompleted after that date,
the Village may deduct the sum of $1,000.00 per day after the Final Performance
Date, from the contract price as payment to the Village, by the Contractor of the
liquidated damages sustained by reason of failure of the Contractor to complete
the Project on or before the time aforesaid.
11. Provided, however, that if the completion of this contract is delayed by the Village,
by general strikes, acts of God, or casualty beyond the control of the Contractor,
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 4 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
then and in such event, the time of completion of this contract shall be extended
for such additional time as shall be caused by such delay.
iii. Provided, always, however, that the Contractor shall, at the time of such delay, if any,
demand of the Village, in writing, such additional time within which to complete
the performance of the Contract. The Contractor will be required to notify the
Village within three (3) days of such delay, stating the reason for same. If the
Contractor does not notify the Village in writing, within three (3) days of the
delay, no request for extension of time will be approved.
f.Measurement of Quantities. All work completed under the contract will be measured by
the Village according to United States standard measures.
g. Pam. Payment under the Contract will be made in accordance with the Illinois Local
Government Prompt Payment Act, 50 ILCS 50511 et seq.
h.Payment for Items Omitted when Partially Completed. Should the Village cancel or alter
any portion of the contract which results in the elimination or non -completion of any
portions of the work partially completed, the contractor will be allowed a fair and
equitable amount covering all items of work incurred prior to the date of cancellation,
alteration, or suspension of such work. A written change order may apply.
i.Partial Pam. When requested, the contractor will make an approximate estimate, in
writing, of the materials in place completed, the amount of work performed, and the
value thereof, at the contract unit prices. From the amount so determined, there shall be
deducted ten percent (10%) to be retained until after completion of the entire Work to the
Village for payment, except that no amount less than $500 will be so certified unless the
total amount of the contract is less than $500.
In addition, an estimate may, at the discretion of the Village and upon
presentation of receipted invoices and freight bills, be made for payment of the
value of acceptable materials delivered on the Work or in acceptable storage
places and not used at the time of such estimate. Ten percent (10%) shall be
retained from the value of such materials until final payment. Such materials,
when so paid for by the Village, shall become the property of the Village, and in
the event of default by the Village, shall become the property of the Village, and
in the event of default by the contractor, the Village may use or cause to be used
such materials in the construction of the work provided for in the contract. The
amount thus paid by the Village shall be deducted from estimates due the
contractor as the material is used in the work.
Partial payment for work or materials shall not be construed as an acceptance of
the work or any part of it, or as a waiver of any provisions of the contract. Partial
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 5 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
payment will only be granted if in the opinion of the Village sufficient labor and
materials have been expended to warrant it.
If partial payments are requested, the Contractor shall submit with each payment
request a properly completed Contractor's Affidavit setting out, under oath, the
name, address and amount due or to become due, of Contractor, each
subcontractor, vendor, supplier or other appropriate party included in its cost, and
for every party listed a full or partial waiver of lien, as appropriate. Beginning with
the second payment request, and with each succeeding payment request, the
Contractor shall submit Contractor's Affidavits and partial waivers of lien for each
subcontractor and supplier showing that the amount paid to date to each is at
least equivalent to the total value of that subcontractor's work, less retainage,
included on the previous payment request.
j.Acceptance and Final Pam. Whenever the Work shall have been completely performed
on the part of the contractor, including Punch list items, and all parts of the Work have
been approved by the Village and accepted by the Village, a final payment showing the
value of the work will be prepared by the contractor as soon as the necessary
measurements and computations can be made, all prior estimates upon which payments
have been made being approximate only and subject to correction in the final payment.
The amount of this estimate, less any partial or semifinal payments previously made and
less any sums that have been deducted or retained under the provisions of the contract,
will be paid to the contractor as soon as practicable after the final acceptance, provided
the contractor has furnished to the Village the required maintenance bond and satisfactory
evidence that all sums of money due for any labor, materials, apparatus, fixtures or
machinery furnished for the purpose of such work have been paid or that the person or
persons to whom the same may be due have consented to such final payment.
If final payment is requested, the Contractor shall submit a properly completed
Contractor's Affidavit setting out, under oath, the name, address and amount due
or to become due, of Contractor, each subcontractor, vendor, supplier or other
appropriate party included in its cost, and a full and final waiver of lien for the full
amount of the Work, less retainage. The Contractor shall assign over to the
Village all manufacturers' and suppliers' warranties respecting any part of the
Work. The Contractor shall also deliver to the Village the required maintenance
bond prior to Final Payment and upon receipt of Final Payment a set of Plans
and Specifications annotated to show the Project "as -built."
The acceptance by the contractor of the final payment shall constitute a release
and waiver of any and all rights and privileges under the terms of the contract;
further, the acceptance by the contractor of final payment shall relieve the Village
from any and all claims or liabilities for anything done or furnished relative to the
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 6 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
Work or for any act or neglect on the part of the Village relating to or connected
with the Work.
k.Punch list. The Contractor shall notify the Village when it believes substantial
performance of the entire Project has been achieved. The Village, and/or any
independent consultant engaged by the Village, shall then inspect the Project site with the
Contractor, and prepare and deliver to the Contractor within five (5) days thereafter, a
written Punch list indicating items of construction which are not in material conformity
with the Contract Documents. The Punch list items shall be completed by the Final
Performance Date. Pending completion of Punch list items, the Village may withhold
from amounts due to the Contractor an amount equal to but not greater than one and one-
half (11/2) times the estimated cost to complete Punch list items.
1.Final Policing of the Sites. Before the completed work will be ready for the Village's final
inspection, the contractor shall have removed from the project sites all surplus equipment,
machinery, materials, debris, barricades, and signs. The contractor shall leave said
project sites in the best possible condition to the complete satisfaction of the Village.
m. Final Inspection. The Village shall make final inspection of all of the Work, as soon as
practicable after notification in writing by the contractor that the work is completed and
ready for acceptance. If the Work is not acceptable to the Village at the time of such
inspection, the Village shall inform the contractor as to the particular defects to be
remedied before final acceptance can be made.
n.Alterations, Cancellations, Extensions and Deductions. The Village reserves the right to
alter the plans, extend or shorten the improvement, add such incidental work as may be
necessary, and increase or decrease the quantities of work to be performed to accord with
such changes, including the deduction or cancellation of any one or more of the unit price
items. Such changes shall not be considered as a waiver of any condition of the contract
nor to invalidate any of the provisions thereof. A written change order may apply.
All Work shall be done under the supervision of the Village's Director of Public
Works, or a designated representative who shall decide all questions which arise
as to the quality and acceptability of materials furnished, work performed,
manner of performance, rate of progress of the work, interpretation of the plans
and specifications, acceptable fulfillment of the contract, compensation and
disputes and mutual rights between contractors under the specifications.
l.Change Orders. The Village may from time to time require changes in the Work. Such
changes shall comply with Section 33-E9 of the Criminal Code, 720 ILCS 5/33E-9.
m. Right of the Village to Terminate the Contract.
.o .e
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 7 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
i. If the Contractor fails to begin the Work under the Contract within the time
specified, or fails to perform the Work in accordance with the terms of the
approved schedule or performs the Work in a manner unacceptable to the Village,
or neglects or refuses to remove materials or perform anew such Work as has
been re j ected by the Village, or if the Contractor shall become insolvent or be
declared bankrupt, or shall make an assignment for the benefit of creditors, or
from any other cause whatsoever shall fail to carry on the Work in a manner
required by the Contract, the Village shall give notice as hereinafter provided to
the Contractor and its surety in writing specifying such failure, delay, neglect,
refusal or default, and if the Contractor, within a period of ten (10) calendar days
after the giving of such notice, shall not proceed in accordance therewith, then the
Village shall have full power and authority to declare the this Contract and the
Contractor in default, and to forfeit the rights of the Contractor in this Contract.
ii.Upon declaration of Contractor's default, the Village may, at its option, call upon the
surety to complete the Work in accordance with the terms of this Contract or may
take over the Work, including any materials on the Work site as may be suitable
and acceptable to the Village and may complete the Work by its own forces or on
its own account, or may enter into a new contract or contracts for the completion
of the Work, or may use such other methods as shall be required for the
completion of the Work in an acceptable manner as the Village may in its
discretion determine.
iii. All costs and charges incurred by the Village, together with the cost of completing
the Work shall be deducted from any moneys due or which may become due on
this to the Contractor under this Contract. Following any payment due and
received by the Village from the Contractor's surety following default, if the
expense so incurred by the Village is less than the sum paid to the Village by the
surety under this Contract for work remaining, the surety shall be entitled to
receive the excess difference paid to the Village. When such Contractor default
costs incurred by the Village exceeds the sum paid to the Village for the work
remaining under the Contract the Contractor and the surety shall be liable and
shall pay to the Village the full cost of such additional expenses.
3)Performance of the Work.
a.Accident Prevention. The contractor shall exercise every precaution at all times for the
protection of persons and properties. The safety provisions of all applicable laws and
ordinances shall be strictly observed. Any practice obviously hazardous, in the opinion
of the Director of Public Works or his authorized representative, shall be immediately
discontinued by the contractor upon his receipt of instructions from the Director of Public
Works or an authorized representative to discontinue such practice.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 8 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
b. Barricades and Warning Signs and Lights. The contractor shall erect substantial
lighted barricades to protect its work at all points deemed necessary by the
Director of Public Works; said contractor shall place at such points the necessary
warning signs, amber lights, caution tape, and other suitable devices to protect
his work properly and to provide for the convenience and safety of the public at
all times. The contractor shall maintain such barricades, signs, lights and
protective devices until the need for them, in the judgment of the Public Works
Director of an authorized representative, has passed.
Contractor shall provide warning signs and barricades to safely mark any
hazards or detours caused by the work. All such warning signs and barricades
for work in, or affecting Village of Mount Prospect streets, access roads, and
state highways shall meet all applicable requirements as stipulated in the latest
edition of the Manual for Uniform Traffic Control Devices published by the U.S.
Department of Transportation. All costs for barricades, signs including all labor
and other associated materials shall be incidental to the fixed unit price bid for
the specific repair or pay item.
c. Cooperation with Utilities. It is understood and agreed that the contractor has considered in
its bid all of the permanent and temporary utility appurtenances in their present or
relocated positions that may be encountered during construction and no additional
compensation will be allowed for any delays, inconvenience, or damage sustained by it
due to any interference from the said utility appurtenances either by the utility company
or by it, or on account of any special construction methods required in prosecuting its
work due to the existence of said appurtenances either in their present or relocated
positions. The contractor shall insure that prompt repairs are, to the approval of the
inspector, made to any utility appurtenances damaged by it without compensation from
the Village.
During performance of the work, Contractor shall protect all utilities and property
from damage. Contractor shall spot all utilities prior to any excavation work.
Contractor shall call J.U.L.I.E. one Call System (1-800-892-0123), and request
utility locations as soon as possible for emergency repairs and within forty-eight
(48) hours for non -emergency work prior to excavation in strict accordance with
J . U . L. I . E. one Call System operation procedures.
d. Clean-up. After all work under each task phase of the work is completed, the Contractor
shall remove all loose debris and other materials not incorporated in the work from the
site of the work. Any clean up or restoration to private property will be the responsibility
of the Contractor.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 9 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
e. Construction Noise Restriction. All construction activities or alteration operations within
the Village shall be performed only between the hours of 8:00 a.m. and 7:00 p.m.
Variations from these time limitations shall be allowed only in the case of maintenance of
operation of safety and traffic control devices such as barricades, signs and lighting, or to
construction of an emergency nature. More stringent requirements may be assessed for
work in state highway or railroad rights-of-way." Working hours outside these times
must receive prior approval from the Village.
f. General. The work to be performed under the contract includes the furnishing of all
supervision, labor, materials, tools, equipment and incidentals of every kind and
description necessary for construction, in accordance with the Contract Documents.
g. Inspection. All materials and each part or detail of the work shall be subject at all times to
inspection by the Village or its inspectors, and the contractor will be held strictly to the
true intent of the Specifications in regard to quality of materials, workmanship and
diligent execution of the contract. The Village or its inspectors shall be allowed access to
all parts of the work and shall be furnished with such information and assistance by the
contractor as is required to make a complete and detailed inspection. Materials,
components or completed work not complying therewith may be rejected by the Village
and shall be replaced by the Contractor at no expense to the Village. Any rejected
material or component shall be removed at the entire expense of the Contractor, after
written notice has been mailed by the Village to the Contractors that such materials or
components have been rejected.
The contractor shall, if the Village requests, remove or uncover such portions of
the finished work as the Village may direct before final acceptance of the same.
After the examination, the contractor shall restore said portion of the work to the
standard required by the Specifications. If the work thus exposed or examined
proves acceptable, the expense of uncovering or removing and the replacing of
the parts removed shall be paid for as extra work; but if the work so exposed or
examined is unacceptable, the expense of uncovering or removing and replacing
of the same shall be borne by the contractor.
h. Materials and Equipment. Except where the Specifications indicate otherwise, the Village
is not responsible for providing any tools, equipment or storage under the contract in
order to permit its completion of any contractual obligations under the contract, which
may be awarded as the result of the bid.
i.Personnel and Equipment. The contractor shall provide an adequate number of competently
trained personnel with sufficient supervision to provide the services required, and
contractor shall provide identification of its personnel if requested by the Village.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 10 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
Any contractor's employee whose employment is reasonably detrimental or
objectionable to the Village shall be immediately transferred from the work -site
upon the Village's request. The exercise of this option shall not be construed as
placing the Village in charge of the Work or making the Village responsible for
safety.
All on the road vehicles or equipment shall be identified by the contractor's name
for purpose of identification.
All tools or equipment required to carry out the operations within the scope of the
contract shall be provided by the Contractor, and shall meet the standards of the
Federal Occupational Safety and Health Act and State of Illinois safety codes as
may be required by law. The Village reserves the right to inspect the equipment
that will be used prior to award of Bid.
j.Property Protection. No vehicles of any kind shall be placed, parked or operated upon or
over any sodded areas.
k.Protection and Restoration of Property. It is understood that in the execution of the Work
herein provided for there may be interference with and/or damage to trees, shrubbery,
crops, fences, railroad tracks, overhead structures such as poles, wires, cables,
underground structures such as sewers, gas mains, telephone conduits and cables, water
mains, drains, service connections, wires, pipes, conduits, located along, adjacent to,
and/or crossing the locations of the Work, and that it may be necessary to relocate or
reconstruct certain of such structures, improvements, and installations and/or to make
repairs to the same by reasons of doing the Work herein provided for, and it is therefore
particularly and specifically agreed that the Bidder except as otherwise herein provided,
shall do the Work necessary for such relocation, reconstruction, and repair and shall bear
and pay all of the cost and expense of such relocation, reconstruction, and/or repair of,
and all damage done to any and all such pipe line and other structures, improvements,
and installations, including service connections, if any, to adjacent property, existing at
the date of the execution of the contract and/or existing, during the period of the Work to
be done under the contract, which may be interfered with, damaged, and/or necessarily
relocated, reconstructed, or repaired in the performance of the Work herein provided for,
including the restoration and resurfacing of unpaved portions of public streets and alleys,
rights-of-way, easements, and private property damaged or disturbed by the Work, the
same to be restored to as good condition as the same existed at the time of the
commencement of any such Work or relocation.
It is further agreed that the owners of any structures, improvements, installations,
referred to in the preceding paragraph shall have the right to do the Work or any
part thereof necessary for the relocation, reconstruction, replacement, repair, and
other Work required by reason of any interference with and/or damage to such
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page I I of 23
SECTION 007200 — GENERAL CONDITIONS: continued
structures, improvements, installations, due to the prosecution of the Work and
upon completion of such Work by them done, said owners may render bills to the
Bidder for the cost and expenses thereof which bills shall be paid by the Bidder
without extra compensation therefore from the Village, upon demand by said
owners, or upon demand made by the Village upon the Bidder for the payment
thereof.
1.Public Convenience and Safety. The contractor shall notify the Director of Public Works
at least three (3) days in advance of the starting of any construction work which might in
any way inconvenience traffic, and the contractor shall at all times conduct the work in
such a manner as to insure the least obstruction to vehicular and pedestrian traffic.
Whenever possible, the contractor shall provide and maintain at his own expense such
temporary roads and approaches as may be necessary to provide access to driveways,
houses, buildings or other property abutting the improvements. In no case will the
contractor obstruct entrance ways into private property without first seeking the Village
and private property owner's approval.
m.Public Relations. The Contractor shall cooperate with the Village of Mount Prospect in
maintaining a high degree of sensitivity to the needs of property and business owners
along the project route. Contractor will distribute written public work notices to
businesses and residences as required by the Village.
n.Removal of Defective and Unauthorized Work. Work done without lines and grades being
given, or beyond the lines shown on the plans or as given, except as herein provided, or
any extra work done without authority will be considered as unauthorized and at the
expense of the contractor, and will not be measured or paid for. Work so done may be
ordered removed or replaced at the contractor's expense.
All work which has been ordered to be removed or replaced shall be remedied or
removed and replaced by the contractor in a manner approved by the Village at
the contractor's expense. Upon failure of the contractor to comply promptly with
any order of the Village made under this provision, the Village shall, after giving
written notice to the contractor, have the authority to cause defective work to be
remedied, or removed and replaced, or to cause unauthorized work to be
removed, and deduct the cost thereof from any compensation due or to become
due the contractor.
o. Scheduling. The contractor shall consult with the Village's Public Works Director or an
authorized representative concerning the details and scheduling of the work contemplated
herein, and shall be governed by the decisions of said Director or representative.
p. Supervision. The contractor shall at all times have a competent person in charge of its work
crew at the job site to whom the Village representative may issue directives. Such person
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
Section 007200
Ground Storage Tank Page 12 of 23
April 2019
SECTION 007200 — GENERAL CONDITIONS: continued
shall be authorized to accept and act upon such directives. Such person shall be fluent in
the English language.
q.Traffic Control. Contractor shall maintain traffic flow(s) and accessibility to private
property(s) as close to normal condition as possible. Contractor shall notify residents,
Village of Mount Prospect and state/county officials, as appropriate, of any driveway or
road closure.
The contractor shall abide with the Illinois Department of Transportation's
Standard Specifications for Road and Bridge Construction, latest edition. The
Contractor shall also abide with the Manual on Uniform Traffic Control Devices,
latest edition. Contractor shall also provide sufficient flag persons to assist with
traffic control during operation.
Traffic control costs to close the street or ROW is to be included in the "all-
inclusive" unit price of the pay item and considered as incidental to that pay item
and will not be considered an extra line item.
r. Tree Protection. All tree protection shall be incidental to the contract and shall be installed
and maintained in accordance with the Tree Protection Ordinance and plan as specified
by the Village. Tree protection fencing shall be paid for per FOOT of TEMPORARY
FENCING.
REMOVAL PROHIBITED UNLESS AUTHORIZED: All trees shall be maintained,
saved, and protected from damage unless removal is approved by the Village.
CRITICAL ROOT ZONE: To prevent unnecessary damage to existing public
trees during construction, proper tree protection guidelines must be followed,
particularly in the root zone where major support roots securely hold the tree in
the soil. This Critical Root Zone (CRZ) is defined as the entire ground area
within the vertical projection of the crown of a tree. This is also commonly
referred to as the area within the drip line of a tree.
Power equipment may not be used to excavate soil, change grades, or dig
trenches in the Critical Root Zone. All soil excavation done within the CRZ must
be done by hand, except as authorized in these specifications. Exceptions to the
above shall be granted only with written permission from the Director of Public
Works.
FENCING: All unpaved ground on public property within the Critical Root Zones
(CRZ) of existing trees subject to construction damage shall be fenced before
any work is started. This Tree Protection Fencing will be paid for as specified in
these contract documents. Once assembled, no fencing shall be removed
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 13 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
without prior approval of the Engineer, and there shall be no construction activity
or material including storage, stockpiling, and equipment access within the
enclosure. Fencing material shall be orange polypropylene snow fence
supported with metal posts, and installed according to the detail which will be
provided by the Forestry Division.
CHANGES TO EXISTING GRADE: No changes to original grade shall be
allowed inside the CRZ.
ROOT PRUNING DURING CONSTRUCTION: All tree roots greater than two
inches (2") in diameter that are encountered in any construction process shall be
cut cleanly with an appropriate saw or pruning shear or other tool specifically
designed for cutting wood. Axes or other such chopping tools shall not be used.
Shovels or other tools designed for digging shall not be used. Contractor shall
contact Forestry for a root inspection before backfilling.
ATTACHMENTS TO TREES: No signs, placards or other objects may be nailed
or stapled to trees.
BRANCH REMOVAL: Tree branches shall not be cut, pruned or trimmed by the
Contractor. If parkway tree branches interfere with the Contractor's work, he
should contact the Forestry Division to request pruning. If Forestry deems the
request reasonable they will endeavor to promptly prune the branches at the
Village's expense.
PENALTIES FOR TREE DAMAGE: Where limbs, trunks or roots of trees not
approved for removal are damaged, the Village shall determine whether the tree
can be repaired or must be removed. Repairs may include, but are not strictly
limited to, pruning of broken limbs, removal of loose bark and proper shaping of
wounds, thinning of the crown to compensate for root loss, fertilization,
straightening and staking.
Repairs shall be performed by the Village. The cost of such repairs shall be paid
for by the Contractor to the Village, using rates listed in the current edition of the
Village's Equipment and Labor Rate Charges. Additionally, the Village may fine
the contractor for unnecessary tree damage according to the schedule listed in
Appendix A, Division III of the Village Code.
If in the opinion of the Village, the amount of damage warrants removal of the
tree due to safety or aesthetic concerns, the Contractor shall remove the tree,
along with its stump to a depth of 12 inches below grade. The Contractor shall
pay the Village for replacement of the tree. Replacement cost will be determined
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 14 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
by multiplying the diameter of the damaged tree, as measured 4-1/2 feet above
the ground, by the rate of $150.00/inch.
The Contractor shall be responsible for being familiar with and complying with all
aspects of the Village of Mount Prospect Tree Protection ordinances and
Arboricultural Standards Manual as they relate to the various site locations. Any
questions regarding tree protection shall be directed to the Village Forestry
Division and their response or direction shall be considered as the final
word/decision on tree protection issues. Any costs for tree protection fencing,
posts, labor or other associated labor or material shall be incidental to the fixed
cost per unit bid.
s.Work In Street Right — of — WaY. All of contractor's construction work in street rights-of-
way shall be done in strict accordance with the applicable controlling public agency's
construction specifications, permitting, bonding, rules, and regulations.
All costs for necessary permits and bonds shall be borne by the Contractor and
considered incidental to the fixed item price of the applicable work.
Contractor shall coordinate with the proper public officials and receive approval
from said officials prior to any street closings or detouring required due to the
work to be performed.
Contractor shall protect existing vegetation from removal or damage wherever
possible. Contractor shall confine construction work to specified construction
limits as shown on the drawings or defined in the specifications. Should
Contractor damage or remove any vegetation outside the construction limits,
Contractor shall restore the affected area to its original state at no expense to the
Village.
4)BOND; INSURANCE; INDEMNIFICATION.
a.Performance and Labor and Material Payment Bond. Upon submission of the executed
contract to the Village, Contractor shall furnish to the Village a surety bond in the amount
one hundred and ten percent (110%) of the bid for the faithful performance of the
Contract and to indemnify the Village against loss. The Contractor shall also furnish a
labor and materials bond in the amount one hundred and ten percent (110%) of the bid to
ensure payment for all labor and materials, including compliance with the provisions of
law relating to the payment of the prevailing rate of wages. The premium of such bonds
is to be paid by the Contractor. The surety must be with a substantial surety company
satisfactory to the Village and authorized by law to do business in the State of Illinois and
endorsed by a local representative of said surety company. All payment and performance
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 15 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
bonds shall name the Village of Mount Prospect as Obligee and be written upon forms
prepared or approved by the Village. Said bonds may be satisfied with a Letter of Credit,
in the form acceptable to the Village, from a bank or savings and loan within the Chicago
metropolitan area. The bonds and Letter of Credit shall remain in effect during the full
term of the Contract and any extension thereof. Failure to so provide these bonds or
Letter of Credit shall result in forfeiture of the bid bond/Letter of Credit to the Village as
liquidated damages and not as a penalty, and the termination of the contract and/or
withdrawal of the award.
b.Insurance Requirements. In submission of a bid, the bidder is certifying that it has all
insurance coverages required by law or that would normally be expected for bidder's type
of work. In addition, the bidder is certifying that, as successful bidder/Contractor, upon
execution of the Contract, it will provide Insurance of such types and in such amounts as
may be necessary to protect itself and the interests of the Village against all hazards or
risks of loss contemplated by the Contract. The Village shall be named as additional
insured on all applicable insurance policies. Satisfactory certificates of insurance shall be
filed with the Village upon execution of the Contract. The certificates shall state that
thirty (30) days advance written notice will be given to the Village before any policy
covered thereby is changed or canceled.
Insurance coverage shall be in the following minimum amounts:
Limit/ Limit/
Type of Insurance Ea. Occurrence Aggregate
General Liability
Bodily Injury $1)0007000 $370007000
Property Damage $1,000,000 $3,000,000
Contractual Ins. $1)0007000 $3)0007000
Automobile Liability
Bodily Injury
Property Damage
Workers Compensation
Employee Claims
Employers Liability
$1, 000, 000 $1)000)000
$1)0001000 $1,000)000
Statutory for Illinois
$1,000,000 per accident
c. Indemnification. The Contractor shall indemnify_and save harmless the Village, its officers
and employees from any and all liability, losses or damages, including attorneys fees and
costs of defense, the Village may suffer as a result of claims, demands, suits, actions or
proceedings of any kind or nature, including workers' compensation claims, in any way
resulting from or arising out of the operations of the Contractor under the Contract,
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
Section 007200
Ground Storage Tank Page 16 of 23
April 2019
SECTION 007200 — GENERAL CONDITIONS: continued
including operations of subcontractors; and the Contractor shall, at his own expense,
appear, defend, and pay all fees of attorneys and all costs and other expenses arising
therefrom or incurred in connection therewith; and, if any judgments shall be rendered
against the Village in any such action, the Contractor shall, at his own expense, satisfy
and discharge same. The Contractor expressly understands and agrees that any bonds,
letters of credit or insurance protection required by the Contract, or otherwise provided
by the Contractor, shall in no way limit the responsibility to indemnify, keep and save
harmless and defend the Village as herein provided.
Contractor agrees to defend and hold harmless the Village from and against all
demands, claims, suits, costs, expenses, damages and adjustments based upon
any infringement of any patent relating to goods specified in the contract, and on
account of the Village's use of any copyrighted or uncopyrighted, composition,
trade secrets, secret process, proprietary rights, patented of unpatented
invention, article or appliance furnished or used under the bid Specifications.
5)Compliance with Laws.
a. Collusion. If at any time it shall be found that the person, firm, or corporation to whom the
Contract has been awarded has, in presenting any proposal or proposals, unlawfully
colluded with any other party or parties, then the Contract so awarded shall be null and
void and the Consultant and his sureties shall be liable to the Village for all loss or
damage which the Village may suffer thereby, and the Village may advertise for new bids
for said work.
b. Observance of Laws, Ordinances, and Regulations; Certifications of Compliance with
Applicable Laws. The contractor shall, at all times during the life of this contract,
observe and abide by all federal, state and local laws which in any way affect the conduct
of the work and with all decrees and orders of courts or agencies of competent
jurisdiction. Likewise, said contractor shall be governed by all municipal ordinances and
regulations which in any way affect the conduct of the work. The contractor shall
indemnify and save harmless the owner, its officers, agents, and employees against any
claim or liability arising from or based on his violation of any law, ordinance, regulation,
decree or order.
The bidder and contractor, as successful bidder, shall comply with all applicable
state, federal and local laws, including, but not limited to the following:
i. Bid Rigging/Rotating. By submitting a bid, the Contractor certifies that no owner,
officer or director is barred from contracting with any unit of state or local
government as a result of violating the bid rigging or bid rotating provisions
contained in 720 ILLS 5/33E-3 & 33E-4.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 17 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
ii. Tax Pam. The Contractor certifies that it is not delinquent in the payment of any
taxes to the Illinois Department of Revenue. (65 ILLS 5/11-42.1-1)
iii. Drug Free Workplace Act. The Contractor will comply with the requirements of the
Drug Free Workplace Act if the contract is $5,000 or more and it has more than
24 employees at the time of entering into the contract (30 ILCS 580).
iv.Preference to Veterans Act. The Contractor will comply with the Preference to
Veterans Act (330 ILCS 55).
v. Substance Abuse Prevention Program. By submitting a bid, the Contractor certifies
that the company has in place, to the extent not covered by a collective bargaining
agreement that deals with the subject of the Act, a substance abuse prevention
program that meets or exceeds the requirements of the Substance Abuse
Prevention in Public Works Projects Act, 820 ILCS 265/1 et seq.
vi.Non-Discrimination. The Contractor will comply with the Illinois Public Works
Employment Discrimination Act (775 ILCS 10/1, et seq.)
vii. Equal employment Opportunity. The Contractor will comply with Article 2 of the
Illinois Human Rights Act (775 ILCS 5/2-101, et seq.), including establishment
and maintenance of a sexual harassment policy as required by Section 2-105, and
the Rules and Regulations of the Illinois Department of Human Rights, including
the EQUAL EMPLOYMENT OPPORTUNITY CLAUSE, which is a material
term of all public contracts, as follows:
EQUAL EMPLOYMENT OPPORTUNITY
In the event of the contractor's non-compliance with the provisions of this
Equal Employment Opportunity Clause or the Act, the contractor may be
declared ineligible for future contracts or subcontracts with the State of
Illinois or any of its political subdivisions or municipal corporations, and the
contract may be cancelled or voided in whole or in part, and other
sanctions or penalties may be imposed or remedies invoked as provided
by statute or regulation. During the performance of this contract, the
contractor agrees as follows:
1) That he or she will not discriminate against any employee or applicant for
employment because of race, color, religion, sex, sexual orientation,
marital status, order of protection status, national origin or ancestry,
citizenship status, age, physical or mental disability unrelated to ability,
military status or an unfavorable discharge from military service; and,
further, that he or she will examine all job classifications to determine if
minority persons or women are underutilized and will take appropriate
affirmative action to rectify any underutilization.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 18 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
2) That, if he or she hires additional employees in order to perform this
contract or any portion of this contract, he or she will determine the
availability (in accordance with this Part) of minorities and women in the
areas from which he or she may reasonably recruit and he or she will hire
for each job classification for which employees are hired in a way that
minorities and women are not underutilized.
3) That, in all solicitations or advertisements for employees placed by him or
her or on his or her behalf, he or she will state that all applicants will be
afforded equal opportunity without discrimination because of race, color,
religion, sex, sexual orientation, marital status, order of protection status,
national origin or ancestry, citizenship status, age, physical or mental
disability unrelated to ability, military status or an unfavorable discharge
from military service.
4) That he or she will send to each labor organization or representative of
workers with which he or she has or is bound by a collective bargaining or
other agreement or understanding, a notice advising the labor
organization or representative of the contractor's obligations under the Act
and this Part. If any labor organization or representative fails or refuses to
cooperate with the contractor in his or her efforts to comply with the Act
and this Part, the contractor will promptly notify the Department and the
contracting agency and will recruit employees from other sources when
necessary to fulfill its obligations under the contract.
5) That he or she will submit reports as required by this Part, furnish all
relevant information as may from time to time be requested by the
Department or the contracting agency, and in all respects comply with the
Act and this Part.
6) That he or she will permit access to all relevant books, records, accounts
and work sites by personnel of the contracting agency and the Department
for purposes of investigation to ascertain compliance with the Act and the
Department's Rules and Regulations.
7) That he or she will include verbatim or by reference the provisions of this
clause in every subcontract awarded under which any portion of the
contract obligations are undertaken or assumed, so that the provisions will
be binding upon the subcontractor. In the same manner as with other
provisions of this contract, the contractor will be liable for compliance with
applicable provisions of this clause by subcontractors; and further it will
promptly notify the contracting agency and the Department in the event
any subcontractor fails or refuses to comply with the provisions. In
addition, the contractor will not utilize any subcontractor declared by the
Illinois Human Rights Commission to be ineligible for contracts or
subcontracts with the State of Illinois or any of its political subdivisions or
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 19 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
municipal corporations. Title 44, Part 750, Section 750, APPENDIX A,
Illinois Administrative Code,
viii. PREVAILING WAGE. This contract calls for the construction of a "public work"
within the meaning of the Illinois Prevailing Wage Act, 820 ILCS 130/1, et seq.,
as amended (the "Act"). The Contractor and all subcontractors are required to
pay wage rates in accordance with the Act to all laborers, workers and mechanics.
The Village has adopted the prevailing wages as determined by the Illinois
Department of Labor ("IDOL") for Cook County. The prevailing rate of wages is
revised by the IDOL and is available on the IDOL website,
www.state.il.us/agency/idol/rates/rates.HTM. The Contractor and all
subcontractors are solely responsible for checking the Department's website for
revisions to prevailing wage rates. In the event that the IDOL should revise the
prevailing rate of wages, then the revised rates shall apply to this Contract. In no
case shall any revision in the rates of prevailing wages result in an increase in the
total Contract price.
All bonds provided by the Contractor under the terms of this Contract shall
include such provisions as will guarantee the faithful performance of the
Contractor's obligations under this clause and under the Prevailing Wage
Act, 820 ILCS 130/1 et. seq.
Contractor shall comply with all applicable provisions of the Prevailing
Wage Act, including, but not limited to, the requirements of Section 5 of
the Prevailing Wage Act, 820 ILCS 130/5. The Contractor, and all
Subcontractors and Sub -Subcontractors participating on the Project, shall
make and keep those records required under Section 5 of the Prevailing
Wage Act in paper or electronic format. In conformance with the Act, each
contractor and subcontractor, or other entity performing work on the
project, shall maintain records of all laborers, mechanics and other
workers employed by them on the project, including the following
information on each worker: (1) name; (2) address; (3) telephone number
when available; (4) social security number; (5) classification or
classifications; (6) gross and net wages paid in each pay period; (7)
number of hours worked each day; (8) starting and ending times of each
day; (9) hourly wage rate; (10) hourly overtime wage rate; (11) hourly
fringe benefit rates; (12) the name and address of each fringe benefit fund;
(13) the plan sponsor of each fringe benefit, if applicable; and (14) the
plan administrator of each fringe benefit, if applicable. These records shall
be kept by the participating contractor and subcontractor for a period of
not less than five (5) years from the date of last payment on the contract
or subcontract. No later than the 15th day of each calendar month, each
participating contractor and subcontractor shall submit a monthly certified
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 20 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
payroll to the Village consisting of the above -referenced information as
well as a statement signed by the participating contractor or subcontractor
that certifies: (a) the records are true and accurate; (b) the hourly rates
paid to each worker is not less than the general prevailing rate of hourly
wages required under the Prevailing Wage Act; and (c) the contractor or
subcontractor is aware that filing a certified payroll that he or she knows to
be false is a Class A misdemeanor.
ix. Compliance with Freedom of Information Act Request. Section 7 of the Illinois
Freedom of Information Act (FOIA), 5 ILLS 140/7, applies to public records in
the possession of a party with whom the Village of Mount Prospect has
contracted. The Village of Mount Prospect will have only a very short period of
time from receipt of a FOIA request to comply with the request and there is a
significant amount of work required to process a request including collating and
reviewing the information.
The bidder/contractor acknowledges the requirements of FOIA and agrees
to comply with all requests made by the Village of Mount Prospect for
public records (as that term is defined by Section 2(c) of FOIA) in the
undersigned's possession and to provide the requested public records to
the Village Mount Prospect within two (2) business days of the request
being made by the Village of Mount Prospect. The bidder/contractor
agrees to indemnify and hold harmless the Village of Mount Prospect from
all claims, costs, penalties, losses and injuries (including but not limited to,
attorney's fees, other professional fees, court costs and/or arbitration or
other dispute resolution costs) arising out of or relating to its failure to
provide public records to the Village of Mount Prospect under the contract.
x. Work Guaranty.
1. Maintenance Bond. A maintenance bond or a maintenance letter of
credit is required. This maintenance bond or maintenance letter of
credit amount shall consist of ten percent (10%) of the final project
cost; it shall be posted by the contractor with the Village upon
completion of all Work; and it shall be valid and effective for a period of
two (2) years after the final acceptance of such Work by the Village for
the purpose of guaranteeing against and securing the correction of any
defect in material or workmanship furnished for such improvements,
latent in character and not discernible at the time of final inspection or
acceptance by the Village of Mount Prospect.
2. General Guaranty. Neither partial or final payment, nor any provision
in the contract, nor partial or entire use of the product/Work embraced
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 21 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
in the contract by the Village or the Public shall constitute an
acceptance of work not done in accordance with the contract, or
relieve the contractor of liability in respect to any express warranties or
responsibility for failure to comply with the terms of those contract
documents.
Unless otherwise expressly provided in the Specifications, in the event
any defects or imperfections in the materials or workmanship to be
furnished by the contractor herein appear within the period of two (2)
years from the date of completion of all the Work and acceptance
thereof by the Village, the contractor will, upon notice from said Village
(which notice may be given by letter to said contractor to the business
address of the contractor shown in the proposal), repair and make
good at his own cost any such defects or imperfections and replace
any defective or imperfect materials or workmanship with other
materials or workmanship satisfactory to said Village, and furnish all
such new materials and labor as may be necessary to do so; and in
the event of the failure, refusal or delay of said workmanship or
materials said Village may do so or have same done by others, and
said contractor and surety or sureties on the bonds given for the
faithful performance of the contract shall be liable to the Village for all
damages and expenses occasioned by such failure, refusal or delay.
All details of warranties shall be included with the bid. Warranty work
shall be at no additional expense to the Village.
Manufacturer warranties and guaranties shall be submitted with the bid
and shall be considered a part of the contract where such
specifications meet the minimum bid Specifications.
xi. Miscellaneous Contract Requirements
1. Contract Alterations. No amendment of a contract shall be valid unless
made in writing and signed by the Village President, Village Manager, or
their authorized representative.
2. Licenses and Permits. The Contractor shall procure at its own expense all
necessary licenses and permits in connection with the work under the
Contract.
3 .Nonassi e nability. The contractor shall not assign the contract, or any part
thereof, to any other person, firm or corporation without the previous
written consent of the Village. Such assignment shall not relieve the
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 22 of 23
SECTION 007200 — GENERAL CONDITIONS: continued
contractor from its obligations or change the terms of the contract unless
agreed by the Village at its sole discretion.
4.Notices. All notices required by the contract shall be given in writing.
5. Taxes. The contractor shall pay all federal, state and local taxes as may be
applicable on all materials, labor and services furnished by it under the
contract, and the amounts of such taxes shall be included in the unit prices
bid.
Village of Mount Prospect Section 007200 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 23 of 23
Section 007300
SUPPLEMENTAL CONDITIONS
SCOPE. These Supplemental Conditions amend or supplement the General Conditions and other
provisions of the Contract Documents as indicated herein. All provisions which are not so amended or
supplemented remain in full force and effect.
I . Article 1 — Definitions and Terminology
a. SC1.01-Defined Terms
1. Owner: Village of Mount Prospect
2. Engineer: Village' Engineering Project Representative (Burns &McDonnell)
2. Article 2 —Preliminary Matters
a. SC 2.02 —Copies of Documents
1. Owner shall furnish to Contractor up to five (5) printed or hard copies of the Drawing
and Specifications. Additional copies will be furnished upon request at the cost of
reproduction.
1. The following is added as Section 5.03 C:
Each policy must list the Village, Mount Prospect Park District and Burns & McDonnell as
additional insureds. The Contractor and all Subcontractors waive subrogation rights against the
Village, Mount Prospect Park District and Burns & McDonnell for all losses. Such insurance
shall apply as primary insurance with respect to any other insurance or self-insurance program
afforded to the Village of Mount Prospect, Mount Prospect Park District and Burns &
McDonnell. There shall be no endorsement or modification of such insurance to make it excess
over other available insurance, and alternatively, if the insurance states that it is excess or pro
rata, it shall be endorsed to be primary with respect to the Village of Mount Prospect, Mount
Prospect Park District and Burns & McDonnell.
The insurance required shall include all major division of coverage and shall be on a
comprehensive general basis including Premise and Operations (including X -C -U), Products and
Completed Operations, and Owned, Non -owned, Leased, and Hired Motor Vehicles. Such
insurance shall be written for not less than any limits of liability required by law or the limits
referenced in Section "General Conditions " of Village of Mount Prospect Front -End
Specifications, paragraph 4(b) — Insurance Requirements.
The Village reserves the right, at its sole discretion, to amend the insurance requirements contained
herein.
All insurance shall be written on an occurrence basis, unless the Village of Mount Prospect
approves in writing coverage on a claims -made basis. Coverages whether written on an
occurrence or a claims -made basis shall be maintained without interruption from the date of
commencement of the Work until the date of final payment and termination of any coverage
required to be maintained after final payment.
Village of Mount Prospect Section 007300 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page I of 2
SECTION 007300 — SUPPLEMENTAL CONDITIONS: continued
Certificates of Insurance acceptable to the Village of Mount Prospect and confirming the
insurance coverage required herein are attached to the Contract. The Village shall have no
obligation to execute the Contract and may award the Contract to the next lowest responsible and
responsive bidder, if such insurance certificates have not been provided to the Village within five
(5) business days after presentation of the Contract to the Contractor for execution.
The Contractor shall furnish to the Village copies of any endorsements that are subsequently
issued amending limits of coverage.
2. Article 14 shall be amended to require current waivers of lien and certified payrolls with all pay
requests. This requirement will also apply to all subcontractors retained by the Contractor.
END OF SECTION 007300
Village of Mount Prospect Section 007300 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 2
O
O
.O
W
CA
Im
c
N
N
I�
M
r -i
I�
L n
M
r -I
r -i
00
r I
L n
�
r%,L
n
N
M
N
Q1
r -I
N
I�
I�
I�
l0
.
Ol
00
N
ui
t.0
N
t0
t0
M
00
M
I�
l0
M
�
t.0I*
O
V
m
Lr)
Lr)
Ol
Lr)
>
O
O
O
O
O
O
O
N
O
O
O
N
M
O
O
o
o
o
o
oq
o
o
o
o
o
00
I�
N
N
r -I
M
N
l0
00
N
N
r -I
l0
r -I
to
00
r-_
r i
Lr)
l0
O1
r*-_
Ln
N
L n
00
Ol
:::1-O
O
N
r1
Ln
to
r*-.
r -I
r -I
Lr)
f)
-:::I:M
ui
000
00
=
N
r1
ON
�
O
�
N
M
r�
l0
(.6
4
r4
M
M
N
O
lD
r�
N
00
00
ar
-I
r -I
r i
N
r
r -I
r -I
r -I
r1 l
r1
r -I
N
r -I
N
r -I
N
r l
r l
r i
r i
cl
dl
I�
I�
00
M
00
Ln
01
I�
r -I
q;J-
W
�
dl
N
dl
00
M
I�
I�
M
W
r -I
�
N
Ol
O
r -I
4
O
00
rqM
r -I
ui
ui
M4
N4
4
r4
N6
O
4
00
M
I
r -I
w
r -I
r -Ir
l
-Ir
l
r -I
m
Ol
r -i
r -i
r -i
r -i
r -i
r -i
rl
r -i
r -i
I�
r -i
r -i
r -I
r -i
r -i
O
=
N
�
N
N
N
N
N
N
N
N
N
N
N
�
N
N
N
N
N
N
N
N
N
N
N
H
Oo
0
O
N
�
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
(N
N
N
(*-4
N
N
N
N
N
N
0
4-0
�..�
Lr)
Lr)
Ln
N
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
N
Lq
N
ul
N
Lq
Ln
Ln
Ln
Ln
Ln
Ln
Ln
o
N
l
r -I
r -I
r -I
r -I
r -I
r -I
r -I
r -I
r -I
r -I
r -I
r-)
r -I
r -I
r -I
r -I
r-)
r -I
r -I
r -I
r -I
O
9I V
O�
LL.CC�
M
LI)
M
Lf)
M
N
N
LI)
Lf)
Lf)
L
L!)
Un
N
L!)
Lf)
L1)
N
Li)
LI)
Lf)
L!)
L!)
Lf)
LI)
Lf)
a„
C
r -I
r -i
r -I
r -I
r -I
r -I
r -i
r -I
r -i
r -I
r -I
r -I
r-
r -I
r -I
r -I
r -I
r -I
r -I
r -I
r -i
� �
H
O
O
O
N
�
00
M
r -I
rn
00
111
m
L n
N
l0
�
°�
°�
LnLn'
L.f)
m
00
00
L r)
M
M
00
N
M
Lli
m
00
00
I�
m�
N
L11
m
O
E
M
M
O
M0
01
-qt
I�
l0
u�
L11
L11
r -I
N
uj
L n
r1
.4
Ol
O
al
I�
00
O
w
�
�
Ln
9:1
Ln
�
Zt
Ln
lzt
I�t
Ln
1;t
M
I�t
LL
O
W �
N
00
l0
m
Ln
Ln
l0
l0
m
00
u1
Ln
Ln
00
Ln
Ln
M
N
Ln
00
u)
M
N
r%,Ln
�
00
qt
r -I
M
N
L
00
00
M
I�
M
m
w
I;t
�
M
m
m
N
r -Z
dl
lD
r-�
ui
O1
MO
Ln
O
0
00
4
O
M0
0
00
N
I�
00
4
u)
N6
l0
m
R
M
Rt�
M
Rt
::I-
RtL!i
RtI�t
qt
M
::I-
M
Rt
Mail 4�
m
M
O�
cl�
a
m
m
m
a
a
m
m<<<
a
m
a
m
m
a
a
a
m
a
m
a
a
a
CA
a
_
O-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
-
a
cc
w
a
zof
ct
CL
a
z
O
O
a
u
oC
LU
o
:2
D
O
_
1z
LU�
G
z
z
z
(�
Q
J
W
Z
or-
W
°u
~
' o
FL
iLL.
Z
�
w
oC
oC
J
oC
oC
O
L/)
W
cI
w
w
o �o
�
m
Q
m
Q
�
O�
or_
a
�
w
Q
u
u
z
On
��,
[�
a
a
LL
J
J
_
L7
~
O
O
2
U
—
w
u
——
u
U
—
_u
O
w
of
c/)
O
of
z
Q
Q
0
ap
o
G�
V)
Lnw
oC
w
Z
w
oC
oC
oC
oC
a
w
w
O
oc
w
=
J
m
J
m
p[
w
w
:t
v1
i
m
m
J
u
oC
u
u
u
u>
U
z
N
Q
LL
Z
0
°�
2
U
oC
o-
O
w
w
w
w
w
O
�
a
4—<j
a
CC
a
CC
a
CC
Q
CC
CC
CC
Q
Q
m
m
u
u
u
u
W
W
W
W
W
LL
J
J
G
G
G
G
G
G
a
O
H
0
H
0
Q
0
LL
C�
C
H
0
m
E
i
O
wl
m
m
tA
m
u
mqqT0� m m m m m m( r N N O ip Ln
r -I r -I r -I rl r -I r -I rl r4 r -I rl r -I r -I 4 r -I rl O rl r -I r -I r -I N O N
Ln
N N N N N O N N N N N N N N N ("A N N N O O O O O
Ln r -I r� r -I r� r� Ln Ln Ln Ln Ln Ln Ln r� r� 00 r -I r-iLri r -I a) ::1- 00 r -I �
M M M M M M M O N Ln 01 � 01
r -I r I r I r- O Lrir-i N r I r -I Ln Ln r-ir-I r -i r -i Ln O rl m O 00
r -I r -I rl r -I r -I r -I rl r -I N N r -I N r -I
00 n n o0 00 00 00 00 00 00 rl� n � � rl%. oo 0o
00
0 0 0 0 0 0 0 1 o0 o0 o0 o0 o0 o0 00 m cl 01 c l c l 4 rlN r -i O
r -I r -I r -I r -i r -i r -I r -i r -i r -i r -i r -i r -I r -I r -I r -I r -I r -I r -I r -I r -I r -I r -I
N N N N N N N N N N N N N N N N N N N N N N N N Ln
rl
N N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Ln
Ln
N
N
Lri
Lri
Lri
Lri
Lri
�
�
�
�
�
�
M
�'
o
�C:)
0i
r'
Ln
Ln
Lr)Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
u
Ln
Ln
Ln
�
N N
N
N
N
N
N
Ln
00
Ln
O
Ln
Ln
Ln
�
Ln
Ln
00
M
Ln
N
N
m
M
Ln
o
Ln
Ln
N
N N N N N N N Ln Ln Ln Ln Ln Ln Ln Ln Ln Ln Ln Ln Ln N Ln Ln Ln Ln
r -i r4 r4 r4 r4 r4 r -i r -i r -i r -i r -i r -I r -i r -i r -i r4 r4
r -I
r -I
r -I
r -I
r -I
Ln
0
Ln
0
Ln
0
Ln
0
Ln
0
Ln
0
m
m
Ln
Ln
Ln
Ln
Ln
m
Ln
Lri
Lri
Lri
Lri
Lri
�
�
�
�
�
�
M
�'
o
�C:)
0i
r'
Ln
Ln
Lr)Ln
Lr)Lr)
Lr)
Lr)
Ln
Lr)
Ln
Ln
Ln
Ln
qzl-
�
Ln
ri 00
Ln
N
11?
Ln
00
Ln
O
Ln
Ln
Ln
�
Ln
Ln
00
M
Ln
N
r�
m
M
Ln
o
Ln
Ln
�
N
Ln
M
'�
I�
Ln
M
�
Ln
c l
r-'
o0
M
o0
00
l0
r4
4
N0
00
l0
cl
I�
00
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
qt
Ln
Ln
M
r -I N
m
Ln
l0
I�
r -I
N
m
Ln
�-0
r -I
N
m
Ln
l0
I*
M
�
O
O
C)
N
D O
J J
J
O
J
J
O
J
D
J
J
J
J
J
J
J
J
J
J
J
Q
J
J
J
0�-+
J
• O
N
LL
LL
LL
LL
LL
LL
Q
Q
Q
m m
m
m
m
m
m
=
_
_
_
_
_
=
m
m
U
A-,
a Q
a
Q
a
a
a
Q
a
Q
Q
a
a
Q
a
Q
Q
a
a
Q
a
Q
Q
a
a
w
r
0
LU
ct
w w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
z Z
Z
Z
Z
z
Z
Z
Z
Z
Z
Z
z
Z
Z
Z
Z
z
Z
Z
o
Z
z z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z�
oo
Z Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
LU
w
o
ct
a Q
Q
a
Q
Q
a
Q
Q
a
Q
a
Q
Q
Q
a
Q
Q
a
Q
Lu
w
z
z
LL.
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Z
w
w
0 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
_
Ln
r -i
m
o0
oo
ui
Nlzt
RztM
t-nLn
L n
Ln
ui
L n
l0
n
Ln
m
M
M
L n
t.0
O
l0
M
a)
r-ir-I
rl
r -I
r -I
rl
0)
r -I
rl
O
r -I
O
O
O
O
O
rl
O
O
O
O
O
O
N
O
O
V
m
>
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
c
O
m
N
00
ONO
m
N
r* -.m
m
rl
Ln
Ln
Ln
kD
r -i•
w
w
m
m
00
m
N
IJP
N
N
N
L n
0000
1
r -i
00
M
`�
�
rl-.
cn
Lnr-ir-ir-irel
O
00
C114
r -i
r -i
w
a
r -i
r -i
r -i
C%4
r -i
r -i
r -i
r -i
r -i
m
m
m
Ln
m
Ln
�
oo
oo
oooo
rn
�
oo
oo
Ln
m
Ln
rn
m����
o
0
0
0
m
m
o
oro
0
00
oMo
0
=
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
H
0
Ln
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
0
L q
Lli
Ul
Ul
L!i
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
Ln
V;
r -I
rl
rl
r -I
r -I
r -I
N'-
0
N
0
LL
Ln
Lf i
Ln
Ln
Ln
Ln
Ln
LnLnuI
Ln
Ln
LnLnLnLnLn
Lf i
Ln
C�
C
r -I
r -I
r -I
r -I
rl
r -I
N
r -I
r -I
r -I
N
r -I
r -I
r -I
r -I
r -I
rl
r -I
r -I
r -I
r -I
H
Ln
Ln
Ln
Owl
r*-.
r -I
R:I-
M
LO
rl
00
N
w
O
00
Lli
00
�
M
qt�
O�
M
M
E
Ln
a�
O
Li
Ln
Ln
Ln
Lnr,
m
oo
m
rn
m
m
qt
w
N
N
w
N
M
O
r -I
Ln
M��
W
r1
M
r 1
W
M
O
M
4
r -i
00
N
lD
r1
ui
k6
M
Ln
M
LD
M
tD
Mm
I�
�
lD
O
00
m
qt
Ln
��
m
qt��
q*
m
m
m
p
M
O
O
NO
rl
CV
M
rl
N
M
M
N
a
mmmmmmammmm=aaaaaaaam
�,
i
•�
_
a
_
a
_
a
_
a
_
a
=
a
J
a
a
a
a
a
a
a
oc
a
ct
a
LU
Off
rt,
o
af
O
°U
w
=
z
0
,
� o
°C
z
Q
O
O
z
w
Of
w
Of
w
Of
w
oC
w
Cir-
w
Or-
w
oc
w
Of
w
o o
J
a0
w
��
-
z�>>>>>>>>�
w
a
LU
oC
w
Z
w
w
a
O
0
cn
oC
oC
oC
oC
oC
oC
oC
oC
Z
o
H
w
w
of
a
w
N
N
a
U
o
ca
Lu
w
c1
LL
z
z
w
Z
Lwi
V
V
V
V
V
V
V
V
a�
0
w
ofLu0o-ocwa�>>������
J
�
w
J
=
w
w
oC
olf
oC
oC
or-
o%
of
oC
oC
Dct
oL
oL
Of
(/')
cn
c/)
V)
V)
SECTION 007310 — PREVAILING WAGE RATES: continued
EXPLANATION OF CLASSES
ASBESTOS - GENERAL - removal of asbestos material/mold and hazardous materials from any place in
a building, including mechanical systems where those mechanical systems are to be removed. This
includes the removal of asbestos materials/mold and hazardous materials from ductwork or pipes in a
building when the building is to be demolished at the time or at some close future date. ASBESTOS -
MECHANICAL - removal of asbestos material from mechanical systems, such as pipes, ducts, and boilers,
where the mechanical systems are to remain.
CERAMIC TILE FINISHER
The grouting, cleaning, and polishing of all classes of tile, whether for interior or exterior purposes, all
burned, glazed or unglazed products; all composition materials, granite tiles, warning detectable tiles, cement
tiles, epoxy composite materials, pavers, glass, mosaics, fiberglass, and all substitute materials, for the made
in the -like units; all mixtures in the like form of cement, metals, and other materials that are for and intended
for use as a finished floor surface, stair treads, promenade roofs, walks, walls, ceilings, swimming pools, and
all other places where the is to form a finished interior or exterior. The mixing of all setting mortars
including but not limited to thin -set mortars, epoxies, wall mud, and any other sand and cement mixtures or
adhesives when used in the preparation, installation, repair, or maintenance of the and/or similar materials.
The handling and unloading of all sand, cement, lime, tile, fixtures, equipment, adhesives, or any other
materials to be used in the preparation, installation, repair, or maintenance of the and/or similar materials.
Ceramic Tile Finishers shall fill all joints and voids regardless of method on all the work, particularly and
especially after installation of said tile work. Application of any and all protective coverings to all types of
the installations including, but not be limited to, all soap compounds, paper products, tapes, and all
polyethylene coverings, plywood, masonite, cardboard, and any new type of products that may be used to
protect the installations, Blastrac equipment, and all floor scarifying equipment used in preparing floors to
receive tile. The clean up and removal of all waste and materials. All demolition of existing the floors and
walls to be re -tiled.
COMMUNICATIONS ELECTRICIAN
Installation, operation, inspection, maintenance, repair and service of radio, television, recording, voice
sound vision production and reproduction, telephone and telephone interconnect, facsimile, data apparatus,
coaxial, fibre optic and wireless equipment, appliances and systems used for the transmission and
reception of signals of any nature, business, domestic, commercial, education, entertainment, and
residential purposes, including but not limited to, communication and telephone, electronic and sound
equipment, fibre optic and data communication systems, and the performance of any task directly related
to such installation or service whether at new or existing sites, such tasks to include the placing of wire and
cable and electrical power conduit or other raceway work within the equipment room and pulling wire
and/or cable through conduit and the installation of any incidental conduit, such that the employees
covered hereby can complete any job in full.
MARBLE FINISHER
Village of Mount Prospect Section 007310 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 4 of 9
SECTION 007310 — PREVAILING WAGE RATES: continued
Loading and unloading trucks, distribution of all materials (all stone, sand, etc.), stocking of floors with
material, performing all rigging for heavy work, the handling of all material that may be needed for the
installation of such materials, building of scaffolding, polishing if needed, patching, waxing of material if
damaged, pointing up, caulking, grouting and cleaning of marble, holding water on diamond or
Carborundum blade or saw for setters cutting, use of tub saw or any other saw needed for preparation of
material, drilling of holes for wires that anchor material set by setters, mixing up of molding plaster for
installation of material, mixing up thin set for the installation of material, mixing up of sand to cement for the
installation of material and such other work as may be required in helping a Marble Setter in the handling of
all material in the erection or installation of interior marble, slate, travertine, art marble, serpentine, alberene
stone, blue stone, granite and other stones (meaning as to stone any foreign or domestic materials as are
specified and used in building interiors and exteriors and customarily known as stone in the trade), carrara,
sanionyx, vitrolite and similar opaque glass and the laying of all marble tile, terrazzo tile, slate the and
precast tile, steps, risers treads, base, or any other materials that may be used as substitutes for any of the
aforementioned materials and which are used on interior and exterior which are installed in a similar manner.
MATERIAL TESTER I: Hand coring and drilling for testing of materials; field inspection of uncured
concrete and asphalt.
MATERIAL TESTER II: Field inspection of welds, structural steel, fireproofing, masonry, soil, facade,
reinforcing steel, formwork, cured concrete, and concrete and asphalt batch plants; adjusting proportions of
bituminous mixtures.
OPERATING ENGINEER - BUILDING
Class 1. Asphalt Plant; Asphalt Spreader; Autograde; Backhoes with Caisson Attachment; Batch Plant;
Benoto (requires Two Engineers); Boiler and Throttle Valve; Caisson Rigs; Central Redi-Mix Plant;
Combination Back Hoe Front End -loader Machine; Compressor and Throttle Valve; Concrete Breaker
(Truck Mounted); Concrete Conveyor; Concrete Conveyor (Truck Mounted); Concrete Paver Over 27E cu.
ft; Concrete Paver 27E cu. ft. and Under: Concrete Placer; Concrete Placing Boom; Concrete Pump (Truck
Mounted); Concrete Tower; Cranes, All; Cranes, Hammerhead; Cranes, (GCI and similar Type); Creter
Crane; Spider Crane; Crusher, Stone, etc.; Derricks, All; Derricks, Traveling; Formless Curb and Gutter
Machine; Grader, Elevating; Grouting Machines; Heavy Duty Self -Propelled Transporter or Prime Mover;
Highlift Shovels or Front Endloader 2-1/4 yd. and over; Hoists, Elevators, outside type rack and pinion and
similar machines; Hoists, One, Two and Three Drum; Hoists, Two Tugger One Floor; Hydraulic Backhoes;
Hydraulic Boom Trucks; Hydro Vac (and similar equipment); Locomotives, All; Motor Patrol; Lubrication
Technician; Manipulators; Pile Drivers and Skid Rig; Post Hole Digger; Pre -Stress Machine; Pump Cretes
Dual Ram; Pump Cretes: Squeeze Cretes-Screw Type Pumps; Gypsum Bulker and Pump; Raised and Blind
Hole Drill; Roto Mill Grinder; Scoops - Tractor Drawn; Slip -Form Paver; Straddle Buggies; Operation of
Tie Back Machine; Tournapull; Tractor with Boom and Side Boom; Trenching Machines.
Class 2. Boilers; Broom, All Power Propelled; Bulldozers; Concrete Mixer (Two Bag and Over); Conveyor,
Portable; Forklift Trucks; Highlift Shovels or Front Endloaders under 2-1/4 yd.; Hoists, Automatic; Hoists,
Inside Elevators; Hoists, Sewer Dragging Machine; Hoists, Tugger Single Drum;
Village of Mount Prospect Section 007310 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 5 of 9
SECTION 007310 — PREVAILING WAGE RATES: continued
Laser Screed; Rock Drill (Self -Propelled); Rock Drill (Truck Mounted); Rollers, All; Steam Generators;
Tractors, All; Tractor Drawn Vibratory Roller; Winch Trucks with "A" Frame.
Class 3. Air Compressor; Combination Small Equipment Operator; Generators; Heaters, Mechanical; Hoists,
Inside Elevators (remodeling or renovation work); Hydraulic Power Units (Pile Driving, Extracting, and
Drilling); Pumps, over 3" (1 to 3 not to exceed a total of 300 ft.); Low Boys; Pumps, Well Points; Welding
Machines (2 through 5); Winches, 4 Small Electric Drill Winches.
Class 4. Bobcats and/or other Skid Steer
Loaders; Oilers; and Brick Forklift. Class
5. Assistant Craft Foreman.
Class 6. Gradall.
Class 7. Mechanics; Welders.
OPERATING ENGINEERS - HIGHWAY CONSTRUCTION
Class 1. Asphalt Plant; Asphalt Heater and Planer Combination; Asphalt Heater Scarfire; Asphalt Spreader;
Autograder/GOMACO or other similar type machines: ABG Paver; Backhoes with Caisson Attachment;
Ballast Regulator; Belt Loader; Caisson Rigs; Car Dumper; Central Redi-Mix Plant; Combination Backhoe
Front Endloader Machine, (1 cu. yd. Backhoe Bucket or over or with attachments); Concrete Breaker (Truck
Mounted); Concrete Conveyor; Concrete Paver over 27E cu. ft.; Concrete Placer; Concrete Tube Float;
Cranes, all attachments; Cranes, Tower Cranes of all types: Creter Crane: Spider Crane; Crusher, Stone, etc.;
Derricks, All; Derrick Boats; Derricks, Traveling; Dredges; Elevators, Outside type Rack & Pinion and
Similar Machines; Formless Curb and Gutter Machine; Grader, Elevating; Grader, Motor Grader, Motor
Patrol, Auto Patrol, Form Grader, Pull Grader, Subgrader; Guard Rail Post Driver Truck Mounted; Hoists,
One, Two and Three Drum; Heavy Duty Self -Propelled Transporter or Prime Mover; Hydraulic Backhoes;
Backhoes with shear attachments up to 40' of boom reach; Lubrication Technician; Manipulators; Mucking
Machine; Pile Drivers and Skid Rig; Pre -Stress Machine; Pump Cretes Dual Ram; Rock Drill - Crawler or
Skid Rig; Rock Drill - Truck Mounted; Rock/Track Tamper; Roto Mill Grinder; Slip -Form Paver; Snow
Melters; Soil Test Drill Rig (Truck Mounted); Straddle Buggies; Hydraulic Telescoping Form (Tunnel);
Operation of Tieback Machine; Tractor Drawn Belt Loader; Tractor Drawn Belt Loader (with attached
pusher - two engineers); Tractor with Boom; Tractaire with Attachments; Traffic Barrier Transfer Machine;
Trenching; Truck Mounted Concrete Pump with Boom; Raised or Blind Hole Drills (Tunnel Shaft);
Underground Boring and/or Mining Machines 5 ft. in diameter and over tunnel, etc; Underground Boring
and/or Mining Machines under 5 ft. in diameter; Wheel Excavator; Widener (APSCO).
Class 2. Batch Plant; Bituminous Mixer; Boiler and Throttle Valve; Bulldozers; Car Loader Trailing
Conveyors; Combination Backhoe Front Endloader Machine (Less than 1 cu. yd. Backhoe Bucket or
over or with attachments); Compressor and Throttle Valve; Compressor, Common Receiver (3); Concrete
Breaker or Hydro Hammer; Concrete Grinding Machine; Concrete Mixer or Paver 7S Series to and
including 27 cu. ft.;
Village of Mount Prospect Section 007310 April 2019
Rehabilitation of 1,0001000 Gallon Station 5E
Ground Storage Tank Page 6 of 9
SECTION 007310 — PREVAILING WAGE RATES: continued
Concrete Spreader; Concrete Curing Machine, Burlap Machine, Belting Machine and Sealing
Machine; Concrete Wheel Saw; Conveyor Muck Cars (Haglund or Similar Type); Drills, All;
Finishing Machine - Concrete; Highlift Shovels or Front Endloader; Hoist - Sewer Dragging
Machine; Hydraulic Boom Trucks (All Attachments); Hydro -Blaster; Hydro Excavating
(excluding hose work); Laser Screed; All Locomotives, Dinky; Off -Road Hauling Units
(including articulating) Non Self -Loading Ejection Dump; Pump Cretes: Squeeze Cretes -
Screw Type Pumps, Gypsum Bulker and Pump; Roller, Asphalt; Rotary Snow Plows;
Rototiller, Seaman, etc., self-propelled; Self -Propelled Compactor; Spreader - Chip - Stone,
etc.; Scraper - Single/Twin Engine/Push and Pull; Scraper - Prime Mover in Tandem
(Regardless of Size); Tractors pulling attachments, Sheeps Foot, Disc, Compactor, etc.; Tug
Boats.
Class 3. Boilers; Brooms, All Power Propelled; Cement Supply Tender; Compressor, Common
Receiver (2); Concrete Mixer (Two Bag and Over); Conveyor, Portable; Farm -Type Tractors
Used for Mowing, Seeding, etc.; Forklift Trucks; Grouting Machine; Hoists, Automatic; Hoists,
All Elevators; Hoists, Tugger Single Drum; Jeep Diggers; Low Boys; Pipe Jacking Machines;
Post -Hole Digger; Power Saw, Concrete Power Driven; Pug Mills; Rollers, other than Asphalt;
Seed and Straw Blower; Steam Generators; Stump Machine; Winch Trucks with "A" Frame;
Work Boats; Tamper -Form -Motor Driven.
Class 4. Air Compressor; Combination - Small Equipment Operator; Directional Boring
Machine; Generators; Heaters, Mechanical; Hydraulic Power Unit (Pile Driving, Extracting,
or Drilling); Light Plants, All (1 through 5); Pumps, over 3" (1 to 3 not to exceed a total of
300 ft.); Pumps, Well Points; Vacuum Trucks (excluding hose work); Welding Machines (2
through 5); Winches, 4 Small Electric Drill Winches.
Class 5. SkidSteer Loader (all); Brick Forklifts; Oilers. Class 6. Field Mechanics and Field
Welders
Class 7. Dowell Machine with Air
Compressor; Gradall and machines of
like nature. OPERATING
ENGINEER - FLOATING
Class 1. Craft Foreman; Master Mechanic; Diver/Wet Tender; Engineer; Engineer (Hydraulic
Dredge) .
Class 2. Crane/Backhoe Operator; Boat Operator with towing endorsement; Mechanic/Welder;
Assistant Engineer (Hydraulic Dredge); Leverman (Hydraulic Dredge); Diver Tender.
Class 3. Deck Equipment Operator, Machineryman, Maintenance of Crane (over 50 ton
capacity) or Backhoe (115,000 lbs. or more); Tug/Launch Operator; Loader/Dozer and like
equipment on Barge, Breakwater Wall, Slip/Dock, or Scow, Deck Machinery, etc.
Village of Mount Prospect Section 007310 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 7 of 9
SECTION 007310 — PREVAILING WAGE RATES: continued
Class 4. Deck Equipment Operator, Machineryman/Fireman (4 Equipment Units or More); Off
Road Trucks; Deck Hand, Tug Engineer, Crane Maintenance (50 Ton Capacity and Under) or
Backhoe Weighing (115,000 pounds or less); Assistant Tug Operator.
Class 5. Friction or Lattice Boom Cranes. Class 6. ROV Pilot, ROV Tender TERRAZ
FINISHER
The handling of sand, cement, marble chips, and all other materials that may be used by the
Mosaic Terrazzo Mechanic, and the mixing, grinding, grouting, cleaning and sealing of all
Marble, Mosaic, and Terrazzo work, floors, base, stairs, and wainscoting by hand or machine,
and in addition, assisting and aiding Marble, Masonic, and Terrazzo Mechanics.
TRAFFIC SAFETY
Work associated with barricades, horses and drums used to reduce lane usage on highway work,
the installation and removal of temporary lane markings, and the installation and removal of
temporary road signs.
TRUCK DRIVER - BUILDING, HEAVY AND HIGHWAY CONSTRUCTION - EAST &
WEST
Class 1. Two or three Axle Trucks. A -frame Truck when used for transportation purposes; Air
Compressors and Welding Machines, including those pulled by cars, pick-up trucks and
tractors; Ambulances; Batch Gate Lockers; Batch Hopperman; Car and Truck Washers;
Carry-alls; Fork Lifts and Holsters; Helpers; Mechanics Helpers and Greasers; Oil
Distributors 2 -man operation; Pavement Breakers; Pole Trailer, up to 40 feet; Power Mower
Tractors; Self-propelled Chip Spreader; Skipman; Slurry Trucks, 2 -man operation; Slurry
Truck Conveyor Operation, 2 or 3 man; Teamsters; Unskilled Dumpman; and Truck Drivers
hauling warning lights, barricades, and portable toilets on the job site.
Class 2. Four axle trucks; Dump Crets and Adgetors under 7 yards; Dumpsters, Track Trucks,
Euclids, Hug Bottom Dump Turnapulls or Turnatrailers when pulling other than self -loading
equipment or similar equipment under 16 cubic yards; Mixer Trucks under 7 yards; Ready -mix
Plant Hopper Operator, and Winch Trucks, 2 Axles.
Class 3. Five axle trucks; Dump Crets and Adgetors 7 yards and over; Dumpsters, Track
Trucks, Euclids, Hug Bottom Dump Turnatrailers or turnapulls when pulling other than self -
loading equipment or similar equipment over 16 cubic yards; Explosives and/or Fission
Material Trucks; Mixer Trucks 7 yards or over; Mobile Cranes while in transit; Oil
Distributors, 1 -man operation; Pole Trailer, over 40 feet; Pole and Expandable Trailers
hauling material over 50 feet long; Slurry trucks, 1 -man operation; Winch trucks, 3 axles or
more; Mechanic --Truck Welder and Truck Painter.
Class 4. Six axle trucks; Dual-purpose vehicles, such as mounted crane trucks with hoist and
accessories; Foreman; Master Mechanic; Self- loading equipment like P.B. and trucks with
scoops on the front.
Other Classifications of Work:
Village of Mount Prospect Section 007310 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 8 of 9
SECTION 007310 — PREVAILING WAGE RATES: continued
For definitions of classifications not otherwise set out, the Department generally has on file such
definitions which are available. If a task to be performed is not subject to one of the classifications
of pay set out, the Department will upon being contacted state which neighboring county has such a
classification and provide such rate, such rate being deemed to exist by reference in this document.
If no neighboring county rate applies to the task, the Department shall undertake a special
determination, such special determination being then deemed to have existed under this
determination. If a project requires these, or any classification not listed, please contact IDOL at
217-782-1710 for wage rates or clarifications.
LANDSCAPING
Landscaping work falls under the existing classifications for laborer, operating engineer and truck
driver. The work performed by landscape plantsman and landscape laborer is covered by the
existing classification of laborer. The work performed by landscape operators (regardless of
equipment used or its size) is covered by the classifications of operating engineer. The work
performed by landscape truck drivers (regardless of size of truck driven) is covered by the
classifications of truck driver.
MATERIAL TESTER & MATERIAL TESTER/INSPECTOR I AND II
Notwithstanding the difference in the classification title, the classification entitled "Material
Tester I" involves the same job duties as the classification entitled "Material Tester/Inspector I".
Likewise, the classification entitled "Material Tester II" involves the same job duties as the
classification entitled "Material Tester/Inspector II".
END OF SECTION 007310
Village of Mount Prospect Section 007310 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 9 of 9
Section 007315
CERTIFICATION REQUIREMENTS
Village of Mount Prospect, Illinois
Please submit all required forms and documentation, fully completed and signed,
with your proposal. No proposal will be accepted without this information.
1. The contractor agrees to provide all items and material to the Village as noted in the
specifications.
2. The undersigned certifies that the offerer is not barred from offering on this solicitation as a result
of a conviction for the violation of the bid -rigging or bid -rotating provisions contained in 720 ILCS
5/33E-3 & 33E-4.
3. Default on Educational Loan. By submitting a bid the contractor certifies that no owner, officer
or director is in default on an educational loan as provided in 5 ILCS 385/1-385/3.
4. Bribery. The Contractor states he or she has not been convicted of bribery or attempting to bribe
an officer or employee of the state of Illinois, nor has the Contractor made an admission of guilt of such
conduct which is a matter of record, nor has any official, officer, owner, agent or employee of the
Contractor been so convicted or made such admission (30 ILCS 500/50-5).
5. Felony or Bribery Conviction. The Contractor is not barred on account of a felony or bribery
conviction (30 ILLS 500/50-10 and 30 ILCS 500/50-10).
6. International Boycott. The Contractor certifies that neither it nor any substantially -owned
affiliated company is participating or shall participate in an international boycott in violation of the
provisions of the U.S. Export Administration Act of 1979 or the regulations of the U.S. Department of
Commerce promulgated under the act.
7. Drug Free Workplace Act. The Contractor will comply with the requirements of the Drug Free
Workplace Act if the contract is $5,000 or more and the vendor has more than 24 employees at the time
of entering into the contract (30 ILCS 580).
8. The contractor and subcontractors, etc. shall pay prevailing wages pursuant to the Wages of
Employees on Public Works Act (820 ILCS 130).
9. Preference to Veterans Act. The Contractor will comply with the Preference to Veterans Act
(330 ILLS 55)
10. Records. The Contractor will comply with the record keeping requirements of the Illinois
Procurement Code (30 ILLS 500/20-65) by keeping the records related to the contract for a minimum of
three (3) years after the completion of the contract and available for review and audit by the Illinois
Auditor General.
11. The Contractor certifies that the company has in place for all of its employees not covered by a
collective bargaining agreement that deals with the subject of the Act, a substance abuse prevention
program that meets or exceeds the requirements of Public Act 95-0635.
Village of Mount Prospect Section 007315 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 2
12. The Contractor certifies that the company is in compliance with Fair Employment Practices as
outlined in the General Conditions
13. Selection of Labor
The Contractor shall comply with all Illinois statutes pertaining to the selection of labor.
14. The successful bidder agrees that upon acceptance by the Village of Mount Prospect, the
executed Invitation to Bid along with all instructions, conditions, and specifications attached thereto
constitute a binding contract which may be enforced by the Village.
Signature/Title
Company Name
Address
Phone Number
FEIN No.
END OF SECTION 007315
Village of Mount Prospect Section 007315 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 2
Section 007330
AFFIDAVIT — BID CERTIFICATION FORM
Bidder:
Company/Firm Name:
Address:
As a condition of entering into a contract with the Village of Mount Prospect, and under oath and penalty
of perjury and possible termination of contract rights and debarment, the undersigned,
being first duly sworn on oath, deposes and states that he or she is
(sole owner, partner, joint ventured, President, Secretary,
etc.) of and has the authority to make all certifications
(Name of Company)
required by this affidavit.
Section I Non Collusion
The undersigned certifies that this bid is genuine and not collusive or a sham, that said bidder has not
colluded, conspired, connived or agreed, directly or indirectly, with any bidder or person, to put in a sham
bid or to refrain from bidding, and has not in any manner, directly or indirectly, sought by agreement or
collusion, or communication or conference with any person, to fix the bid price element of this bid, or of
that of any other bidder, or to secure any advantage against any other bidder or any person interested in
the proposed contract.
Section II Bid Rigging and Rotating
The undersigned further states that
(Name of Company)
is not barred from bidding or contracting as a result of a conviction for violations of state laws prohibiting
bid rigging or bid rotating or any similar offense of any state of the United States, as provided in Sections
33E-3 and 33E-4 of the Illinois Criminal Code, 720 ILLS 5/33E -3,33E-4.
Section III Drug Free Workplace
The undersigned further states that
(Name of Company)
provides a drug free workplace pursuant to the Drug Free Workplace Act, 30 ILCS 580/1, et seq., and
has, to the extent not covered by a collective bargaining that deals with the subject of the Substance
Abuse Prevention in Public Works Projects Act, 820 ILCS 265/1 et seq., a substance abuse prevention
program that meets or exceeds these requirements of that Act.
Village of Mount Prospect Section 007330 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank Page 1 of 2
SECTION 007330 — AFFIDAVIT: continued
AFFIDAVIT — BID CERTIFICATION FORM
Section IV Tax Payment
The undersigned further states that is
(Name of Company)
not delinquent in payment of any taxes to the Illinois Department of Revenue, in accordance with Illinois
Compiled Statues, 65 ILCS 5/11-42.1. The undersigned understands that making a false statement
regarding delinquency in taxes is a Class A Misdemeanor and, in addition voids the contract and allows
the municipality to recover all amounts paid to the individual or entity under the contract in civil action.
Section V Sexual Harassment Policy
Pursuant to Section 2-105(A) of the Illinois Human Rights Act, 775 ILCS 5/2-105 (A), every party to a
public contract must:
"Have written sexual harassment policies that shall include, at a minimum, the following information: (I)
the illegality of sexual harassment; (II) the definition of sexual harassment under State law; (III) a
description of sexual harassment, utilizing examples; (IV) the vendor's internal complaint process
including penalties; (V) the legal recourse, investigative and complaint process available through the
Department (of Human Rights) and the Commission (Human Rights Commission); (VI) directions on
how to contact the Department and Commission; and (VII) protection against retaliation as provided by
Section 6-101 of the Act. (Illinois Human Rights Act)."
A "public contract" includes: ... every contract to which the State, any of its political subdivisions or any
municipal corporation is a party." 775 ILCS 5/1-103 (M) (2002),
The undersigned further states that
has
(Name of Company)
a written sexual harassment policy in place in full compliance with 775 ILCS 5/2-105 (A) (4).
It is expressly understood the foregoing statements and representations and promises are made as a
condition to the right of the bidder to receive payment under any award made under the terms and
provisions of this bid.
The undersigned certifies that all information contained in this Affidavit is true and correct.
Signed by:
Signature
Name Printed:
Signed and sworn to before me this day of , 20
My commission expires:
Notary Public
Village of Mount Prospect
Rehabilitation of 1,000,000 Gallon Station 5E
END OF SECTION 007330
Section 007330
Ground Storage Tank Page 2 of 2
Title:
April 2019
DIVISION 1 - GENERAL REQUIREMENTS
SECTION 011100 - SUMMARY OF WORK
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section summarizes the Work covered in detail in the complete Contract Documents.
B. Owner: Village of Mount Prospect is contracting for Work described in the Contract
Documents.
1. Contract Identification: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage
Tank
2. Work Site Location: 112 Highland Avenue in Mount Prospect, IL.
C. Engineer: The Contract Documents were prepared by Burns & McDonnell Engineering
Company, Inc. (1431 Opus Pl., Suite 400, Downers Grove, Illinois 60515)
1.02 PROJECT DESCRIPTION:
A. The Village of Mount Prospect owns and operates one (1) one -million gallon potable water
ground storage tank located at 112 Highland Avenue (Tank 5E). The proj ect includes, but is
not limited to the following bid items: Complete blast and recoat of the wet interior, high
pressure wash the exterior followed by spot repair and topcoat of the exterior. Replacement of
the 50A breaker in the electrical vault. The project also includes various improvements to the
Tank's safety measures, steel work, seam sealing, foundation repair, tank disinfection, and site
restoration.
B. Included at the back of this Project Manual is the inspection report written for Tank 5E. The
inspection report was written in 2017 by Tank Industry Consultants. The report contains
photographs of the tank. The report and photographs are for informational purposes and not to
be used for bidding purposes.
1.03 WORK BY OTHERS
A. Work Under Other Contracts: None
1.04 CONTRACTOR'S USE OF PREMISES:
A. Limited Use:
1. Limit use of the premises for storage and execution of the Work to allow for Owner
occupancy. Confine operations to areas within Contract limits indicated. Portions of Site
outside the Contract limits shall not be disturbed.
2. Coordinate with other separate contractors and Owner to avoid interference of operations.
3. Conduct operations so as to ensure the least inconvenience to Owner and the general
public.
4. The Contractor shall be responsible for providing all temporary sanitary and office
facilities for his use. Obtaining utility connections and payment of all costs associated
with the use of facilities shall be the responsibility of the Contractor with no additional
cost to the Owner.
1.05 OWNER'S USE OF PREMISES:
A. Full Owner Occupancy: The Owner will occupy the Site during the entire construction period.
Cooperate with the Owner during construction operations to minimize conflicts and facilitate
Owner usage. Perform the Work so as not to interfere with the Owner's operations.
1.06 WORK SEQUENCE:
Village of Mount Prospect 01 1100-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 011100 - SUMMARY OF WORK: continued
A. General: Construction sequence shall be determined by Contractor subject to Owner's need for
continuous operation of existing facilities.
B. Continuous Service of Existing Facilities: Exercise caution and schedule operations to ensure
that functioning of present facilities will not be disrupted. Shutdown of Owner's operating
facilities to perform the Work shall be held to a minimum length of time and shall be
coordinated with Owner who shall have control over the timing and schedules of such
shutdowns.
1. The Contractor shall provide 7 days advance notice to Owner regarding shutdown of the
Tank.
2. Approval to proceed with shutdown shall not be granted until all equipment and materials
required to complete the repairs are onsite.
1.07 MEASUREMENT AND PAYMENT:
A. Unit Price Contracts: All Work indicated on the Contract Drawings and specified in the
Contract Documents shall be included in the "Unit Price Schedule" in the Agreement. A Unit
Price is an amount proposed by Contractor and stated in the Agreement as a price per unit of
measurement for materials or services.
B. Specific Items: Measurement and payment of specific items shall be as specified in Section
012000.
1.08 COPIES OF DOCUMENTS:
A. Furnished Copies: After execution of Agreement, Contractor will be furnished at no cost,
electronic copies in Adobe ® PDF format of the Contract Documents including revised
Drawings, and the Project Manual, in addition to those used in execution of the Agreement.
B. Additional Copies: Additional copies of above documents will be supplied by Engineer upon
request at printing and delivery cost.
PART 2 - PRODUCTS — Not Applicable.
PART 3 - EXECUTION — Not Applicable.
END OF SECTION 01 1100
Village of Mount Prospect 01 1100-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 012000 — MEASUREMENT AND PAYMENT
PART 1 - GENERAL INFORMATION
1.01 MEASUREMENT AND PAYMENT:
A. This Section describes the measurement and payment for the Work to be done under the items
included in this Contract.
B. Each unit or lump -sum price stated in the Bid shall constitute full compensation as herein
specified for each item of work completed in accordance with the Contract Documents. The
price shall be full compensation for furnishing all materials and for all labor, equipment, fees,
tools and incidentals necessary to complete the item as included in the Contract Documents.
C. No separate measurement and payment shall be made for Work not specifically listed in this
Section. It shall be understood that all Work necessary to complete the Contract as included in
the Contract Documents shall be included in cost of the unit and lump sum items included in
the Contract.
D. Pay Items 2 & 3 of the Schedule of Values Section 004015 includes all work to be completed
for the Tank 5E one -million gallon ground storage tank. Alternate bid items are included in the
Bid Form and may be added to the bid by the Owner. Descriptions of sub -pay items and
alternates are provided below.
1.02 BASE BID PAY ITEMS:
A. Mobilization Pay Item No. 1
1. Mobilization will be paid for at the contract lump sum price for the mobilization and
demobilization of all equipment to and from the site in accordance with Article 671 of the
IDOT Standard Specifications for Road and Bridge Construction and the restoration of
the project site. The unit price for this item shall constitute full compensation for all
equipment, materials, labor, fees, tools and incidentals necessary to complete this item.
No additional compensation will be given for re -mobilization to and from the site due to
any reason.
B. Interior Coating Rehabilitation — Pay Item No. 2
1. Interior Coating will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools and incidentals required to complete the
appropriate surface preparation and re -coat the tank interior.
C. Exterior Coating Rehabilitation — Pay Item No. 3
1. Exterior Coating Rehabilitation will be paid for at the contract lump sum price. This work
shall include all equipment, materials, labor, fees, tools and incidentals required to
complete the proper surface preparation, spot prime, and over -coat the tank exterior.
D. Steel Work & Miscellaneous Repairs — Pay Item No. 4
1. Steel Work & Miscellaneous Repairs will be paid for at the contract lump sum price. This
work shall include all equipment, materials, labor, fees, tools and incidentals required to
complete the structural work and miscellaneous work as specified. This work includes
but is not limited to the following:
a. Miscellaneous chipping and grinding
b. Seam sealing
C. Sealant repair
d. Foundation repair
e. Removal and replacement of the existing wet interior ladder with a fall prevention
device.
£ Removal and replacement of the existing exterior ladder with a fall prevention
device.
g. Installation of shell manhole davits (2)
Village of Mount Prospect Section 012000 - 1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 012000 — MEASUREMENT AND PAYMENT: continued
h. Installation of a self-closing gate on the existing roof safety railing
i. Replacement of the existing roof safety railing toe bar
j . Installation of mud guards (2): Install a removable mud guard on the inlet/outlet
pipe and the drain pipe.
E. Electrical Work — Pay Item No. 5
1. Electrical Work will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools, and incidentals required to remove and replace
the existing breaker in the electrical vault.
F. Tank Disinfection — Pay Item No. 6
1. Tank Disinfection will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools and incidentals required to disinfect and test
the tank as specified.
G. Site Restoration — Pay Item No. 7
1. Site Restoration will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools, and incidentals required to restore any
disturbed areas of the site as specified.
H. Contingency — Man Hours for Additional Work — Pay Item No. 8
1. Contingency will be paid for at the contract price per man-hour. This work shall include
all equipment, materials, labor, fees, tools, and incidentals required to complete the work
as specified and as requested by the Village.
1.03 ALTERNATE BID PAY ITEMS
A. Exterior Coating w/ Full Blast Pay Item No. LA
1. Exterior Coating w/ Full Blast will be paid for at the contract lump sum price as an
addition or deduction to the cost of Bid Item 3. This work shall include all equipment,
materials, labor, fees, tools and incidentals required to complete the appropriate surface
preparation and re -coat of the tank exterior.
B. Partial Beam Replacement — Pay Item No. 1.13
1. Partial Beam Replacement includes removal and replacement of the center support ring,
24 inner roof beams, 24 inner roof perlins, and 24 outer beam ends. Partial Beam
Replacement also includes material and labor to caulk all joints 1/2" or smaller between
the roof and beams with Sika Flex IA. This work shall include all equipment, materials,
labor, fees, tools and incidentals required to complete the items listed above. Work shall
be paid at the contract lump sum price for Partial Beam Replacement.
C. Complete Beam Replacement — Pay Item No. 1.0
1. Complete Beam Replacement includes removal and replacement of the center support
ring, roof beams, and roof perlins. Complete Beam Replacement also includes material
and labor to caulk all joints 1/2" or smaller between the roof and beams with Sika Flex IA.
This work shall include all equipment, materials, labor, fees, tools and incidentals
required to complete the items listed above. Work shall be paid at the contract lump sum
price for Complete Beam Replacement.
END OF SECTION 012000
Village of Mount Prospect Section 012000 - 2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 012500 - SUBSTITUTIONS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes administrative and procedural requirements for handling requests for
substitutions made after award of the Contract.
B. Related Work Specified Elsewhere:
1. Requirements for submitting Contractor's construction progress schedule and the
Submittal schedule: SECTIONS 013200 and 013300.
2. Requirements governing Contractor's selection of products: SECTION 016000.
1.02 DEFINITIONS:
A. Definitions in this Article do not change or modify the meaning of other terms used in the
Contract Documents.
B. Substitutions: Changes in products, Materials, Equipment, and methods of construction
required by the Contract Documents proposed by the Contractor after award of the Contract are
considered to be requests for substitutions. The following are not considered to be requests for
substitutions:
1. Revisions to the Contract Documents requested by Owner or Engineer.
2. Specified options of products and construction methods included in the Contract
Documents.
1.03 SUBMITTALS:
A. Substitution Request Submittal: Engineer will consider written requests for substitution if
received within 30 days after commencement of the Work. Requests received more than 30
days after commencement of the Work may be considered or rejected at the discretion of
Engineer.
1. Submit 3 copies of each request for substitution for consideration. Submit requests in the
form and according to procedures required for Change Order proposals. Requests for
substitution shall not be submitted in the form of a Request for Information (RFI).
2. Identify the Equipment or Material, the fabrication, or installation method to be replaced
in each request. Include related Specification Section/Article and Drawing numbers.
3. Provide complete documentation showing compliance with the requirements for
substitutions, and the following information, as appropriate:
a. Statement indicating why specified product or method of construction cannot be
provided.
b. Coordination information, including a list of changes or modifications needed to
other parts of the Work and to construction performed by Owner and separate
contractors that will be necessary to accommodate the proposed substitution.
C. A detailed comparison of significant qualities of the proposed substitution with
those of the Work specified. Significant qualities may include elements such as
performance, weight, size, durability, visual effect, and specific features and
requirements indicated.
d. Product data, including drawings and descriptions of products and fabrication and
installation procedures.
e. Samples, where applicable or requested.
f. Identification of available sales, maintenance, repair, and replacement services.
g. A statement indicating the effect of the substitution on Contractor's construction
progress schedule compared to the schedule without approval of the substitution.
Indicate the effect of the proposed substitution on the overall Contract Times. If
Village of Mount Prospect 012500-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 012500 - SUBSTITUTIONS: continued
specified product cannot be provided within the Contract Times, provide letter from
manufacturer, on manufacturer's letterhead, stating lack of availability or delay in
delivery.
h. An itemized estimate of costs that will result directly or indirectly from approval of
the substitution, including:
(1) A proposal of the net change, if any, in the Contract Price.
(2) Costs of redesign required by the proposed change.
(3) Costs of resulting claims as determined in coordination with other
contractors having work on the Project affected by the substitution.
i. Statement indicating whether or not incorporation or use of the substitute is subject
to payment of any license fee or royalty.
j. Contractor's certification that the proposed substitution conforms to requirements in
the Contract Documents, will perform adequately the functions and achieve the
results called for by the general design, is similar in substance to that specified, and
is suitable for same use as that indicated and specified.
k. Contractor's waiver of rights to additional payment or time that may subsequently
become necessary because of the failure of the substitution to perform adequately.
4. Engineer's Action: If necessary, Engineer will request additional information or
documentation for evaluation within two weeks of receipt of a request for substitution.
Engineer will notify Contractor of acceptance or rejection of the substitution within 4
weeks of receipt of the request, or one week of receipt of additional information or
documentation, whichever is later. Acceptance will be in the form of a Change Order.
PART 2 - PRODUCTS
2.01 SUBSTITUTIONS:
A. Conditions: Engineer will receive and consider Contractor's request for substitution when one
or more of the following conditions are satisfied, as determined by Engineer. If the following
conditions are not satisfied, Engineer will return the requests without action except to record
noncompliance with these requirements.
1. Extensive revisions to the Contract Documents are not required.
2. Proposed substitution is in keeping with the general intent of the Contract Documents and
will produce indicated results.
3. Substitution request is timely, fully documented, and properly submitted.
4. The specified product or method of construction cannot be provided within the Contract
Times. Engineer will not consider the request if the product or method cannot be
provided as a result of failure to pursue the Work promptly or coordinate activities
properly.
5. The requested substitution offers Owner a substantial advantage, in cost, time, energy
conservation, or other considerations, after deducting additional responsibilities Owner
must assume. Owner's additional responsibilities may include compensation to Engineer
for redesign and evaluation services, increased cost of other construction by Owner, and
similar considerations.
6. The specified product or method of construction cannot receive necessary approval by a
governing authority, and the requested substitution can be approved.
7. The specified product or method of construction cannot be provided in a manner that is
compatible with other materials and where Contractor certifies that the substitution will
overcome the incompatibility.
Village of Mount Prospect 012500-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 012500 - SUBSTITUTIONS: continued
8. The specified product or method of construction cannot be coordinated with other
materials and where Contractor certifies that the proposed substitution can be
coordinated.
9. The specified product or method of construction cannot provide a warranty required by
the Contract Documents and where Contractor certifies that the proposed substitution
provides the required warranty.
B. Engineer's review and acceptance of Submittals shall not relieve Contractor from
responsibility for any variation from the requirements of the Contract Documents. Engineer's
acceptance of Submittals not complying with the Contract Documents does not constitute an
acceptable or valid request for substitution, nor does it constitute approval of a substitute.
Acceptance by Engineer shall not relieve Contractor from responsibility for errors or omissions
in the Submittals.
PART 3 - EXECUTION (Not Applicable)
END OF SECTION 012500
Village of Mount Prospect 012500-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013100 - PROJECT COORDINATION AND MEETINGS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes administrative provisions for coordinating construction operations on
Project including, but not limited to, the following:
1. Coordination drawings.
2. Project meetings.
3. Requests for information (RFIs).
B. Related Work Specified Elsewhere:
1. For preparing and submitting Contractor's construction progress schedule: SECTION
013200.
2. For Submittal Requirements: SECTION 013300.
3. For coordinating closeout of the Contract: SECTION 017800.
1.02 DEFINITIONS:
A. RFI: Request for information prepared by Contractor and submitted to Engineer seeking
interpretation or clarification of the Contract Documents.
1.03 COORDINATION:
A. Coordination: Coordinate construction operations included in different Sections of the
Specifications to ensure efficient and orderly installation of each part of the Work. Coordinate
construction operations, included in different Sections that depend on each other for proper
installation, connection, and operation.
1. Schedule construction operations in sequence required to obtain the best results where
installation of one part of the Work depends on installation of other components, before
or after its own installation.
2. Make adequate provisions to accommodate items scheduled for later installation.
3. Where availability of space is limited, coordinate installation of different components to
allow optimum performance and accessibility for required maintenance, service, and
repair of all components, including mechanical and electrical.
B. Prepare memoranda for distribution to each party involved, outlining special procedures
required for coordination. Include such items as required notices, reports, and list of attendees
at meetings.
C. Administrative Procedures: Coordinate scheduling and timing of required administrative
procedures with other construction activities and activities of others to avoid conflicts and to
ensure orderly progress of the Work. Such administrative activities include, but are not limited
to, the following:
1. Preparation of construction progress schedule.
2. Preparation of the schedule of values.
3. Installation and removal of temporary facilities and controls.
4. Delivery and processing of Submittals.
5. Progress meetings.
6. Preinstallation conferences.
7. Project closeout activities.
8. Startup and adjustment of systems.
9. Project closeout activities.
Village of Mount Prospect 013100-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013100 - PROJECT COORDINATION AND MEETINGS: continued
1.04 SUBMITTALS:
A. Coordination Drawings: Prepare Coordination Drawings if limited space availability
necessitates maximum utilization of space for efficient installation of different components or
if coordination is required for installation of products and materials fabricated by separate
entities.
1. Content: Project -specific information, drawn accurately to scale. Do not base
Coordination Drawings on reproductions of the Contract Documents or standard printed
data. Include the following information, as applicable:
a. Indicate functional and spatial relationships of components of architectural,
structural, civil, mechanical, process, and electrical systems.
b. Indicate required installation sequences.
C. Indicate dimensions shown on the Contract Drawings and make specific note of
dimensions that appear to be in conflict with submitted Equipment and minimum
clearance requirements. Provide alternate sketches to Engineer for resolution of
such conflicts. Minor dimension changes and difficult installations will not be
considered changes to the Contract.
d. Crane or other construction equipment placement and motion space required.
2. Sheet Size: At least 8-1/2 by 11 inches but no larger than 30 by 40 inches.
3. Number of Copies: Submit one electronic copy and two opaque hard copies of each
Submittal to Engineer. Engineer will return comments electronically.
4. Refer to individual Sections for coordination drawing requirements for Work in those
Sections.
1.05 PROJECT MEETINGS:
A. Preconstruction Conference:
1. Engineer will conduct a meeting within 20 days after the Effective Date of the
Agreement, to review items stated in the following agenda and to establish a working
understanding between the parties as to their relationships during performance of the
Work.
2. Preconstruction conference shall be attended by:
a. Representative(s) of Contractor including Contractor's superintendent.
b. Engineer and Resident Project Representative.
C. Representative(s) of Owner.
d. At Owner's option, representatives of principal Subcontractors and Suppliers.
3. Meeting Agenda:
a. Construction schedules.
b. Phasing.
C. Critical Work sequencing and long -lead items.
d. Designation of key personnel and their duties; lines of communication.
e. Project coordination.
£ Procedures and Processing of:
(1) RFIs.
(2) Field decisions.
(3) Substitutions.
(4) Submittals.
(5) Change Orders.
(6) Applications for Payment.
g. Procedures for testing.
h. Procedures for preparing and maintaining record documents.
Village of Mount Prospect 013100-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013100 - PROJECT COORDINATION AND MEETINGS: continued
i. Use of Premises:
(1) Office, work, storage, laydown, and parking areas.
(2) Owner's requirements.
(3) Work restrictions and hours.
j. Construction facilities, controls, and construction aids.
k. Temporary utilities.
1. Safety and first-aid.
m. Security.
n. Deliveries of Equipment and Materials.
4. Location of Meeting: At or near the Project Site, to be determined after award of
Contract.
5. Reporting:
a. Within three working days after the meeting, Engineer will prepare and distribute
minutes of the meeting to Owner and Contractor.
b. Contractor shall provide copies to Subcontractors and major Suppliers.
B. Coordination Schedules:
1. Engineer will conduct a meeting at least ten days before submission of the first
Application for Payment to finalize the initial coordination schedules requested under
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS.
2. The meeting shall be attended by:
a. Representative(s) of Contractor including Contractor's superintendent (and
scheduler).
b. At Owner's option, representatives of principal Subcontractors and Suppliers.
C. Engineer and Resident Project Representative.
d. Representative(s) of Owner.
C. Construction Progress Meetings:
1. Engineer will schedule and conduct a meeting at least bi-weekly and at other times
requested by Engineer. Representatives of the Owner, Engineer, and Contractor shall be
present at each meeting. With Engineer's concurrence, Contractor may request
attendance by representatives of Subcontractors, Suppliers, or other entities concerned
with current program or involved with planning, coordination, or performance of future
activities. All participants in the meeting shall be familiar with the Project and
authorized to conclude matters relating to the Work.
2. Contractor and each Subcontractor represented shall be prepared to discuss the current
construction progress report and any anticipated future changes to the schedule. Each
Subcontractor shall comment on the schedules of Contractor and other Subcontractors
and advise if their current progress or anticipated activities are compatible with that
Subcontractor's Work.
3. If one Subcontractor is delaying another, Contractor shall issue such directions as are
necessary to resolve the situation and promote construction progress.
4. Meeting Agenda:
a. Review of construction progress since previous meeting.
b. Field observations, interface requirements, conflicts.
C. Issues which may impede construction schedule.
d. Off -Site fabrication.
e. Delivery schedules.
f. Submittal schedules and status.
g. Site use; coordination with other contractors.
h. Temporary facilities, controls, and services.
Village of Mount Prospect 013100-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013100 - PROJECT COORDINATION AND MEETINGS: continued
i. Hours of Work.
j. Hazards and risks.
k. Housekeeping.
1. Quality and Work standards.
m. RFIs.
n. Status of Change Orders.
o. Documentation of information for payment requests.
p. Corrective measures and procedures to regain construction schedule if necessary.
q. Revisions to construction schedule.
r. Review of proposed activities for succeeding Work period.
S. Review proposed Contract modifications for:
(1) Effect on construction schedule and on completion date.
(2) Effect on other contracts of the Project.
t. Other business.
5. Location of Meetings: At or near Project Site, to be determined after award of Contract.
6. Reporting:
a. Within three working days after each meeting, Engineer will prepare and distribute
minutes of the meeting to Owner and Contractor.
b. Contractor shall distribute copies to principal Subcontractors and Suppliers.
1.06 REQUESTS FOR INFORMATION (RFIs):
A. Procedure: Promptly on discovery of the need for interpretation of the Contract Documents,
and if not possible to request interpretation at Project meeting, prepare and submit an RFI with
the content specified.
1. RFIs shall originate with Contractor. RFIs submitted by entities other than Contractor
will be returned with no response.
2. Coordinate and submit RFIs in a prompt manner so as to avoid delays in Contractor's
Work or work of Subcontractors.
B. Content of the RFI: Include a detailed, legible description of item needing interpretation and
the following:
1. Project name.
2. Date.
3. Name of Contractor.
4. Contract number and title.
5. Name of Engineer.
6. RFI number, numbered sequentially.
7. Specification Section number and title and related paragraphs, as appropriate.
8. Drawing number and detail references, as appropriate.
9. Field dimensions and conditions, as appropriate.
10. Contractor's suggested solution(s). If Contractor's solution(s) impact the Contract Times
or the Contract Price, Contractor shall state impact in the RFI.
11. Contractor's signature.
12. Attachments: Include drawings, descriptions, measurements, photos, product data, Shop
Drawings, and other information necessary to fully describe items needing interpretation.
C. Hard -Copy RFIs:
1. Identify each page of attachments with the RFI number and sequential page number.
D. Software -Generated RFIs: Software -generated form with substantially the same content as
indicated above.
1. Attachments shall be electronic files in Adobe Acrobat PDF format.
Village of Mount Prospect 013100-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013100 - PROJECT COORDINATION AND MEETINGS: continued
E. Engineer's Action: Engineer will review each RFI, determine action required, and return it.
Allow seven working days for Engineer's response for each RFI. RFIs received after 1:00
p.m. local time will be considered as received the following working day.
1. The following RFIs will be returned without action:
a. Requests for approval of Submittals.
b. Requests for approval of substitutions.
C. Requests for coordination information already indicated in the Contract Documents.
d. Requests for adjustments in the Contract Times or the Contract Price.
e. Requests for interpretation of Engineer's actions on Submittals.
f. Incomplete RFIs or RFIs with numerous errors.
2. Multiple RFIs addressing similar or identical issues may be addressed by Engineer with a
single broad response.
3. Engineer's action may include a request for additional information, in which case
Engineer's time for response will start again upon Contractor's response and resubmittal.
4. If Contractor believes the RFI response warrants change in the Contract Times or the
Contract Price, notify Engineer in writing within ten days of receipt of the RFI response.
F. On receipt of Engineer's action, update the RFI log and promptly distribute the RFI response to
affected parties. Review response and notify Engineer within seven days if Contractor
disagrees with response.
G. RFI Log: Prepare, maintain, and submit a tabular log of RFIs organized by the RFI number.
Submit log bi-weekly. Include the following:
1. Project name.
2. Name and address of Contractor.
3. Contractor representative name and telephone number.
4. Name and address of Engineer.
5. RFI number including RFIs that were dropped and not submitted.
6. RFI description.
7. Date the RFI was submitted.
8. Date Engineer's response was received.
9. Identification of related Field Order, Work Change Directive, and Proposal Request, as
appropriate.
PART 2 - PRODUCTS - Not Applicable.
PART 3 - EXECUTION - Not Applicable.
END OF SECTION 013100
Village of Mount Prospect 013100-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes administrative and procedural requirements for documenting the
progress of construction during performance of the Work, including the following:
1. Preliminary construction progress schedule.
2. Construction progress schedule.
3. Schedule of Submittals.
4. Schedule of values.
5. Construction progress reports.
6. Daily construction reports.
7. Equipment and Material location reports.
8. Field condition reports.
9. Special reports.
B. Related Work Specified Elsewhere:
1. For submitting and distributing meeting and conference minutes: SECTION 013100 -
PROJECT COORDINATION AND MEETINGS.
2. For submitting schedules and reports: SECTION 013300 - SUBMITTALS.
3. For submitting construction photographs: SECTION 013233 - PROJECT
PHOTOGRAPHS.
1.02 REFERENCES:
A. Associated General Contractor's of America (AGC):
1. Construction Planning and Scheduling.
1.03 DEFINITIONS:
A. Activity: A discrete part of a contract that can be identified for planning, scheduling,
monitoring, and controlling the construction Work. Activities included in a construction
schedule consume time and resources, but shall not include planned work stoppages.
Activities shall not normally reflect the Work of more than one trade.
1. Critical activities are activities on the critical path and have zero or negative float.
Critical activities must start and finish on the planned early start and finish times.
2. Predecessor Activity: An activity that precedes another activity in the network.
3. Successor Activity: An activity that follows another activity in the network.
B. "Baseline" schedule: The schedule submitted and accepted by Engineer for the Work.
C. Cost Loading: The allocation of the schedule of values for the completion of an activity as
scheduled. The sum of costs for all activities must equal the total Contract Price, unless
otherwise approved by Engineer.
D. CPM: Critical path method (CPM), which is a method of planning and scheduling a
construction contract where activities are arranged based on activity relationships. Network
calculations determine when activities can be performed and the critical path of Contract.
E. Critical Path: The longest connected chain of interdependent activities through the network
schedule that establishes the minimum overall Contract duration and contains no float.
F. Event: The starting or ending point of an activity. An event has no duration.
G. Float: The measure of leeway in starting and completing an activity.
1. Float time is not for the exclusive use or benefit of either Owner or Contractor, but is a
jointly owned, expiring Project resource available to both parties as needed to meet
schedule milestones and Contract completion date.
Village of Mount Prospect 013200-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS: continued
2. Free float is the amount of time an activity can be delayed without adversely affecting the
early start of the successor activity.
3. Total float is the measure of leeway in starting or completing an activity without
adversely affecting an intermediate deadline or the planned Contract completion date.
H. Fragnet: A partial or fragmentary network that breaks down activities into smaller activities
for greater detail.
I. Milestone: A key or critical point in time for reference or measurement. A milestone has no
duration.
J. Network Diagram: A graphic diagram of a network schedule, showing activities and activity
relationships.
K. Resource Loading: The allocation of manpower and equipment necessary for the completion
of an activity as scheduled.
1.04 SUBMITTALS:
A. Qualification Data: For scheduling consultant.
B. Schedule of Submittals: Submit in specified electronic format. Arrange the following
information in a tabular format:
1. Scheduled date for first submittal.
2. Specification Section number and title.
3. Submittal category (technical or informational).
4. Name of Subcontractor or Supplier.
5. Description of the Work covered.
6. Scheduled date for Engineer's final release or approval.
C. Preliminary Construction Progress Schedule: Submit one electronic copy and two opaque hard
copies.
1. Acceptance of cost -loaded preliminary construction schedule will not constitute
acceptance of schedule of values for cost -loaded activities.
D. Construction Progress Reports: Submit two copies of bi-weekly intervals.
E. Daily Construction Reports: Submit two copies at monthly intervals.
F. Material Location Reports: Submit two copies at monthly intervals.
G. Field Condition Reports: Submit two copies at time of discovery of differing conditions.
H. Special Reports: Submit two copies at time of unusual event.
1.05 COORDINATION:
A. Coordinate preparation and processing of schedules and reports with performance of
construction activities and with scheduling and reporting of separate contractors.
B. Coordinate construction progress schedule with the schedule of values, list of subcontracts,
schedule of Submittals, Material and Equipment procurement, progress reports, payment
requests, and other required schedules and reports.
1. Secure time commitments for performing critical elements of the Work from parties
involved.
2. Coordinate each construction activity in the network with other activities and schedule
them in proper sequence.
PART 2 - PRODUCTS
2.01 SCHEDULE OF SUBMITTALS:
A. Preparation: Submit a schedule of Submittals, arranged in chronological order by dates
required by construction progress schedule. Include time required for review, resubmittal,
Village of Mount Prospect 013200-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS: continued
ordering, manufacturing, fabrication, and delivery when establishing dates as required in
SECTION 013300 - SUBMITTALS.
1. Coordinate Submittals schedule with list of subcontracts, the schedule of values, and
"Baseline" construction progress schedule.
2. Initial Submittal: Submit concurrently with preliminary bar -chart schedule. Include
Submittals required during the first 14 days of construction. List those required to
maintain orderly progress of the Work and those required early because of long lead time
for manufacture or fabrication.
3. Final Submittal: Submit concurrently with the first complete submittal of construction
progress schedule.
2.02 CONTRACTOR'S CONSTRUCTION PROGRESS SCHEDULE, GENERAL:
A. Time Frame: Extend schedule from date established in the Notice to proceed to date of Final
Completion.
1. Contract completion date shall not be changed by submission of a schedule that shows an
early completion date, unless specifically authorized by Change Order.
2. Submittal Review Time: Include review and resubmittal times indicated in SECTION
013300 - SUBMITTALS in schedule. Coordinate Submittal review times in Contractor's
construction progress schedule with schedule of Submittals.
3. Substantial Completion: Indicate completion in advance of date established for
Substantial Completion, and allow time for Engineer's administrative procedures
necessary for certification of Substantial Completion.
B. Milestones: Include milestones indicated in the Contract Documents in schedule, including,
but not limited to, the Notice to Proceed, Substantial Completion, and Final Completion.
C. Computer Software: Prepare schedules using a program that has been developed specifically
to manage construction schedules and is acceptable to Engineer:
1. Primavera Project Planner (P3).
2. Primavera 3e.
3. Primavera 5.0.
4. SureTrak.
5. Engineer -approved equal.
2.03 PRELIMINARY CONSTRUCTION PROGRESS SCHEDULE:
A. Bar -Chart Schedule: Submit preliminary horizontal bar -chart -type construction schedule
within seven days of date established in the Notice to Proceed.
1. Preparation: Indicate each significant construction activity separately. Identify first
workday of each week with a continuous vertical line. Outline significant construction
activities for first 60 days of construction. Include skeleton diagram for the remainder of
the Work.
B. Preliminary Schedule of Values:
1. Initiate a preliminary value assigned to each significant construction activity.
2. Values shall give an indication of cash requirement prediction, with total equal to
Contract Price.
3. Submit within ten days of Effective Date of Contract to Engineer (and Owner) for
review.
2.04 CONSTRUCTION PROGRESS SCHEDULE (GANTT CHART):
A. Gantt -Chart Schedule: After submittal of preliminary construction progress schedule as stated
above, submit a detailed construction progress schedule within 30 days after the Notice to
Village of Mount Prospect 013200-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS: continued
Proceed. Base the schedule on the preliminary construction progress schedule and incorporate
review comments and other feedback.
B. The schedule shall show the Work in a horizontal bar chart or other graphic format suitable for
displaying scheduled and actual progress.
1. The schedule shall indicate phases of the Work, starting date, interim milestones, and
dates of Substantial Completion and Final Completion.
2. Breakdown Work phases into separate time bar for each significant construction activity
entry, with dates Work is expected to begin and be completed. Within each time bar,
indicate estimated completion percentage in 10% increments.
3. Scale and spacing shall allow room for notation and revisions.
4. Sheet Size: Minimum 11 x 17 inches.
C. Provide subschedules to define in more detail critical portions of schedules, including
inspections and tests.
D. Coordinate construction progress schedule with schedule of values, schedule of Submittals
schedule, procurement schedule, progress reports, and payment requests.
E. Engineer will review and comment on construction progress schedule and, upon agreement
between Engineer and Contractor on necessary changes:
1. Contractor shall distribute copies as specified of the accepted "baseline" schedule to
Engineer. Contractor shall provide additional copies to Subcontractors and other parties
required to comply with scheduled dates, one copy to each party.
F. Revise the construction progress schedule after each meeting, event, or activity where revisions
have been recognized and accepted to reflect impacts of new developments on the schedule.
G. Update and submit five copies to Engineer of the revised schedule at least once each month to
show actual progress compared to the originally accepted "baseline" schedule and any
proposed changes in the schedule of remaining Work. Include with construction progress
report.
2.05 SCHEDULE OF VALUES:
A. Based on the preliminary draft schedule of values, reviewed by Engineer (and Owner), submit
finalized schedule of values acceptable to Engineer as to form and basic details. Submit final
within 30 days after Notice to Proceed.
B. Coordinate preparation of schedule of values with preparation and content of construction
progress schedule.
C. Content:
1. Schedule shall list the installed value of the component parts of the Work in sufficient
detail to serve as a basis for computing values for progress payments during
construction.
2. Follow the construction progress schedule breakdown of Work activities as format for
listing component items and assigning values.
3. For each major line item, list subvalues of major products or operations under the item.
a. Each item shall include a directly proportional amount of the Contractor's overhead
and profit.
b. For items on which progress payments will be requested for stored materials
received, but not installed, break down the value into:
(1) The cost of the materials, delivered and unloaded, including taxes paid unless
taxes are exempted.
(2) The total installed value.
C. The sum of all values listed in the schedule shall equal the total Contract Price.
Village of Mount Prospect 013200-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS: continued
2.06 REPORTS:
A. Construction Progress Reports:
1. Submit a report on actual construction progress on a monthly basis. More frequent
reports may be required should the Work fall behind the accepted schedule.
2. Construction progress reports shall consist of the revised construction progress schedule
and a narrative report which shall include but not be limited to the following:
a. Comparison of actual progress to planned progress shown on originally accepted
schedule.
b. Summary of activities completed since the previous construction progress report.
C. Summary of activities planned for next reporting period.
d. Planned, earned, and spent earned value analysis for the month.
e. Identification of problem areas.
f. A description of current and anticipated delaying factors, if any.
g. Impact of possible delaying factors.
h. Proposed corrective actions.
3. Submit a construction progress report to Engineer with each application for partial
payment. Work reported complete but not readily apparent to Engineer must be
substantiated with supporting data when requested by Engineer.
4. If a schedule update reveals that, through no fault of Owner, the Work is likely to be
completed later than the Contract completion date, Contractor shall:
a. Establish a plan for making up lost time.
(1) Increase number of workers, or
(2) Increase amount or kinds of tools, or
(3) Work overtime or additional shifts, or
(4) A combination of 2 or more of the above 3 actions.
b. Submit plan to Owner and Engineer before implementing the plan.
C. Take actions as necessary to get the Work back on schedule at no additional cost to
Owner.
B. Daily Construction Reports: Prepare a daily construction report recording the following
information concerning events at Project Site:
1. List of Subcontractors at Project Site.
2. List of separate contractors at Project Site.
3. Approximate count of personnel at Project Site, and breakdown by craft.
4. Equipment at Project Site.
5. Material deliveries.
6. High and low temperatures and general weather conditions.
7. Accidents.
8. Meetings and significant decisions.
9. Unusual events (refer to special reports).
10. Stoppages, delays, shortages, and losses.
11. Meter readings and similar recordings.
12. Emergency procedures.
C. Field Condition Reports: Promptly on discovery of a difference between field conditions and
the Contract Documents, prepare and submit a detailed report. Submit with a request for
information (RFI). Include a detailed description of the differing conditions, together with
recommendations for changing the Contract Documents.
D. Special Reports:
1. General: Submit special reports directly to Owner within one day of an occurrence.
Distribute copies of report to parties affected by the occurrence.
Village of Mount Prospect 013200-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013200 - CONSTRUCTION PROGRESS SCHEDULES AND REPORTS: continued
2. Reporting Unusual Events: When an event of an unusual and significant nature occurs at
Project Site, whether or not related directly to the Work, prepare and submit a special
report. List chain of events, persons participating, response by Contractor's personnel,
evaluation of results or effects, and similar pertinent information. Advise Owner in
advance when these events are known or predictable.
PART 3 - EXECUTION (Not Applicable)
END OF SECTION 013200
Village of Mount Prospect 013200-6 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes definitions, descriptions, transmittal, and review of Submittals.
B. Related Work Specified Elsewhere:
1. SECTION 013100 —PROJECT COORDINATION AND MEETINGS
2. SECTION 013200 — CONSTRUCTION PROGRESS SCHEDULES AND REPORTS
3. SECTION 017800 — CONTRACT CLOSEOUT
1.02 GENERAL INFORMATION:
A. Definitions:
1. Shop Drawings, product data, and Samples are technical Submittals prepared by
Contractor, Subcontractor, manufacturer, or Supplier and submitted by Contractor to
Engineer as a basis for approval of the use of Equipment and Materials proposed for
incorporation in the Work or needed to describe installation, operation, maintenance, or
technical properties, as specified in each Division of the Specifications.
a. Shop Drawings include custom -prepared data of all types including drawings,
diagrams, performance curves, material schedules, templates, instructions, and
similar information not in standard printed form applicable to other projects.
b. Product data includes standard printed information on materials, products, and
systems; not custom -prepared for this Proj ect, other than the designation of
selections from available choices.
C. Samples include both fabricated and unfabricated physical examples of materials,
products, and Work; both as complete units and as smaller portions of units of
Work; either for limited visual inspection or (where indicated) for more detailed
testing and analysis. Mock-ups are a special form of Samples which are too large to
be handled in the specified manner for transmittal of Sample Submittals.
2. Informational Submittals are those technical reports, administrative Submittals,
certificates, and guarantees not defined as Shop Drawings, product data, or Samples.
a. Technical reports include laboratory reports, tests, technical procedures, technical
records, and Contractor's design analysis.
b. Administrative Submittals are those nontechnical Submittals required by the
Contract Documents or deemed necessary for administrative records. These
Submittals include maintenance agreements, Bonds, Project photographs, physical
work records, statements of applicability, copies of industry standards, Project
record data, schedules, security/protection/safety data, and similar type Submittals.
C. Certificates and guarantees are those Submittals on Equipment and Materials where
a written certificate or guarantee from the manufacturer or Supplier is called for in
the Specifications.
3. Refer to ARTICLES 1.03 and 1.04 of this Part for detailed lists of Submittals and specific
requirements.
B. Quality Requirements:
1. Submittals such as Shop Drawings and product data shall be of suitable quality for
legibility and reproduction purposes. Every line, character, and letter shall be clearly
legible. Drawings such as reproducibles shall be useable for further reproduction to yield
legible hard copy.
2. Documents submitted to Engineer that do not conform to specified requirements shall be
subject to rejection by Engineer, and upon request by Engineer, Contractor shall resubmit
Village of Mount Prospect 013300-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
conforming documents. If conforming Submittals cannot be obtained, such documents
shall be retraced, redrawn, or photographically restored as may be necessary to meet such
requirements. Contractor's (or his Subcontractor's) failure to initially satisfy the legibility
quality requirements will not relieve Contractor (or his Subcontractors) from meeting the
required schedule for Submittals.
C. Language and Dimensions:
1. All words and dimensional units shall be in the English language.
2. Metric dimensional unit equivalents may be stated in addition to the English units.
However, English units of measurement shall prevail.
D. Submittal Completeness:
1. Submittals shall be complete with respect to dimensions, design criteria, materials of
construction, and other information specified to enable Engineer to review the
information effectively.
2. Where standard drawings are furnished which cover a number of variations of the general
class of Equipment, each drawing shall be annotated to indicate exactly which parts of
the drawing apply to the Equipment being furnished. Use hatch marks to indicate
variations that do not apply to the Submittal. The use of "highlighting markers" will not
be an acceptable means of annotating Submittals. Annotation shall also include proper
identification of the Submittal permanently attached to the drawing.
3. Reproductions or copies of Contract Drawings or portions thereof will not be accepted as
complete fabrication or erection drawings. Contractor may use a reproduction of
Contract Drawings for erection drawings to indicate information on erection or to identify
detail drawing references. Whenever the Drawings are revised to show this additional
Contractor information, Engineer's title block shall be replaced with Contractor's title
block, and Engineer's professional seal shall be removed from the drawing. Contractor
shall revise these erection drawings for subsequent Engineer revisions to the Contract
Drawings.
E. Form of Submittals:
1. Submittals and other Project documents shall be transmitted in electronic format as
specified.
a. Selected Submittals may be provided in paper ("hardcopy") copies with advance
approval of Engineer, and using the procedures specified herein.
b. Equipment instruction books and operating manuals shall be provided in paper
copies in addition to specified electronic format.
2. Electronic Format:
a. Scanned Submittals and documents are not acceptable. Transmit Submittals and
Project documents in:
(1) Nonproprietary, native electronic format incorporating any necessary
reference files, or
(2) Adobe *PDF files created directly from native electronic format, or
(3) Engineer -approved equal.
b. For any given Submittal, the filename and format shall be consistent for initial
submission and subsequent revisions of the same. Use consistent naming
convention throughout.
(1) Nonconforming Submittals are subject to re j ection by Engineer.
C. Provide "as -constructed" Submittals, record documents, Equipment instruction
books and operating manuals, and other documents on CD-ROM in Adobe *PDF
format as required and approved by Engineer. In addition, provide all drawings in
AutoCAD 2013 format on CD-ROM.
Village of Mount Prospect 013300-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
d. Equipment instruction books and operating and maintenance manuals shall be in
Adobe *PDF format combined in one pdf file for the complete O&M manual, or
divided into pdf files that represent entire volumes (corresponding to hardcopy
volumes). The pdf files shall be completely bookmarked with links within the index
sheet to the different sections within the manuals/volumes, corresponding to the
defined tabs within the hardcopy version.
3. Digital delivery media shall be via email or Engineer's Mass File Transfer (MFT) site(s).
1.03 TECHNICAL SUBMITTALS:
A. Items shall include, but not be limited to, the following:
1. Manufacturer's specifications.
2. Catalogs, or parts thereof, of manufactured Equipment.
3. Shop fabrication and erection drawings.
4. Bills of material and spare parts list.
5. Instruction books and operating manuals.
6. Material lists or schedules.
7. Performance tests on Equipment by manufacturers.
8. Concrete mix design information.
9. Samples and color charts.
10. All drawings, catalogs or parts thereof, manufacturer's specifications and data, Samples,
instructions, and other information specified or necessary:
a. For Engineer to determine that Equipment and Materials conform to the design
concept and comply with intent of the Contract Documents.
b. For proper erection, installation, operation, and maintenance of Equipment and
Materials which Engineer will review for general content but not for basic details.
C. For Engineer to determine what supports, anchorages, structural details,
connections, and services are required for Equipment and Materials, and effects on
contiguous or related structures and Equipment and Materials.
B. Schedule of Submittals:
1. In establishing schedule for Submittals, allow 10 days in Engineer's office for reviewing
original Submittals and 10 days in Engineer's office for reviewing resubmittals.
2. Submittals requiring revision shall be resubmitted within 10 days after receipt of
Engineer's review notations.
3. The schedule shall indicate the anticipated dates of original submission for each item and
Engineer's approval thereof, and shall be based upon at least one resubmission of each
item.
4. Schedule all Submittals (Shop Drawings, product data, and Samples) required prior to
fabrication or manufacture for submission within 30 days of the Notice to Proceed.
Schedule Submittals pertaining to storage, installation, and operation at the Site for
Engineer's approval prior to delivery of the Equipment and Materials.
5. Resubmit Submittals the number of times required for Engineer's "Submittal Approved."
However, any need for resubmittals in excess of the number set forth in the accepted
schedule, or any other delay in obtaining approval of Submittals, will not be grounds for
extension of the Contract Times, provided Engineer completes his reviews within the
times specified.
6. Where a Submittal is required by the Contract Documents or the accepted schedule of
Submittals, any related Work performed prior to Engineer's review and approval of the
pertaining Submittal will be at the sole expense and responsibility of Contractor.
C. Transmittal of Submittals:
Village of Mount Prospect 013300-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
1. All Submittals (Shop Drawings, product data, and Samples) for Equipment and Materials
furnished by Contractor, Subcontractors, manufacturers, and Suppliers shall be submitted
to Engineer by Contractor.
2. After checking and verifying all field measurements, transmit all Submittals to Engineer
for approval as follows:
a. Submittal Information Block:
(1) Affix to all paper copies whether Submittal is prepared by Contractor,
Subcontractor, or Supplier. Use a stamp with information acceptable to the
Engineer.
b. Mark each Submittal by Project name and number, Contract title and number, and
applicable Specification Section and Article number. Include in the letter of
transmittal the Drawing number and title, sheet number (if applicable), revision
number, and electronic filename (if applicable). Unidentifiable Submittals will be
returned for proper identification.
C. Check stamp and approve Contractor's approval of Submittals of Subcontractors,
Suppliers, and manufacturers prior to transmitting them to Engineer. Contractor's
submission shall constitute a representation to Owner and Engineer that Contractor
approves Submittals and has determined and verified all design criteria, quantities,
dimensions, field construction and installation criteria, materials, catalog numbers,
compliance with Laws and Regulations, and similar data, and Contractor assumes
full responsibility for doing so; and Contractor has coordinated each Submittal with
the requirements of the Work and the Contract Documents.
d. At the time of each submission, call to the attention of Engineer in the letter of
transmittal any deviations from requirements of the Contract Documents.
e. Make all modifications noted or indicated by Engineer and return the required
number of revised Submittals until approved. Direct specific attention in writing, or
on revised Submittals, to changes other than the modifications called for by
Engineer on previous Submittals. After paper copy Submittals have been approved,
submit copies thereof for final distribution. Previously approved Submittals
transmitted for final distribution will not be further reviewed and are not to be
revised. If errors are discovered during manufacture or fabrication, correct the
Submittal and resubmit for review.
f. Following completion of the Work and prior to final payment, furnish record
documents and approved Samples and Shop Drawings necessary to indicate "as
constructed" conditions, including field modifications, in the number of copies
specified. Furnish additional copies for insertion in Equipment instruction books
and operating manuals as required. All such copies shall be clearly marked
"PROJECT RECORD."
(1) Submit a final record copy of the Master Field Drawing list which shall
indicate the final revision status of each drawing on the list.
g. Keep a copy or sample of each Submittal in good order at the Site.
3. Quantity Requirements:
a. Except as otherwise specified, transmit all Shop Drawings in the following
quantities:
(1) Initial Submittal:
(a) Electronic -One copy to Engineer.
(2) Resubmittals:
(a) Electronic -One copy to Engineer.
(3) Submittal for final distribution:
Village of Mount Prospect 013300-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
(a) Paper - 3 copies plus the number required by Contractor, to Engineer.
(b) Electronic -One copy to Engineer.
(4) As -constructed documents:
(a) Paper - 3 copies to Engineer.
(b) Electronic -One copy to Engineer. (One copy to Owner.)
b. Transmit Submittals of product data as follows:
(1) Initial Submittal:
(a) Electronic -One copy to Engineer.
(2) Resubmittals:
(a) Electronic -One copy to Engineer.
(3) Submittal for final distribution:
(a) Paper - 3 copies plus the number of copies required by Contractor, to
Engineer.
(b) Electronic -One copy to Engineer.
C. Transmit Submittals of Material Samples, color charts, and similar items as follows:
(1) Initial Submittal - 3 to Engineer.
(2) Resubmittal - 3 to Engineer.
(3) Upon approval, 1 Sample will be returned to Contractor.
d. Transmit Submittals of Equipment instruction books and operating manuals as
follows:
(1) Initial Submittal:
(a) Electronic -One copy to Engineer. One copy to Owner.
(2) Resubmittals:
(a) Electronic -One copy to Engineer. One copy to Owner.
(3) Submittal for Final Distribution - 3 paper copies to Engineer.
e. When all Submittals have been updated to "as -constructed" conditions, transmit to
Engineer and to Owner in electronic format.
f. Owner may copy and use for internal operations and staff training purposes any and
all document Submittals required by this Contract and approved for final
distribution, whether or not such documents are copyrighted, at no additional cost to
Owner. If permission to copy any such Submittal for the purposes stated is
unreasonably withheld from Owner by Contractor or any Subcontractor,
manufacturer, or Supplier, Contractor shall provide to Engineer 50 copies plus the
number of copies required by Contractor at each final distribution issue.
D. Engineer's Review:
1. Engineer will review and take appropriate action on Submittals in accordance with the
accepted schedule of Submittals. Engineer's review and approval will be only to
determine if the items of Equipment and Materials covered by the Submittals will, after
installation or incorporation in the Work, conform to information given in the Contract
Documents and be compatible with the design concept of the completed Project as a
functioning whole as indicated by the Contract Documents.
2. Engineer's review and approval will not extend to design data reflected in Submittals
which is peculiarly within the special expertise of Contractor or Contractor's
Subcontractors or Suppliers. Review and approval of a component item as such will not
indicate approval of the assembly in which the item functions.
3. Engineer's review and approval of Shop Drawings, product data, or Samples will not
relieve Contractor of responsibility for any deviation from requirements of the Contract
Documents unless Contractor has in writing called Engineer's attention to such deviation
at the time of submission, and Engineer has given written concurrence in and approval of
Village of Mount Prospect 013300-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
the specific deviation. Approval by Engineer shall not relieve Contractor from
responsibility for errors or omissions in Submittals.
E. Submittal Action Stamp:
1. Engineer's review action stamp, appropriately completed, will appear on all Submittals of
Contractor when returned by Engineer. Review status designations listed on Engineer's
action stamp are defined as follows:
A - SUBMITTAL APPROVED: Signifies Equipment or Material
represented by the Submittal conforms with the design concept and
complies with the intent of the Contract Documents and is approved
for incorporation in the Work. Contractor is to proceed with
fabrication or procurement of the items and with related Work. Copies
of the Submittal are to be transmitted to Engineer for final distribution.
B -SUBMITTAL APPROVED AS NOTED (RESUBMIT): Signifies
Equipment and Material represented by the Submittal conforms with
the design concept and complies with the intent of the Contract
Documents and is approved for incorporation in the Work in
accordance with Engineer's notations. Contractor is to proceed with
fabrication or procurement of the items and with related Work in
accordance with Engineer's notations and is to submit a revised
Submittal responsive to notations marked on the returned Submittal or
written in the letter of transmittal.
C -SUBMITTAL RETURNED FOR REVISION (RESUBMIT):
Signifies Equipment and Material represented by the Submittal appears
to conform with the design concept and comply with the intent of the
Contract Documents but information is either insufficient in detail or
contains discrepancies which prevent Engineer from completing his
review. Contractor is to resubmit revised information responsive to
Engineer's annotations on the returned Submittal or written in the letter
of transmittal. Fabrication or procurement of items represented by the
Submittal and related Work is not to proceed until the Submittal is
approved.
D -SUBMITTAL NOT APPROVED (SUBMIT ANEW): Signifies
Equipment and Material represented by the Submittal does not
conform with the design concept or comply with the intent of the
Contract Documents and is disapproved for use in the Work.
Contractor is to provide Submittals responsive to the Contract
Documents.
E - PRELIMINARY SUBMITTAL: Signifies Submittals of such
preliminary nature that a determination of conformance with the design
concept or compliance with the intent of the Contract Documents must
be deferred until additional information is furnished. Contractor is to
submit such additional information to permit layout and related
activities to proceed.
Village of Mount Prospect 013300-6 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
F - FOR REFERENCE, NO APPROVAL REQUIRED: Signifies
Submittals which are for supplementary information only; pamphlets,
general information sheets, catalog cuts, standard sheets, bulletins and
similar data, all of which are useful to Engineer or Owner in design,
operation, or maintenance, but which by their nature do not constitute a
basis for determining that items represented thereby conform with the
design concept or comply with the intent of the Contract Documents.
Engineer reviews such Submittals for general content but not for basic
details.
G - DISTRIBUTION COPY (PREVIOUSLY APPROVED): Signifies
Submittals which have been previously approved and are being
distributed to Contractor, Owner, Resident Project Representative, and
others for coordination and construction purposes.
F. Instruction Books and Operating Manuals:
1. In addition to electronic Submittals specified above, equipment instruction books and
operating manuals prepared by the manufacturer shall include the following:
a. Index and tabs.
b. Instructions for installation, start-up, operation, inspection, maintenance, parts lists
and recommended spare parts, and data sheets showing model numbers.
C. Applicable drawings.
d. Warranties and guarantees.
e. Address of nearest manufacturer -authorized service facility.
f. All additional data specified.
2. Information listed above shall be bound into hard -back binders of three-ring type. Sheet
size shall be 8-1/2 x 11. Binder color shall be white. Capacity shall be a minimum of 1-
1/2 inches, but sufficient to contain and use sheets with ease.
a. Provide the following accessories:
(1) Label holder.
(2) Business card holder.
(3) Sheetlifters.
(4) Horizontal pockets.
b. The following information shall be imprinted, inserted, or affixed by label on the
binder front cover:
(1) Owner's name.
(2) Owner's facility or plant name.
(3) Equipment item name.
(4) Volume number (if applicable).
(5) Contract number.
(6) Manufacturer's name and address.
C. The following information shall be imprinted, inserted, or affixed by label on the
binder spine:
(1) Equipment item name.
(2) Owner's name and Owner's facility or plant name.
(3) Manufacturer's name.
(4) Contract number.
(5) Volume number (if applicable).
d. Submit mockup of cover and spine for Engineer's review.
Village of Mount Prospect 013300-7 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
G. Samples:
1. Office Samples shall be of sufficient size and quantity to clearly illustrate the following:
a. Functional characteristics of the product, with integrally related parts and
attachment devices.
b. Full range of color, texture, and pattern.
C. Material, manufacturer, pertinent catalog number, and intended use.
1.04 INFORMATIONAL SUBMITTALS:
A. Informational Submittals are comprised of technical reports, administrative Submittals, and
guarantees which relate to the Work, but do not require Engineer approval prior to proceeding
with the Work. Informational Submittals include:
1. Hydrostatic testing of pipes.
2. Field test reports.
3. Concrete cylinder test reports.
4. Certification on Materials:
5. Soil test reports.
6. Piping stress analysis.
7. Shipping or packing lists.
8. Job progress schedules.
9. Equipment and Material delivery schedules.
10. Progress photographs.
11. Warranties and guarantees.
12. Hydraulic calculations.
B. Transmittal of Informational Submittals:
1. All informational Submittals furnished by Subcontractors, manufacturers, and Suppliers
shall be submitted to Engineer by Contractor unless otherwise specified.
a. Identify each informational Submittal by Project name and number, Contract title
and number, and Specification Section and Article number marked thereon or in
letter of transmittal. Unidentifiable Submittals will be returned for proper
identification.
b. At the time of each submission, call to the attention of Engineer in the letter of
transmittal any deviations from requirements of the Contract Documents.
2. Quantity Requirements:
a. Technical reports and administrative Submittals except as otherwise specified:
(1) Paper: 3 copies to Engineer.
(2) Electronic: One to Engineer.
b. Written Certificates and Guarantees:
(1) Engineer: 3 copies.
3. Test Reports:
a. Responsibilities of Contractor, Owner, and Engineer regarding tests and inspections
of Equipment and Materials and completed Work are set forth elsewhere in these
Contract Documents.
b. The party specified responsible for testing or inspection shall in each case, unless
otherwise specified, arrange for the testing laboratory or reporting agency to
distribute test reports as follows:
(1) Owner: Two copies.
(2) Engineer: One copy.
(3) Resident Project Representative: One copy.
(4) Contractor: Two copies.
Village of Mount Prospect 013300-8 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 013300 - SUBMITTALS: continued
(5) Manufacturer or Supplier: One copy.
C. Engineer's Review:
1. Engineer will review informational Submittals for indications of Work or Material
deficiencies.
2. Engineer will respond to Contractor on those informational Submittals which indicate
Work or Material deficiency.
PART 2 - PRODUCTS - Not Applicable.
PART 3 - EXECUTION — Not Applicable.
END OF SECTION 013 3 00
Village of Mount Prospect 013300-9 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 014200 - DEFINITIONS AND STANDARDS
PART 1 - GENERAL
1.01 SUMMARY:
A. Definitions:
1. Basic contract definitions used in the Contract Documents are defined in the GENERAL
CONDITIONS. Definitions and explanations are not necessarily either complete or
exclusive, but are general for the Work.
2. General Requirements are the provisions or requirements of DIVISION 1 Sections, and
which apply to the entire Work of the Contract.
B. Related Information Specified Elsewhere: Specification standards and associations applicable
to the Work are specified in each Section.
1.02 SPECIFICATION FORMAT AND CONTENT EXPLANATIONS:
A. Specification Format: The Specifications are organized into Divisions and Sections based on
the Construction Specifications Institute's (CSI) Section Format and MasterFormat numbering
system. Some portions may not fully comply and no particular significance will be attached to
such compliance or noncompliance.
1. Divisions and Sections: For convenience, a basic unit of Specification text is a "Section,"
each unit of which is numbered and named. These are organized with related Sections,
into "Divisions," which are recognized as the present industry consensus on uniform
organization and sequencing of Specifications. The Section title is not intended to limit
meaning or content of Section, nor to be fully descriptive of requirements specified
therein, nor to be an integral part of text.
2. Section Numbering: Used for identification and to facilitate cross-references in Contract
Documents. Sections are placed in numeric sequence; however, numbering sequence is
not complete, and listing of Sections in Table of Contents at beginning of the Project
Manual must be consulted to determine numbers and names of Specification Sections in
these Contract Documents.
3. Page Numbering: Numbered independently for each Section. Section number is shown
with page number at bottom of each page, to facilitate location of text.
4. Parts: Each Section of Specifications generally has been subdivided into three basic
"parts" for uniformity and convenience (PART 1 - GENERAL, PART 2 - PRODUCTS,
and PART 3 - EXECUTION). These "Parts" do not limit the meaning of text within.
Some Sections may not contain all three "Parts" when some are not applicable, or may
contain more than three "Parts" to add clarity to organization of Section.
5. Underscoring of Titles: Used strictly to assist reader of Specification in scanning text for
key words in content. No emphasis on or relative importance is intended except where
underscoring may be used in body of text to emphasize a duty, critical requirement, or
similar situation.
6. Project Identification: Project file number and identification are recorded at bottom of
each page of Specifications to minimize possible misuse of Specifications, or confusion
with other Project Specifications.
B. Specification Content:
1. These Specifications apply certain conventions in the use of language and the intended
meaning of certain terms, words, and phrases when used in particular situations or
circumstances. These conventions are explained as follows:
a. Imperative and Streamlined Language: These Specifications are written in
imperative and abbreviated form. This imperative language of the technical
Village of Mount Prospect 014200-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 014200 -DEFINITIONS AND STANDARDS: continued
Sections is directed at the Contractor, unless specifically noted otherwise.
Incomplete sentences shall be completed by inserting "shall," "the Contractor shall,"
and "shall be," and similar mandatory phrases by inference in the same manner as
they are applied to notes on the Drawings. The words "shall be" shall be supplied
by inference where a colon (:) is used within sentences or phrases. Except as
worded to the contrary, fulfill (perform) all indicated requirements whether stated
imperatively or otherwise.
b. Specifying Methods: The techniques or methods of specifying requirements varies
throughout text, and may include "prescriptive," "compliance with standards,"
"performance," "proprietary," or a combination of these. The method used for
specifying one unit of Work has no bearing on requirements for another unit of
Work.
C. Overlapping and Conflicting Requirements: Where compliance with two or more
industry standards or sets of requirements is specified, and overlapping of those
different standards or requirements establishes different or conflicting minimums or
levels of quality, notify Engineer in writing for a decision, which Engineer will
render in writing within a reasonable time.
d. Abbreviations: Throughout the Contract Documents are abbreviations implying
words and meanings which shall be appropriately interpreted. Specific
abbreviations have been established, principally for lengthy technical terminology
and in conjunction with coordination of Specification requirements with notations
on Drawings and in schedules. These are normally defined at first instance of use.
Organizational and association names and titles of general standards are also
abbreviated.
C. Assignment of Specialists: In certain instances, Specification text requires that specific Work
be assigned to specialists in the operations to be performed. These specialists shall be engaged
for performance of those units of Work, and assignments are requirements over which
Contractor has no choice or option. These assignments shall not be confused with, and are not
intended to interfere with, enforcement of building codes and similar regulations governing the
Work, local trade and union jurisdictions, and similar conventions. Nevertheless, final
responsibility for fulfillment of Contract requirements remains with Contractor.
D. Trades: Except as otherwise specified or indicated, the use of titles such as "carpentry" in
Specification text, implies neither that the Work must be performed by an accredited or
unionized tradesperson of corresponding generic name (such as "carpenter"), nor that specified
requirements apply exclusively to work by tradespersons of that corresponding generic name.
1.03 DRAWING SYMBOLS:
A. Except as otherwise indicated, graphic symbols used on Drawings are those symbols
recognized in the construction industry for purposes indicated. Refer instances of uncertainty
to Engineer for clarification.
1.04 INDUSTRY STANDARDS:
A. Applicability of Standards: Except where the Contract Documents include more stringent
requirements, applicable construction industry standards have the same force and effect as if
bound or copied directly into the Contract Documents. Such standards are made a part of the
Contract Documents by reference and are stated in each Section.
1. Referenced standards, referenced directly in Contract Documents or by governing
regulations, have precedence over nonreferenced standards which are recognized in
industry for applicability to the Work.
Village of Mount Prospect 014200-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 014200 -DEFINITIONS AND STANDARDS: continued
2. Where compliance with an industry standard is required, the latest standard in effect at
time of opening Bids shall govern.
3. Where an applicable code or standard has been revised and reissued after the effective
date of the Contract and before performance of Work affected by the revision, Engineer
will decide whether to issue a Change Order to proceed with the revised standard.
4. In every instance the quantity or quality level shown or specified shall be the minimum to
be provided or performed. The actual installation may comply exactly, within specified
tolerances, with the minimum quantity or quality specified, or it may exceed that
minimum within reasonable limits. In complying with these requirements, indicated
numeric values are minimum or maximum values, as noted, or appropriate for the context
of the requirements. Refer instances of uncertainty to Engineer for a decision before
proceeding.
5. Each entity engaged in construction on the Project is required to be familiar with industry
standards applicable to that entity's construction activity. Copies of applicable standards
are not bound with the Contract Documents.
a. Where copies of standards are needed for performance of a required construction
activity, Contractor shall obtain copies directly from the publication source.
B. Abbreviations and Names: Trade association names and titles of general standards are
frequently abbreviated. Where such acronyms or abbreviations are used in the Specifications
or other Contract Documents, they mean the recognized name of the trade association,
standards generating organization, authority having jurisdiction, or other entity applicable to
the context of the text provision.
PART 2 - PRODUCTS - Not Applicable.
PART 3 - EXECUTION - Not Applicable
END OF SECTION 014200
Village of Mount Prospect 014200-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 015700 - TEMPORARY BARRIERS AND CONTROLS
PART 1 - GF.NF.RAT
1.01 SUMMARY:
A. This Section includes General Requirements for:
1. Safety and protection of Work.
2. Safety and protection of existing property.
3. Barriers.
4. Environmental controls.
5. Access roads and parking areas.
6. Traffic control and use of roadways.
PART 2 - PRODUCTS — Not Applicable.
P A R T I- F.XF.CT TTT(lN
3.01 SAFETY AND PROTECTION OF WORK AND PROPERTY:
A. General:
1. Provide for the safety and protection of the Work and of Materials and Equipment to be
incorporated therein, whether in storage on or off the Site. Provide protection at all
times against rain, wind, storms, frost, freezing, condensation, or heat so as to maintain
all Work and Equipment and Materials free from injury or damage. At the end of each
day, all new Work likely to be damaged shall be appropriately protected.
2. Notify Engineer immediately at any time operations are stopped due to conditions which
make it impossible to continue operations safely or to obtain proper results.
3. Construct and maintain all necessary temporary drainage and do all pumping necessary to
keep excavations, floors, pits, trenches, manholes, and ducts free of water.
4. Protect floors from damage by proper covering and care when handling heavy equipment,
painting, or handling mortar or other such materials. Use proper cribbing and shoring to
prevent overloading of floors while moving heavy equipment. Provide metal pans under
pipe -threading machines and clean such pans daily, keeping oil off floors. Restore floors
to former condition where damaged or stained.
5. Concrete floors less than 28 days old shall not be loaded without written permission from
Engineer.
6. Restrict access to roofs except as required by the Work. Where access is required,
provide protection with plywood, boards, or other suitable materials.
B. Property Other than Owner's:
1. Provide for the safety and protection of property at the Site or adjacent thereto, including
trees, shrubs, lawns, walks, pavements, roadways, structures, utilities, and Underground
Facilities not designated for removal, relocation, or replacement in the course of
construction. Report immediately to the owners thereof and promptly repair damage to
existing facilities resulting from construction operations.
2. Names and telephone numbers of representatives of agencies and utilities having
jurisdiction over streets and utilities in the Work area shall be obtained by the Contractor.
Concerned agencies or utilities shall be contacted a minimum of 48 hours prior to
performing Work, closing streets and other traffic areas, or excavating near underground
utilities or pole lines.
a. Water.
Village of Mount Prospect 015700-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 015700 - TEMPORARY BARRIERS AND CONTROLS: continued
b. Gas.
C. Sanitary sewers.
d. Storm drains.
e. Pipeline companies.
f. Telephone.
g. Electric.
h. Municipal streets.
i. State highways.
j. City engineer.
k. Fire.
1. Police.
3. Operation of valves or other appurtenances on existing utilities, when required, shall be
by or under the direct supervision of the owning utility.
4. Where fences are to be breached on private property, the owners thereof shall be
contacted and arrangements made to ensure proper protection of any livestock or other
property thus exposed.
5. The applicable requirements specified for protection of the Work shall also apply to the
protection of existing property of others.
6. Before acceptance of the Work by Owner, restore all property affected by Contractor's
operations to the original or better condition.
3.02 BARRIERS:
A. General:
1. Furnish, install, and maintain suitable barriers as required to prevent public entry, to
protect the public, and to protect the Work, existing facilities, trees, and plants from
construction operations. Remove when no longer needed or at completion of Work.
2. Materials may be new or used, suitable for the intended purpose, but shall not violate
requirements of applicable codes and standards or regulatory agencies.
3. Barriers shall be of a neat and reasonable uniform appearance, structurally adequate for
the required purposes.
4. Maintain barriers in good repair and clean condition for adequate visibility. Relocate
barriers as required by progress of Work.
5. Repair damage caused by installation and restore area to original or better condition.
Clean the area.
3.03 SECURITY:
A. Provide security as required to look after the interests of the Contractor.
3.04 ENVIRONMENTAL CONTROLS:
A. Noise Control: Per State and Federal (OSHA) Standards.
B. Dust Control:
1. Provide positive methods and apply dust control materials to minimize raising dust from
construction operations; and to prevent airborne dust from dispersing into the
atmosphere.
2. Clean interior spaces prior to the start of finish painting and continue cleaning on an
as -needed basis until painting is finished.
3. Schedule operations so that dust and other contaminants resulting from cleaning process
will not fall on wet or newly -coated surfaces.
C. Water and Erosion Control:
Village of Mount Prospect 015700-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 015700 - TEMPORARY BARRIERS AND CONTROLS: continued
1. Provide methods to control surface water to prevent damage to the Project, the Site, or
adjoining properties.
2. Plan and execute construction and earthwork by methods to control surface drainage from
cuts and fills, and from borrow and waste disposal areas, to prevent erosion and
sedimentation.
a. Hold the areas of bare soil exposed at one time to a minimum.
b. Provide temporary control measures such as berms, dikes, and drains.
3. Control fill, grading, and ditching to direct surface drainage away from excavations, pits,
tunnels, and other construction areas; and to direct drainage to proper runoff.
4. Provide, operate, and maintain hydraulic equipment of adequate capacity to control
surface and groundwater.
5. Treat and dispose of surface runoff water in a manner to prevent flooding, erosion,
sedimentation, or other damage to any portion of the Site or to adjoining areas, and in a
manner acceptable to authorities having jurisdiction.
D. Debris Control and Clean -Up:
1. Keep the premises free at all times from accumulations of debris, waste materials, and
rubbish caused by construction operations and employees. Responsibilities shall
include:
a. Adequate trash receptacles about the Site, emptied promptly when filled.
b. Periodic cleanup to avoid hazards or interference with operations at the Site and to
maintain the Site in a reasonably neat condition.
C. The keeping of construction materials such as forms and scaffolding neatly stacked.
d. Immediate cleanup to protect the Work by removing splattered concrete, asphalt,
oil, paint, corrosive liquids, and cleaning solutions from walls, floors, and metal
surfaces before surfaces are marred.
2. Prohibit overloading of trucks to prevent spillages on access and haul routes. Provide
periodic inspection of traffic areas to enforce requirements.
3. Final cleanup is specified in SECTION 017800 - CONTRACT CLOSEOUT.
E. Pollution Control:
1. Provide methods, means, and facilities required to prevent contamination of soil, water,
or atmosphere by the discharge of hazardous or toxic substances from construction
operations.
2. Provide equipment and personnel, perform emergency measures required to contain any
spillages, and remove contaminated soils or liquids. Excavate and dispose of any
contaminated earth off -Site in approved locations, and replace with suitable compacted
fill and topsoil.
3. Take special measures to prevent harmful substances from entering public waters,
sanitary, or storm sewers.
3.05 ACCESS ROADS AND PARKING AREAS:
A. On -Site Roads and Parking Areas:
1. Locate roads, drives, walks, and parking facilities to provide access to construction
offices, mobilization, Work, storage areas, and other areas required for execution of the
Contract.
a. Consult with Engineer regarding any desired deviation therefrom.
b. Size of parking facilities shall be adequate to provide for needs of Contractor's
personnel, Resident Project Representatives, and visits to Site by Engineer and
Owner.
Village of Mount Prospect 015700-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 015700 - TEMPORARY BARRIERS AND CONTROLS: continued
2. Provide access for emergency vehicles. Maintain driveways a minimum of 15 feet wide
between and around combustible materials in storage and mobilization areas.
3. Maintain traffic areas free of excavated materials, construction equipment, snow, ice, and
debris.
4. Construct temporary bridges and culverts to span low areas and allow unimpeded
drainage.
5. Keep fire hydrants and water control valves free from obstruction and accessible for use.
6. Construction:
a. Clear areas required.
b. Fill, compact, and grade areas as necessary to provide suitable support for vehicular
traffic under anticipated loadings.
C. Provide for surface drainage of facilities and surrounding areas.
d. Maintain roads, walks, and parking areas in a sound, clean condition. Repair or
replace portions damaged during progress of Work.
7. Removal:
a. Completely remove temporary materials and construction when construction needs
can be met by use of permanent installation, unless construction is to be integrated
into permanent construction. Remove and dispose of compacted materials to depths
required by various conditions to be met in completed Work.
b. Restore areas to original, better, or specified condition at completion of Work.
B. Existing On -Site Roads and Parking Areas:
1. Designated existing on -Site streets and parking facilities may be used for construction
traffic.
a. Provide temporary additional roads as needed for required construction access.
b. Maintain existing construction, and restore to original, better, or specified condition
at completion of Work.
C. Do not allow heavy vehicles or construction equipment in parking areas.
3.06 TRAFFIC CONTROL AND USE OF ROADWAYS:
A. Traffic Control:
1. Provide, operate, and maintain equipment, services, and personnel, with traffic control
and protective devices, as required to expedite vehicular traffic flow on haul routes, at
Site entrances, on -Site access roads, and parking areas. This includes traffic signals and
signs, flagmen, flares, lights, barricades, and other devices or personnel as necessary to
adequately protect the public.
2. Remove temporary equipment and facilities when no longer required. Restore grounds to
original, better, or specified condition when no longer required.
3. Provide and maintain suitable detours or other temporary expedients if necessary.
4. Bridge over open trenches where necessary to maintain traffic.
5. Consult with governing authorities to establish public thoroughfares which will be used
as haul routes and Site access. All operations shall meet the approval of owners or
agencies having jurisdiction.
6. This work shall be done in accordance with Part IV of Illinois Department of
Transportation Reprint of the "Manual on Uniform Traffic Control Devices" published by
the Federal Highway Administration, the appropriate articles of Section 1084 of the
Standard Specifications and the Standard Specification for Traffic Control Devices
adopted April 1, 2013 by the Illinois Department of Transportation. All applicable state
standards for traffic control devices, lane closures and traffic control staging shall
conform to current IDOT standards at all times.
Village of Mount Prospect 015700-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 015700 - TEMPORARY BARRIERS AND CONTROLS: continued
a. When traffic is to be directed over a detour route, the Contractor shall furnish, erect,
maintain and remove all applicable traffic control devices and signing along the
detour route according to the details shown in the plans.
b. The governing factor in the execution and staging of work for this project is to
provide the motoring public, residents, and business owners with the safest possible
conditions along the roadway and in the construction zone. The Contractor shall so
arrange his operations as to keep the closing of any lane of the roadway to a
minimum.
C. All operations which require a reduction in the number of lanes of traffic shall
comply with the aforementioned standards including a flagman posted at each end
of the lane closure at all times. "stop" and 'slow" paddles shall be used to control
traffic. Flags will NOT be allowed as the sole means of traffic control. Minimum
lane widths shall be 10 feet. Single lane roads will not be allowed without flagmen,
and under no circumstances will a one lane condition remain overnight unless
approved by the Owner.
d. Type II barricades with working steady burn light units shall be used whenever the
change in pavement height exceeds 2 inches due to any construction activity and at
all butt joints. The Engineer reserves the right to stop any construction activity when
traffic control is neglected.
e. Traffic control devices include signs and their supports, signals, pavement
markings, barricades (with sandbags if necessary), channelization devices, warning
lights, arrow boards, flaggers, or any other device used for the purpose of guiding
traffic through or detouring around the construction zone.
f. The Contractor will be responsible for the proper location, installation, and
arrangement of all traffic control devices. Special attention shall be given to
advance warning signs during construction operations in order to keep lane
assignment consistent with barricade placement at all times/ The Contractor shall
cover or remove all traffic control devices which are inconsistent with detour or
lane assignment patterns during the transition from one construction stage to
another.
g. The Contractor shall ensure that all traffic control devices installed by him are
operational 24 hours a day, including Sundays and Holidays.
h. The Contractor shall be reachable on a 24 hour a day basis to receive notification of
any deficiencies regarding traffic control and protection and shall dispatch
personnel, materials, and equipment to correct any such deficiencies. The
Contractor shall respond to any call from the Owner concerning a request for
improving or correcting traffic control devices and begin making the requested
repairs within two hours from the time of notification.
i. When traveling in lanes open to public traffic, the Contractor's vehicles shall always
move with and not against the flow of traffic. These vehicles shall enter and leave
work areas in a manner which will not be hazardous to or interfere with traffic and
shall not park or stop except within designated work areas. Those vehicles
belonging to the Contractor or his employees shall remain on public property area
only and shall not pull into, park, or block any access to private property.
j. Any drop off greater than three inches, but less than six inches, within eight feet of
the pavement edge shall be protected by Type I or II barricades equipped with
mono -directional steady burn lights at 100 -foot center to center spacing. If the drop
off within eight feet of the pavement edge exceeds six inches, the barricades
mentioned above shall be placed at 50 -foot center to center spacing. Barricades that
Village of Mount Prospect 015700-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 015700 - TEMPORARY BARRIERS AND CONTROLS: continued
must be placed in excavated areas shall have leg extensions installed such that the
top of the barricade is in compliance with the height requirement of Standard
702001. Vertical panels or other delineating devices may be substituted for Type I
or Type II barricades with the approval of the Engineer.
B. Maintenance of Roadways:
1. Repair roads, walkways, and other traffic areas damaged by operations. Keep traffic
areas as free as possible of excavated materials and maintain in a manner to eliminate
dust, mud, and hazardous conditions.
2. All operations and repairs shall meet the approval of owners or agencies having
jurisdiction.
END OF SECTION 015700
Village of Mount Prospect 015700-6 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 016000 - EOUIPMENT AND MATERIALS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes administrative and procedural requirements governing Contractor's
selection of products for use in the Project.
B. Related Sections: The following Sections contain requirements that relate to this Section:
1. For the applicability of industry standards to products specified: DIVISIONS 32.
2. For submittal of Contractor's construction progress schedule and the Submittal schedule:
SECTIONS 013200 and 013300.
3. For handling requests for substitutions made after award of the Contract: SECTION
012500.
1.02 DEFINITIONS:
A. Definitions used in this Article are not intended to change the meaning of other terms used in
these Contract Documents, such as "specialties," "systems," "structures," "finishes,"
"accessories," and similar terms. Such terms are self-explanatory and have well-recognized
meanings in the construction industry.
1. "Products" are items purchased for incorporation in the Work, whether purchased for the
Project or taken from previously purchased stock. The term "product" includes the terms
"Material," "Equipment," "system," and terms of similar intent.
a. "Named Products" are items identified by the manufacturer's product name,
including make or model number or other designation, shown or listed in the
manufacturer's published product literature that is current as of the date of the
Contract Documents.
b. "Foreign Products," as distinguished from "domestic products," are items
substantially manufactured (50% or more of value) outside the United States and its
possessions. Products produced or supplied by entities substantially owned (more
than 50%) by persons who are not citizens of, nor living within, the United States
and its possessions are also considered to be foreign products.
2. "Materials" are products substantially shaped, cut, worked, mixed, finished, refined or
otherwise fabricated, processed, or installed to form a part of the Work.
3. "Equipment" is a product with operational or nonoperational parts, whether motorized, or
manually operated, that may require service connections, such as wiring or piping.
1.03 SUBMITTALS:
A. Submittal of preliminary procurement schedule is specified in SECTION 013200 -
CONSTRUCTION PROGRESS SCHEDULES AND REPORTS.
B. Submittals for products are specified in SECTION 013 3 00.
1.04 QUALITY ASSURANCE:
A. Source Limitations: To the fullest extent possible, provide products of the same kind from a
single source.
1. When specified products are available only from sources that do not, or cannot, produce a
quantity adequate to complete Project requirements in a timely manner, consult with
Engineer to determine the most important product qualities before proceeding. Qualities
may include attributes, such as visual appearance, strength, durability, or compatibility.
When a determination has been made, select products from sources producing products
that possess these qualities, to the fullest extent possible.
Village of Mount Prospect 016000-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 016000 - EQUIPMENT AND MATERIALS: continued
B. Compatibility of Options: When the Contractor is given the option of selecting between two or
more products for use on the Project, the product selected shall be compatible with products
previously selected, even if previously selected products were also options.
1. Each prime contractor is responsible for providing products and construction methods
that are compatible with products and construction methods of other prime or separate
contractors.
2. If a dispute arises between prime contractors over concurrently selectable, but
incompatible products, Engineer will determine which products shall be retained and
which are incompatible and must be replaced.
C. Foreign Product Limitations: Except under one or more of the following conditions, provide
domestic products, not foreign products, for inclusion in the Work:
1. No available domestic product complies with the Contract Documents.
2. Domestic products that comply with the Contract Documents are available only at prices
or terms substantially higher than foreign products that comply with the Contract
Documents.
D. Nameplates: Along with required labels and operating data, manufacturer or producer's
nameplates, imprints, or trademarks may be placed on surfaces exposed to view.
1. Labels: Locate required product labels and stamps on concealed surfaces or, where
required for observation after installation, on accessible surfaces that are not conspicuous.
2. Equipment Nameplates: Provide a permanent nameplate on each item of service -
connected or power -operated Equipment. Locate on an easily accessible surface that is
inconspicuous in occupied spaces. The nameplate shall contain the following
information and other essential operating data:
a. Name of product and manufacturer including address (and telephone number).
b. Model and serial number.
C. Capacity.
d. Speed.
e. Ratings.
E. Electronic Equipment Compliance:
1. Contractor warrants that all equipment, devices, items, systems, software, hardware, or
firmware provided shall properly, appropriately, and consistently function and accurately
process date and time data (including without limitation: calculating, comparing, and
sequencing). This warranty supercedes anything in the Specifications or other Contract
Documents which might be construed inconsistently. This warranty is applicable
whether the equipment, device, item, system, software, hardware, or firmware is
specified with or without reference to a manufacturer's name, make, or model number.
1.05 TRANSPORTATION AND SHIPMENT:
A. Shipment Preparation:
1. Contractor shall require manufacturers and Suppliers to prepare products for shipment in
a manner to facilitate unloading and handling, and to protect against damage,
deterioration, or unnecessary exposure to the elements in transit and storage. Provisions
for protection shall include the following:
a. Crates or other suitable packaging materials.
b. Covers and other means to prevent corrosion, moisture damage, mechanical injury,
and accumulation of dirt in motors, electrical equipment, and machinery.
C. Suitable rust -preventive compound on exposed machined surfaces and unpainted
iron and steel.
d. Grease packing or oil lubrication in all bearings and similar items.
Village of Mount Prospect 016000-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 016000 - EQUIPMENT AND MATERIALS: continued
B. Marking: Each product item shall be tagged or marked as identified in the delivery schedule or
on Submittals. Complete packing lists and bills of material shall be included with each
shipment. Each piece of every item need not be marked separately, provided that all pieces of
each item are packed or bundled together and the packages or bundles are properly tagged or
marked.
1.06 PRODUCT DELIVERY, STORAGE, AND HANDLING:
A. Deliver, store, and handle products according to the manufacturer's recommendations, using
means and methods that will prevent damage, deterioration, and loss, including theft.
1. Schedule delivery to minimize long-term storage at the Site and to prevent overcrowding
of construction spaces. Allow ample time to avoid delay of the Work.
2. Coordinate delivery with installation time to assure minimum holding time for items that
are flammable, hazardous, easily damaged, or sensitive to deterioration, theft, and other
losses.
3. Deliver products to the Site in an undamaged condition in the manufacturer's original
sealed container or other packaging system, complete with labels and instructions for
handling, storing, unpacking, protecting, and installing.
4. Inspect products upon delivery to ensure compliance with the Contract Documents and to
ensure that products are undamaged and properly protected. Inspect shipment to assure:
a. Product complies with requirements of Contract Documents and reviewed
Submittals.
b. Quantities are correct.
C. Containers and packages are intact and labels are legible.
d. Products are properly protected and undamaged.
5. Store products at the Site in a manner that will facilitate inspection and measurement of
quantity or counting of units. Mark deliveries of component parts of Equipment to
identify the Equipment, to permit easy accumulation of parts, and to facilitate inspection
and measurement of quantity or counting of units.
6. Store heavy Materials away from the Project structure in a manner that will not endanger
the supporting construction.
7. Store products subject to damage by the elements above ground, under cover in a
weathertight enclosure, and with ventilation adequate to prevent condensation. Maintain
temperature and humidity within range required by manufacturer's instructions.
8. Protect motors, electrical Equipment, plumbing fixtures, and machinery of all kinds
against corrosion, moisture deteriorations, mechanical injury, and accumulation of dirt or
other foreign matter.
9. Protect exposed machined surfaces and unpainted iron and steel as necessary with
suitable rust -preventive compounds.
10. Protect bearings and similar items with grease packing or oil lubrication.
11. Handle and store steel plate, sheet metal, and similar items in a manner to prevent
deformation.
12. For storage of pipe and other products on easements and rights-of-way in residential and
commercial areas, do not exceed the minimum required by scheduled laying operations,
and conform to all requirements of public authorities. Store or place pipe along roads, set
back from shoulder or curb, and at an angle tending to deflect vehicles if struck. Place or
block pipe to preclude its accidental movement.
B. Handling:
1. Provide equipment and personnel necessary to unload and handle products, by methods
to prevent damage or soiling to products, or packaging.
Village of Mount Prospect 016000-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 016000 - EQUIPMENT AND MATERIALS: continued
2. Handle by methods to prevent bending or overstressing. Where lifting points are
designated, lift components only at those points.
3. Provide additional protection to surrounding surfaces as necessary to prevent damage.
C. Maintenance of Storage:
1. Inspect stored products on a scheduled basis.
2. Verify that storage facilities comply with manufacturer's product storage requirements,
including environmental conditions continually maintained.
3. Verify that surfaces of products exposed to elements are not adversely affected; that any
weathering of finishes is acceptable under requirements of Contract Documents.
4. For mechanical and electrical Equipment in long-term storage, provide manufacturer's
service instructions to accompany each item, with notice of enclosed instructions on
exterior of package. Service Equipment on a regularly scheduled basis.
D. Protection After Installation: Provide substantial coverings as necessary to protect installed
products from damage from subsequent construction operations. Remove coverings when no
longer needed or as specified.
1.07 EXISTING EQUIPMENT AND MATERIALS:
A. Products to be Reused:
1. For Equipment and Materials specifically indicated or specified to be reused in the Work,
use special care in removal, handling, storage, and reinstallation to assure proper function
in the completed Work. Arrange for transportation, storage, and handling of products
which require off -Site storage, restoration, or renovation and pay all costs for such
Work. Contractor may at its option, furnish and install new items in lieu of those
specified to be reused.
B. Products Not to be Reused:
1. Equipment and Materials designated to be removed but not reused or delivered to Owner,
shall become the property of the Contractor and shall be removed from the Site.
PART 2 - PRODUCTS
2.01 PRODUCT SELECTION:
A. General Product Requirements: Provide products that comply with the Contract Documents,
that are undamaged and, unless otherwise specified or indicated, new at the time of installation.
1. Provide products complete with accessories, trim, finish, safety guards, and other devices
and details needed for a complete installation and the intended use and effect.
2. Where available, provide standard products of types that have been produced and used
successfully in similar situations on other projects.
3. Continued Availability: Where, because of the nature of its application, Owner is likely
to need replacement parts or additional amounts of a product at a later date, either for
maintenance and repair or replacement, provide standard products for which the
manufacturer has published assurances that the products and its parts are likely to be
available to Owner at a later date.
4. Conform to applicable Specifications, codes, standards, and regulatory agencies.
5. Comply with size, make, type, and quality specified, or as specifically approved in
writing by Engineer.
6. Manufactured and Fabricated Products:
a. Design, fabricate, and assemble in accordance with the best engineering and shop
practices.
Village of Mount Prospect 016000-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 016000 - EQUIPMENT AND MATERIALS: continued
b. Manufacture like parts of duplicate units to standard sizes and gages, to be
interchangeable.
C. Equipment and Materials shall be suitable for service conditions intended.
d. Equipment capacities, sizes, and dimensions indicated or specified shall be adhered
to unless variations are specifically approved in writing by Engineer.
e. Provide labels and nameplates where required by regulatory agencies or to state
identification and essential operating data.
7. Do not use products for any purpose other than that for which designed.
8. To the fullest extent possible, provide products of the same kind from a single source.
PART 3 - EXECUTION
3.01 INSTALLATION OF PRODUCTS:
A. Comply with manufacturer's instructions and recommendations for installation of products in
the applications indicated. Anchor each product securely in place except as required for proper
movement and performance, and accurately located and aligned with other Work.
1. Obtain and distribute copies of manufacturer's printed instructions and recommendations
if not a part of Submittals, containers, or packaging to parties involved in the installation,
including a copy to Engineer and Resident Project Representative.
2. Maintain one complete set of instructions at the Site during installation and until
completion.
3. Handle, install, connect, clean, condition, and adjust products in accordance with such
instructions and in conformance with specified requirements. Should job conditions or
specified requirements conflict with manufacturer's instructions, consult with Engineer
for further instructions.
B. Clean exposed surfaces and protect as necessary to ensure freedom from damage and
deterioration at time of Substantial Completion.
END OF SECTION 016000
Village of Mount Prospect 016000-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 017800 - CONTRACT CLOSEOUT
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes administrative and procedural requirements for Contract closeout
including, but not limited to, the following:
1. Inspection procedures.
2. Project record document submittal.
3. Instruction book and operating manual submittal.
4. Submittal of warranties.
5. Final cleaning.
B. Closeout requirements for specific construction activities are included in the appropriate
Sections of the Specifications.
C. Related Work Specified Elsewhere:
1. Prerequisites to Substantial Completion and Final Acceptance: GENERAL
CONDITIONS.
2. Submittals: SECTION 013 3 00.
3. Warranties: SECTION 017836.
1.02 SUBSTANTIAL COMPLETION:
A. Preliminary Procedures: Before requesting inspection for certification of Substantial
Completion, complete the following. List exceptions in the request.
1. In the Application for Payment that coincides with, or first follows, the date Substantial
Completion is claimed, show 100% completion for the portion of the Work claimed as
Substantially Complete.
a. Include supporting documentation for completion as indicated in these Contract
Documents and a statement showing an accounting of changes to the Contract Price.
b. If 100% completion cannot be shown, include a list of incomplete items, the value
of incomplete Work, and reasons the Work is not complete.
2. Advise Owner of pending insurance changeover requirements.
3. Submit specific warranties, workmanship Bonds, maintenance agreements, final
certifications, and similar documents.
4. Obtain and submit releases enabling Owner unrestricted use of the Work and access to
services and utilities. Include occupancy permits, operating certificates, and similar
releases.
5. Submit record drawings, instruction books and operating manuals, final project
photographs, damage or settlement surveys, property surveys, and similar final record
information.
6. Complete final cleanup requirements.
B. Inspection Procedures: On receipt of a request for inspection, Engineer will either proceed
with inspection or advise Contractor of unfilled requirements. Engineer will prepare the
Certificate of Substantial Completion following inspection or advise Contractor of construction
that must be completed or corrected before the certificate will be issued.
1. Engineer will repeat inspection when requested and assured by Contractor that the Work
is Substantially Complete.
2. Results of the completed inspection will form the basis of requirements for final
acceptance.
Village of Mount Prospect 017800-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 017800 - CONTRACT CLOSEOUT: continued
1.03 FINAL ACCEPTANCE:
A. Preliminary Procedures: Before requesting final inspection for certification of final acceptance
and final payment, complete the following. List exceptions in the request.
1. Submit the final payment request with releases and supporting documentation not
previously submitted and accepted. Include insurance certificates for products and
completed operations where required.
2. Submit an updated final statement, accounting for final additional changes to the Contract
Price.
3. Submit a certified copy of Engineer's final inspection list of items to be completed or
corrected, endorsed and dated by Engineer. The certified copy of the list shall state that
each item has been completed or otherwise resolved for acceptance and shall be endorsed
and dated by Engineer.
4. Submit consent of surety to final payment.
5. Submit evidence of final, continuing insurance coverage complying with insurance
requirements.
6. Submit a final liquidated damages settlement statement.
B. Reinspection Procedure: Engineer will reinspect the Work upon receipt of notice that the
Work, including inspection list items from earlier inspections, has been completed, except for
items whose completion is delayed under circumstances acceptable to Engineer.
1. Upon completion of reinspection, Engineer will prepare a certificate of final acceptance.
If the Work is incomplete, Engineer will advise Contractor of Work that is incomplete or
of obligations that have not been fulfilled but are required for final acceptance.
2. If necessary, reinspection will be repeated.
1.04 RECORD DOCUMENT SUBMITTALS:
A. General: Do not use record documents for construction purposes. Protect record documents
from deterioration and loss in a secure, fire-resistant location. Provide access to record
documents for Engineer's reference during normal working hours.
B. Record Drawings: Maintain a clean, undamaged set of blue or black line white -prints of
Contract Drawings and Shop Drawings. Mark the set to show the actual installation where the
installation varies substantially from the Work as originally shown. Mark which drawing is
most capable of showing conditions fully and accurately. Where Shop Drawings are used,
record a cross-reference at the corresponding location on the Contract Drawings. Give
particular attention to concealed elements that would be difficult to measure and record at a
later date.
1. Record information concurrently with construction progress.
2. Mark record sets with red erasable pencil. Use other colors to distinguish between
variations in separate categories of the Work. Mark each document "PROJECT
RECORD" in neat, large, printed letters.
3. Mark new information that is important to Owner but was not shown on Contract
Drawings or Shop Drawings.
4. Note related Change Order numbers where applicable.
5. Organize record drawing sheets into manageable sets. Bind sets with durable -paper
cover sheets; print suitable titles, dates, and other identification on the cover of each set.
6. Upon completion of the Work, submit record drawings to Engineer for Owner's records.
7. Include the following:
a. Depths of various elements of foundation in relation to finish first floor datum.
b. Horizontal and vertical locations of underground utilities and appurtenances,
referenced to permanent surface improvements.
Village of Mount Prospect 017800-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 017800 - CONTRACT CLOSEOUT: continued
C. Location of internal utilities and appurtenances concealed in the construction,
referenced to visible and accessible features of construction.
d. Where Submittals are used for mark-up, record a cross-reference at corresponding
location on Drawings.
e. Field changes of dimension and detail.
f. Changes made by Change Order or other Modifications.
g. Details not on original Contract Drawings.
C. Record Specifications: Maintain one complete copy of the Project Manual including Addenda.
Include with the Project Manual one copy of other written construction documents, such as
Change Orders and Modifications issued in printed form during construction.
1. Mark these documents to show substantial variations in actual Work performed in
comparison with the text of the Specifications and modifications.
2. Give particular attention to substitutions and selection of options and information on
concealed construction that cannot otherwise be readily discerned later by direct
observation.
3. Note related record drawing information and product data.
4. Upon completion of the Work, submit record Specifications to Engineer for Owner's
records.
5. Include the following:
a. Manufacturer, trade name, catalog number, and Supplier of each product and item
of Equipment actually installed, particularly optional and substitute items.
b. Changes made by Addendum, Change Order, or other Modifications.
C. Related Submittals.
D. Record Product Data: Maintain one copy of each product data Submittal. Note related Change
Orders and markup of record drawings and specifications.
1. Mark these documents to show significant variations in actual Work performed in
comparison with information submitted. Include variations in products delivered to the
Site and from the manufacturer's installation instructions and recommendations.
2. Give particular attention to concealed products and portions of the Work that cannot
otherwise be readily discerned later by direct observation.
3. Upon completion of markup, submit complete set of record product data to Engineer for
Owner's records.
E. Record Samples Submitted: Immediately prior to Substantial Completion, Contractor shall
meet with Engineer and Owner's personnel at the Project Site to determine which Samples are
to be transmitted to Owner for record purposes. Comply with Owner's instructions regarding
packaging, identification, and delivery to Owner.
F. Miscellaneous Record Submittals: Refer to other Specification Sections for requirements of
miscellaneous record keeping and Submittals in connection with actual performance of the
Work. Immediately prior to the date or dates of Substantial Completion, complete
miscellaneous records, and place in good order. Identify miscellaneous records properly and
bind or tile, ready for continued use and reference. Submit to Engineer for Owner's records.
G. Instruction Books and Operating Manuals: Organize operation and maintenance data into
suitable sets of manageable size as specified in SECTION 013300.
1.05 SPARE PARTS:
A. Products Required:
1. Provide to Owner the quantities of products, spare parts, maintenance tools, and
maintenance materials specified in individual Sections, in addition to that required for
completion of Work.
Village of Mount Prospect 017800-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 017800 - CONTRACT CLOSEOUT: continued
2. Products shall be identical to those installed in the Work. Include quantities required
from Supplier or manufacturer of original purchase to avoid variations in manufacture.
B. Storage, Maintenance:
1. Coordinate with Owner. Deliver and unload spare products to Owner at Project Site and
obtain receipt prior to final payment.
2. For portions of the Work accepted and occupied by Owner prior to Substantial
Completion, deliver the applicable spare products to Owner at time of acceptance.
Obtain receipt.
3. Maintain spare products in original containers with labels intact and legible, until
delivery to Owner.
PART 2 - PRODUCTS (Not Applicable)
P A R T I- F.XF.CT MON
3.01 FINAL CLEANING:
A. General: Contractor shall keep the Site premises free from accumulations of waste materials,
rubbish, and other debris resulting from the Work. Regular Site cleaning is included in
SECTION 015700.
B. Cleaning: Employ experienced workers or professional cleaners for final cleaning. Clean each
surface or unit to the condition expected in a normal, commercial building cleaning and
maintenance program. Comply with manufacturer's instructions.
1. Complete the following cleaning operations before requesting inspection for certification
of Substantial Completion.
a. Remove labels that are not permanent labels.
b. Remove debris and surface dirt from limited -access spaces including roofs,
plenums, shafts, trenches, equipment vaults, manholes, and similar spaces.
C. Clean the Site, including landscape development areas, of rubbish, litter, and other
foreign substances. Sweep paved areas broom clean; remove stains, spills, and
other foreign deposits. Rake grounds that are neither paved nor planted to a smooth,
even -textured surface.
2. Remove temporary structures, tools, equipment, supplies, and surplus materials.
3. Remove temporary protection devices and facilities which were installed to protect
previously completed Work.
4. Special Cleaning: Cleaning for specific units of Work is specified in applicable Sections
of Specifications.
C. Removal of Protection: Remove temporary protection and facilities installed for protection of
the Work during construction.
D. Compliance: Comply with regulations of authorities having jurisdiction and safety standards
for cleaning. Do not burn waste materials. Do not bury debris or excess materials on the
Owner's property. Do not discharge volatile, harmful, or dangerous materials into drainage
systems. Remove waste materials from the Site and dispose of lawfully.
1. Extra materials of value remaining after completion of associated Work become Owner's
property. Dispose of these materials as directed by Owner.
E. Repairs:
1. Repair damaged protective coated surfaces.
2. Repair roads, walks, fences, and other items damaged or deteriorated because of
construction operations.
3. Restore all ground areas affected by construction operations.
END OF SECTION 017800
Village of Mount Prospect 017800-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 017836 - WARRANTIES
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes administrative and procedural requirements for warranties required by
the Contract Documents, including manufacturer's standard warranties on products and special
warranties.
1. Refer to the GENERAL CONDITIONS for terms of the Contractor's period for
correction of the Work.
B. Related Sections: The following Sections contain requirements that relate to this Section:
1. Procedures for submitting warranties: SECTION 013300.
2. Contract closeout procedures: SECTION 017800.
3. Certifications and other commitments and agreements for continuing services to Owner:
Specified throughout the Contract Documents.
C. Disclaimers and Limitations: Manufacturer's disclaimers and limitations on product warranties
do not relieve Contractor of the warranty on the Work that incorporates the products.
Manufacturer's disclaimers and limitations on product warranties do not relieve Suppliers,
manufacturers, and Subcontractors required to countersign special warranties with Contractor.
1.02 WARRANTY REQUIREMENTS:
A. Related Damages and Losses: When correcting failed or damaged warranted construction,
remove and replace construction that has been damaged as a result of such failure or that must
be removed and replaced to provide access for correction of warranted construction.
B. Reinstatement of Warranty: When Work covered by a warranty has failed and been corrected
by replacement or rebuilding, reinstate the warranty by written endorsement. The reinstated
warranty shall be equal to the original warranty with an equitable adjustment for depreciation.
C. Replacement Cost: Upon determination that Work covered by a warranty has failed, replace or
rebuild the Work to an acceptable condition complying with requirements of the Contract
Documents. Contractor is responsible for the cost of replacing or rebuilding defective Work
regardless of whether Owner has benefited from use of the Work through a portion of its
anticipated useful service life.
D. Owner's Recourse: Expressed warranties made to Owner are in addition to implied warranties
and shall not limit the duties, obligations, rights, and remedies otherwise available under the
Law. Expressed warranty periods shall not be interpreted as limitations on the time in which
Owner can enforce such other duties, obligations, rights, or remedies.
1. Rejection of Warranties: Owner reserves the right to reject warranties and to limit
selection to products with warranties not in conflict with requirements of the Contract
Documents.
E. Where the Contract Documents require a special warranty, or similar commitment on the Work
or part of the Work, Owner reserves the right to refuse to accept the Work, until Contractor
presents evidence that entities required to countersign such commitments are willing to do so.
1.03 SUBMITTALS:
A. Submit written warranties to Engineer prior to the date certified for Substantial Completion. If
the Certificate of Substantial Completion designates a commencement date for warranties other
than the Date of Substantial Completion for the Work, or a designated portion of the Work,
submit written warranties upon request of Engineer.
1. When a designated portion of the Work is completed and occupied or used by Owner, by
separate agreement with Contractor during the construction period, submit properly
Village of Mount Prospect 017836-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 017836 - WARRANTIES: Continued
executed warranties to Engineer within 15 days of completion of that designated portion
of the Work.
B. When the Contract Documents require Contractor, or Contractor and a Subcontractor, Supplier,
or manufacturer to execute a special warranty, prepare a written document that contains
appropriate terms and identification, ready for execution by required parties. Submit a draft to
Owner, through Engineer, for approval prior to final execution.
C. Bind warranties and bonds in heavy-duty, commercial -quality, durable three-ring, vinyl -
covered loose-leaf binders, thickness as necessary to accommodate contents, and sized to
receive 8 -1/2 -by- I l -inch paper.
1. Provide heavy paper dividers with celluloid covered tabs for each separate warranty.
Mark the tab to identify the product or installation. Provide a typed description of the
product or installation, including the name of the product, and the name, address, and
telephone number of the installer.
2. Identify each binder on the front and spine with the typed or printed title
"WARRANTIES," and as required by SECTION 013300.
3. When warranted construction requires operation and maintenance manuals, provide
additional copies of each required warranty, as necessary, for inclusion in each required
manual.
PART 2 - PRODUCTS (Not Applicable)
PART 3 - EXECUTION (Not Applicable)
END OF SECTION 017836
Village of Mount Prospect 017836-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
DIVISION 5 - METALS
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS
PART 1 -GENERAL
1.01 SUMMARY:
A. The completed Work for the Tank SE one -million gallon tank, except as otherwise specified,
shall include:
1. Miscellaneous chipping and Binding
2. Removal and replacement of the existing wet interior ladder with a fall prevention device.
3. Removal and replacement of the existing exterior ladder with a fall prevention device.
4. Installation of shell manhole davits (2)
5. Installation of aself-closing gate on the existing roof safety railing per OSHA
requirements.
6. Relocation of the existing roof safety railing toe bar
7. Installation of mud guards (2): Install a removable mud guard on the inlet/outlet pipe and
the drain pipe.
8. Partial Beam Replacement (Alternative Bid Item 1.B)
9. Complete Beam Replacement (Alternative Bid Item 1.C)
B. New manways and ladders shall be designed and installed per the project specifications. The
Contractor is to provide all materials, design, labor, supervision, and equipment to install this
work in conformance with the project requirements provided as part of this Section and in
accordance with specified and applicable requirements of AWWA D100.
C. Related Work Specified Elsewhere:
1. Protective Coatings: SECTION 099000.
1.02 REFERENCES:
A. Applicable Standards:
1. American Institute of Steel Construction (RISC):
a. Manual of Steel Construction.
b. Quality Criteria and Inspection Standards.
2. American Water Works Association (AWWA)
a. D100-11 —Standard for Welded Carbon Steel Tanks for Water Storage
b. D102-03 —Standard for Painting Steel Water Storage Tanks
C. C652-02 —Standard for Disinfection of Water Storage Facilities
3. American Welding Society (AWS):
a. A4.3 -Standard Methods for Determination of the Diffusible Hydrogen Content of
Martensitic, Bainitic, and Ferritic Steel Weld Metal Produced by Arc Welding.
b. A5.1 -Specification for Carbon Steel Electrodes for Shielded Metal Arc Welding.
C. A5.4 -Specification for Stainless Steel Electrodes for Shielded Metal Arc Welding.
d. A5.5 -Specification for Low -Alloy Steel Electrodes for Shielded Metal Arc
Welding.
e. B4.0 -Standard Methods for Mechanical Testing of Welds.
£ B5.1 -Specification for the Qualification of Welding Inspectors.
g. C4.1 -Oxygen Cutting Surface Roughness Gauge and Chart for Criteria Describing
Oxygen Cut Surfaces.
h. C5.4 -Recommended Practices for Stud Welding.
i. D1.1 -Structural Welding Code -Steel.
j . D1.6 -Structural Welding Code -Stainless Steel.
Village of Mount Prospect 051000-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
k. QC 1 - Standard Qualification and Certification of Welding Inspectors.
4. American National Standards Institute (ANSI):
a. Z49.1 - Safety in Welding and Cutting.
5. American Society of Civil Engineers (ASCE):
a. 7 - Minimum Design Loads for Buildings and Other Structures.
6. American Society for Testing and Materials (ASTM):
a. Al - Carbon Steel Tee Rails.
b. A6 - Standard Specification for General Requirements for Rolled Structural Steel
Bars, Plates, Shapes, and Sheet Piling.
C. A36 - Carbon Structural Steel.
d. A53 - Pipe, Steel, Black and Hot -Dipped, Zinc -Coated Welded and Seamless.
e. A106 - Seamless Carbon Steel Pipe for High -Temperature Service.
f. A108 - Steel Bar, Carbon and Alloy, Cold -Finished. i
g. A123 - Zinc (Hot -Dip Galvanized) Coatings on Iron and Steel Products.
h. A 143 - Safeguarding Against Embrittlement of Hot -Dip Galvanized Structural Steel
Products and Procedure for Detecting Embrittlement
i. A 15 3 - Zinc Coating (Hot -Dip) on Iron and Steel Hardware — AASHTO No.:
M232.
j. A 167 - Stainless and Heat -Resisting Chromium -Nickel Steel Plate, Sheet, and
Strip.
k. A193 - Alloy -Steel and Stainless Steel Bolting Materials for High Temperature or
High Pressure Service and Other Special Purpose Applications.
1. A240 — Chromium and Chromium -Nickel Stainless Steel Plate, Sheet, and Strip for
Pressure Vessels and for General Applications
m. A264 - Stainless Chromium -Nickel Steel -Clad Plate,.
n. A307 - Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength.
o. A312 — Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel
Pipes.
p. A325 -Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength.
q. A384 - Safeguarding Against Warpage and Distortion During Hot -Dip Galvanizing
of Steel Assemblies
r. A385 - Providing High -Quality Zinc Coatings (Hot -Dip)
S. A449 - Hex Cap Screws, Bolts and Studs, Steel, Heat Treated, 120/105/90 ksi
Minimum Tensile Strength, General Use.
t. A490 - Structural Bolts, Alloy Steel, Heat Treated, 150 ksi Minimum Tensile
Strength.
U. A500 - Cold -Formed Welded and Seamless Carbon Steel Structural Tubing in
Rounds and Shapes.
V. A563 - Carbon and Alloy Steel Nuts.
w. A572 - High Strength Low -Alloy Columbium -Vanadium Structural Steel.
X. A588 - High -Strength Low -Alloy Structural Steel, up to 50 ksi [345 MPa]
Minimum Yield Point, with Atmospheric Corrosion Resistance - AASHTO No.: M
222.
y. A673 - Sampling Procedure for Impact Testing of Structural Steel.
Z. A780 - Repair of Damaged and Uncoated Areas of Hot -Dip Galvanized Coatings.
aa. A786 - Hot -Rolled Carbon Low -Alloy, High -Strength Low -Alloy, and Alloy Steel
Floor Plates.
bb. A992 - Structural Steel Shapes.
Village of Mount Prospect 051000-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
cc. A 1011 /A 1011 M - Steel, Sheet and Strip, Hot -Rolled, Carbon, Structural, High -
Strength Low -Alloy, High -Strength Low -Alloy with Improved Formability, and
Ultra -High Strength.
dd. B695 - Coatings of Zinc Mechanically Deposited on Iron and Steel.
ee. C 1107 — Packaged, Dry Hydraulic Cement Grout (Nonshrink).
ff. F436 - Hardened Steel Washers.
gg. F593 - Stainless Steel Bolts, Hex Cap Screws, and Studs.
hh. F594 - Stainless Steel Nuts.
ii. F959 - Compressible -Washer -Type Direct Tension Indicator for Use with Structural
Fasteners.
jj. F 1554 - Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength.
kk. F2329 - Zinc Coating, Hot -Dip, Requirements for Application to Carbon and Alloy
Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners.
7. Manufacturers Standardization Society of the Value and Fittings Industry (MSS):
a. SP -58 - Pipe Hangers and Supports.
8. The National Association of Architectural Metal Manufacturers (NAAMM):
a. MBG 531 - Metal Bar Grating Manual.
b. MBG 532 - Heavy Duty Metal Bar Grating Manual.
C. MBG 533 - Welding Specifications for Fabrication of Steel, Aluminum and
Stainless Steel Bar Grating.
9. Research Council on Structural Connections (RCSQ:
a. Specification for Structural Joints Using High -Strength Bolts.
10. Society for Protective Coatings (SSPC):
a. SP 1 - Solvent Cleaning.
b. SP3 - Power Tool Cleaning.
C. SP5 - White Metal Blast Cleaning.
d. SP6 - Commercial Blast Cleaning.
e. SP 10 - Near -White Blast Cleaning.
f. SP 11 - Power Tool Cleaning to Bare Metal.
11. Occupational Safety and Health Administration (OSHA) - All applicable OSHA
regulations, including, but not limited to 29 CFR Part 1910 and Part 1926 Subpart R -
Steel Erection.
12. Uniform Building Code (UBC).
1.03 SUBMITTALS:
A. Submittals:
1. Submit as specified in DIVISION 1.
2. Includes, but not limited to, the following:
a. General arrangement and outline information.
b. Foundation design information as specified in DIVISION 1.
C. Erection drawings for all work.
d. Bolt and load indicator details and manufacturer's instructions.
e. Welder qualifications.
f. Welding inspector qualifications.
g. Welding procedure qualifications for both shop and field welds.
h. Painting Manufacturer's product data sheets and application instructions.
i. Name and experience record of field painting subcontractor.
3. Design/Shop Drawings:
Village of Mount Prospect 051000-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
a. Shop drawings of new components shall be designed by and under the stamp and
signature of a professional engineer experienced in the design of tanks and
attachments and registered in the State of Illinois.
b. Prepare and submit a "tank design data package" under the seal of a State of Illinois
registered professional structural engineer. Packages shall include design and
construction criteria and related calculations, derivations, safety factors, metallurgy,
allowable stresses, thickness, design procedures and assumptions, if any, related to
the proposed vessel, and new components in accordance with applicable standards
and codes.
C. Fabrication/erection shop drawings shall include, but not be limited to the
following:
(1) Plan and elevation views, sections, parts, etc. showing materials, dimensions
and details required for construction, installation, etc.
(2) Selected views as required to completely describe materials, construction,
connections, accessories, appurtenances and show required connections and
dimensions, including maps for welders and radiograph technicians.
B. Mill Tests:
1. Perform for each melt of material used in the fabrication.
2. Furnish two copies of each certified mill test to Engineer upon request.
1.04 OUALITY ASSURANCE:
A. Welder Qualifications:
1. Welders employed for welding and cutting work shall be qualified and certified per
requirements of AWWA D-100, ASME Section IX, or the American Welding, Society D
1.1, by a qualified independent certification source, unless otherwise approved by the
Consulting Engineer. Failure to comply with this requirement automatically obligates the
Contractor to x-ray examine, at a minimum, all welds performed by non-compliant
personnel, at no additional cost to the Owner.
2. Welders shall be previously qualified by passing the tests prescribed in the AWS
Standard Qualification Procedure, or by passing such other tests as the Engineer may
accept.
3. Welders shall have been tested within the past twelve months, and their qualification
shall be considered as remaining in effect unless the welder is not engaged in a given
process of welding for a period exceeding six months.
4. Submit two certified copies of the qualification records to Engineer as evidence of
qualification to the above-mentioned code.
5. Tank repairs shall be performed by a contractor principally engaged in the erection and
repair of water storage tanks.
B. Inspection: Material or workmanship will be subject to inspection in the shop and field.
1.05 DELIVERY, STORAGE AND HANDLING:
A. Handle and store all steel and appurtenances as specified in DIVISION 1.
B. All steel and its coatings shall be protected from damage caused by handling, storage, and
shipping.
C. Store all steel and appurtenances blocked -up off the ground and in orderly stacks.
D. Protect all items with shop applied protective coatings from corrosion. Store in an
environment and manner consistent with type of coating.
PART 2 - PRODUCTS
Village of Mount Prospect 051000-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
2.01 GENERAL:
A. Steel: Conform to ASTM A36, as designated in AISC Manual, Part 1, unless otherwise
indicated or specified.
B. Connection Bolts, Nuts, and Washers:
1. Conform to ASTM A325, unless otherwise indicated or specified.
2. Be galvanized when connecting galvanized steel.
3. Conform to A325, Type 3, for use with A242 steel.
4. Compressible Washer -Type, Direct -Tension Indicators:
a. ASTM F959 Type 325 for use with A325 bolts.
b. ASTM F959 Type 490 for use with A490 bolts.
C. Galvanized for use with galvanized bolts.
5. Nuts: Heavy Hex conforming to ASTM A563 Grade DH.
6. Flat and beveled washers: Conform to ASTM F436.
C. Anchor Bolts:
1. Conform to ASTM A307 using A36 steel, unless otherwise indicated to be stainless steel
or high strength.
2. Machine Bolts: Conform to ASTM A307.
3. Stainless Steel: Conform to ASTM F593, Type 304, with nuts conforming to ASTM
F594. Sleeves shall conform to ASTM A312.
4. High Strength: Conform to ASTM A449 with nuts conforming to ASTM A563.
5. Washers:
a. ASTM A307 and A449 Bolts: Conform to ASTM F436.
b. Stainless -Steel Bolts: Conform to ASTM A167, Type 304 and dimensional
tolerances of F436.
D. Square and Rectangular Tubing: Conform to ASTM A500.
E. Checker Plate: Conform to ASTM A36 with deformations of the four-way type.
F. Shear -Stud Connectors: Manufacture from cold -finished carbon steel conforming to ASTM
A108, Grade 1015 and 1020.
G. Welding:
1. For ASTM A36 steel, use E70 electrodes for shielded metal arc welding, F7 series
electrodes for submerged arc, and E70T series electrodes for flux -cored arc welding.
2. Select "matching" filler metal in accordance with Table 4.1.1, AWS D 1.1 and Table 4.1.4
for ASTM A242 steel.
3. Select "matching" electrodes in accordance with AWS A5.4 for welding of stainless
steel.
2.02 STEEL FABRICATION:
A. Fabricate all steel to conform to AISC specifications, codes, and standards.
B. Permissible variations for sweep, camber, length, and cross-section of all steel members shall
conform to ASTM A6, AISC "Manual of Steel Construction, Part 1," and AISC "Quality
Criteria and Inspection Standards" unless indicated otherwise.
C. Field -measure existing steel and structures where necessary to ensure fabrication fit -up of new
steel.
D. Shop Milling:
1. Perform at base of columns and at top of column base plates, except that rolled-steel
bearing plates 4 inches thickness or less may be straightened by pressing.
2. Perform on butted ends for bolted or partial penetration welded column splices. Shop
milling is not required for welded column splices with full penetration welds.
3. Perform at ends of columns which butt against a plate.
Village of Mount Prospect 051000-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
E. Welding:
1. All welding shall be shielded metal arc, submerged arc, or flux -cored arc. Other welding
processes may be used provided they are qualified by applicable tests as prescribed in the
AWS D 1.1 Code and approved by Engineer prior to use. For use of any other welding
process, Contractor shall prepare and submit to Engineer for approval, a qualified
welding procedure specification and the procedure qualification test results. These
submittals shall be deemed Submittals, and these other welding processes shall be
approved for use only after receipt of specific written approval from Engineer.
2. Conform to AWS Code, AISC Manual Part 4, and the AISC Quality Criteria and
Inspection Standards.
3. Contractor shall perform fabrication welding inspection in accordance with AWS D 1.1.
This welding inspection shall be performed by AWS Certified Welding Inspector(s)
(CWI). All such Certified Welding Inspectors shall be qualified and certified in
accordance with provisions of AWS QC 1 "Standard for Qualification and Certification of
Welding Inspectors." Only individuals so qualified shall be authorized to perform
fabrication/erection or verification inspection of welding performed under the provisions
of this AWS D 1.1 Code and these Contract Documents. Certifications verifying
qualifications of welding inspectors shall be submitted to Engineer as Submittals prior to
commencement of structural welding operations and/or prior to welding inspection
performed by an individual welding inspector. Defective welds shall be corrected.
F. Shop Connections:
1. Weld, rivet, or bolt at Contractor's option except when otherwise specified.
2. Welded connections shall be as specified or in accordance with acceptable alternative
designs.
a. Except where higher capacity connections are required, welded beam connections
shall conform to AISC Manual Part 4, Tables III and IV. Welds of connection
angles to beam webs shall conform with Tables III and IV, with particular regard
for minimum web thickness. Provide longer connection angles or reinforce web as
required.
b. All butt joint groove welds shall be complete penetration welds and shall conform
to applicable standards in AISC Manual Part 4 with special emphasis on
maintaining root opening. Accomplish this for single -bevel butt joint welds by
using backup plates or by chipping out and welding on the opposite side.
C. Prepare weld bevels with a mechanically guided cutting torch or by grinding.
d. Remove all run -out tabs.
3. Bolted connections shall conform with AISC Manual Part 4.
a. All bolted connections shall be made with minimum 3/4 -inch bolts, nuts, and
washers unless otherwise approved by Engineer.
b. Use the minimum number of rows of bolts for beam connections so bottom row is at
or below centerline of the beam.
C. Beam connections shall have a minimum capacity of that specified in AISC Manual
Part 4, Tables II -B for "Oversize and Short -Slotted Holes" in friction -type
connections with the number of bolt rows indicated.
G. Provisions for Field Connections:
1. Provide with bolted connections unless otherwise indicated or specified.
2. Provide for field welding only when so indicated or when detail clearances make bolting
impractical.
3. Provide all members to be field welded with bolted erection connections adequate to
resist erection stresses prior to field welding.
Village of Mount Prospect 051000-6 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
4. Girt and miscellaneous steel connections shall use either ASTM A325 or ASTM A307
bolts. For A307 bolts, oversized or slotted holes are not allowed.
2.03 LADDERS — INTERIOR
A. Interior tank and riser ladders shall be fabricated from carbon steel, with carbon steel stand-
offs.
B. Fabricate ladder side bars from minimum 2-1/2" by 3/8" flat carbon steel as required and
spaced a minimum of 16" apart per ANSI AI4.3. Furnish rungs fabricated of 1" square carbon
steel bars spaced 12" on centers, welded to the side bars. Weld ladder side bars to the tank shell
using stand-offs with a minimum 8" clearance at rung center support.
C. Interior ladders shall use dielectric bolted connections between stainless fall arrest system and
the carbon steel ladder. Stand-offs shall be surface prepared and coating using interior coating
system referenced in Section 09 90 00.
D. Provide Saf-T-Climb by North Safety or equal vertical sliding -grip -cable fall -arresting safety
system: complete with sleeve, snap hooks, splices, brackets, manual pass-through, cables and
full body harness in accordance with ANSI A 14.3 and OSHA 1926.502 and 1910.27
standards. All arrest installations for both interior and exterior ladders shall be constructed of
Type 304 stainless steel. Deliver two sets of harness and locking mechanism in industrial
quality gasketed/lockable cabinet/enclosure to Owner.
2.04 RAILINGS
A. Provide all Work per API 6501 ANSI AWWA, OSHA, or State requirements where more
stringent than specifications and the Drawings.
B. Fabricate railings from welded carbon steel shapes, hot -dip galvanized after fabrication.
2.05 MANWAYS
A. The roof manhole cover shall be rotated 90 degrees so the cover does not open toward the roof
center.
B. The gaskets for all shell manholes shall be replaced with new gaskets. Hinged support arms
shall be installed on the exterior of the tank for the manhole covers.
2.06 SHOP PROTECTIVE COATING: Prepare surface and apply primer as specified in SECTION
PART 3 - EXECUTION
3.01 PROCEDURES:
A. The Contractor is responsible to review and field verify the length and quantity of materials
prior to the start of activities. The Owner's Representative shall be notified if the Contractor
believes there is significant additional work to be done which was not shown on the Drawings
or marked in the field. The Owner's Representative shall review the conditions noted, and
determine if the distress requires additional work.
B. The Contractor shall supply written instructions and full-time site supervision to the workers
on the installation of the materials, prior to the start of work.
C. The Contractor shall remove all debris from the site daily. If the site is left in an unacceptable
condition, the Owner may contract for cleaning separately and back -charge the Contractor for
the cleaning.
D. Installation activities shall proceed in a workmanship like manner rand in accordance with the
established schedule of work and the Contractor's written instructions. Do not begin surface
Village of Mount Prospect 051000-7 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
preparation or coating work until current metal work has been completed and accepted by the
Owner's Representative.
E. Correct any discrepancy or areas determined to be deficient by the Owner's Representative
prior to starting work in new sections.
F. Dispose of all debris off-site and leave the work area clean and ready for use by the Owner.
3.02 PREPARATION:
A. Field check location and elevation of column anchor bolts and footings before erecting
structural steel columns.
B. Field measure existing steel for plumbness and elevation at connecting points.
C. Contractor shall submit the method and sequence of erection for acceptance.
D. Assure that all preassemblies not specifically indicated on Contract Drawings to be
preassembled before lifting shall maintain structural integrity during lifting.
3.03 STEEL ERECTION:
A. Erect all steel to conform to AISC specifications, codes and standards, AISC Quality Criteria
and Inspection Standard, or any local, State, or Federal Codes which may exceed such
requirements.
B. Protect existing structure from weather when connecting steel to existing structure.
C. Protect steel and anchor bolt sleeves from entrapped water that can cause damage from
freezing or corrosion.
D. Erection Bracing:
1. Provide all necessary temporary struts, ties, cables, temporary flooring, planking, and
scaffolding in connection with the erection of the structural steel or support of erection
machinery.
2. Place as required to maintain proper position against loads from erection equipment,
construction material, and wind.
3. Leave bracing in place until sufficient steel connections, concrete slabs, exterior walls,
and roof decks are in place to ensure stability of the structure.
E. Connections:
1. Unless clearance is insufficient, connections shall be bolted friction type.
2. Tighten high-strength bolts to correct bolt tension in accordance with AISC Manual, Part
5, "Specification for Structural Joints using A325 or A490 Bolts."
3. Miscellaneous steel connections shall use either ASTM A307 or ASTM A325 bolts.
4. Where required for connection fit -up, bolt holes may be adjusted in one of the following
manners (flame cutting or enlargement of holes is not allowed).
a. Reamed to AISC allowable maximum size for oversized holes.
b. Holes may be filled with weld metal, ground smooth, and field drilled.
C. Other Engineer -approved method.
5. Welded Connections:
a. Make welded connections as specified and leave all erection bolts in place after
completion of welding.
b. Reinforce connections when members requiring fillet welds are not in contact. Use
backup bars or spacer bars on all butt welds where root opening exceeds 3/16 -inch.
C. Remove all run -out tabs.
F. Welding and Welders:
Village of Mount Prospect 051000-8 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 051000 -METALS: STRUCTURAL AND MISCELLANEOUS: continued
1. The requirements for erection welding and welders shall be the same as specified for steel
fabrication.
2. All welds shall be stamped with a mark identifying the welder. Remove welders from
work after two defective welds.
3. Contractor shall perform erection welding inspection in accordance with AWS D1.1.
This welding inspection shall be performed by AWS Certified Welding Inspector(s)
(CWI). All such Certified Welding Inspectors shall be qualified and certified in
accordance with the provisions of AWS QC "Standard for Qualification and
Certification of Welding Inspectors." Only individuals so qualified shall be authorized to
perform fabrication/erection or verification inspection of welding performed under the
provisions of this AWS D1.1 Code and these Contract Documents. Certifications
verifying the qualifications of welding inspectors shall be submitted to Engineer as
Submittals prior to commencement of structural welding operations and/or prior to
welding inspection performed by an individual welding inspector. Defective welds shall
be corrected.
G. Protect pipe sleeves, other anchorage members and concrete bases from deleterious materials
at all times, and from water which may cause ice damage during freezing weather.
3.04 FIELD PROTECTIVE COATINGS:
A. Surface preparation, priming, and finish coating are specified in SECTION 099000.
END OF SECTION 051000
Village of Mount Prospect 051000-9 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS
PART 1 - GENERAL
1.01 SUMMARY:
A. The work covered by this section shall be included in the Contractor's bid for the complete
exterior and interior coating rehabilitation of the Tank 5E one -million gallon ground storage
tank.
B. In addition to the exterior and interior coating rehabilitation, the Work covered by this section
shall also include:
1. Seam sealing: Seal the existing roof manhole and the existing roof vent intersections with
an epoxy seam sealer. Seal the roof stiffener -to -roof interface and the unwelded lapped
roof seams with flexible sealant.
2. Sealant repair: Remove the existing bituminous sealant along the bottom plate -to -
foundation interface and seal with flexible polyurethane sealant.
3. Foundation repair: Chip unsound concrete to sound material and brush-off blast. Apply
bonding agent and a vinyl emollient modified concrete patching mortar to the original
contour. Apply a concrete sealer to the repaired areas.
C. This Section includes the coating of exterior and interior surfaces throughout the Project.
Examples of acceptable coating systems are specified on "coating system" sheets at the end of
this Section.
D. Coating systems include surface preparation, prime coat (first coat), finish coats (second and
third coats), inspection, cleaning, and touch-up of surfaces and equipment. Shop preparation,
prime coat, and finish coats to be shop -applied, may be specified elsewhere or referenced to
this Section so that a complete system is specified and coordinated.
1. Where surface preparation and first (prime) coat are specified in other Sections to be
shop -applied, such as for structural steel, hollow metal doors or equipment, only the
touch-up and finish coats are a part of field painting. Surface preparation is the required
degree of preparation prior to application of first (prime) coat regardless if done in shop
or field.
2. If materials are provided without shop primer such as miscellaneous steel or sheet metal,
then surface preparation, first, second, and third coats are a part of field painting.
3. Concealed surfaces are generally not required to have finish -coats unless otherwise
specified, but prime coat should be applied and touched up prior to concealment.
4. Where Equipment and Materials are provided with shop -applied finished coating system,
touch-up and finish coats are a part of field painting.
5. Refer to applicable Sections to determine whether surface preparation and first coat, or
complete coating system, is to be shop -applied.
E. Related Work Specified Elsewhere:
1. Shop Painting and Coatings: All applicable Divisions.
2. Factory Prefinished Items: All applicable Divisions.
F. Colors:
1. Color of finish coatings shall match accepted color Samples.
2. When second and finish coats of a system are of same type or tint, use an alternate color
on second coat to enable visual coverage inspection of the third coat. When first and
second coats only are specified and are of same or different types or tint, use an alternate
color on first coat to enable visual coverage inspection of the second coat.
1.02 REFERENCES:
A. Applicable Standards:
1. American National Standards Institute (ANSI):
Village of Mount Prospect 099000-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS: continued
a. A13.1 - Scheme for the Identification of Piping Systems.
b. Z53.1 - Safety Color Code for Marking Physical Hazards.
2. American Society for Testing and Materials (ASTM):
a. D2092 — Guide for Treatment of Zinc -Coated (Galvanized) Steel Surfaces for
Painting.
b. D4258 - Surface Cleaning Concrete for Coating.
C. D4259 - Abrading Concrete.
d. D4260 - Acid Etching Concrete.
e. D4261 - Surface Cleaning Concrete Unit Masonry for Coating.
3. Society for Protective Coatings (SSPQ Surface Preparation Specifications:
a. Guide 7 — Guide to the Disposal of Lead -Contaminated Surfaces
b. SP 1 - Solvent Cleaning: Removes oil, grease, soil, drawing and cutting compounds,
and other soluble contaminants.
C. SP2 - Hand Tool Cleaning: Remove loose material. Not intended to remove
adherent mill scale, rust, and paint.
d. SP3 - Power Tool Cleaning: Removes loose material. Not intended to remove all
scale or rust.
e. SP5 - White Metal Blast Cleaning: Removes all scale, rust, foreign matter. Leaves
surface gray -white uniform metallic color.
f. SP6 - Commercial Blast Cleaning: Two-thirds of every nine square inches free of
all visible residues; remainder only light discoloration.
g. SP7 - Brush -Off Blast Cleaning: Removes only loose material, remaining surface
tight and abraded to give anchor pattern.
h. SP10 - Near -White Blast Cleaning: At least 95% of every nine square inches shall
be free of all visible residues.
i. SP 11 - Power Tool Cleaning to Bare Metal.
j. SP 12 — Surface Preparation and Cleaning of Steel and Other Hard Materials by
High and Ultrahigh Pressure Water Jetting Prior to Recoating.
k. SP 13 — Surface Preparation of Concrete.
4. National Sanitation Foundation (NSF):
a. 61 - Drinking Water Treatment Chemicals — Health Effects.
5. Code of Federal Regulations (CFR)
a. OSHA Construction Standard 29 CFR 1926.62 — Lead
b. 40 CFR 262 — Standards Applicable to Generators of Hazardous Waste
C. 40 CFR 265 — Interim Status Standards for Owners and Operators of Hazardous
Waste Treatment, Storage, and Disposal Facilities
1.03 SUBMITTALS:
A. Submit as specified in DIVISION 1.
B. Includes, but not limited to, the following:
1. Schedule of products and paint systems to be used. Schedule shall include the following
information:
a. Surfaces for system to be applied.
b. Surface preparation method and degree of cleanliness.
C. Product manufacturer, name, and number.
d. Method of application.
e. Dry film mil thickness per coat of coating to be applied.
2. Color charts for selection and acceptance.
Village of Mount Prospect 099000-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS: continued
3. Technical and material safety data sheets.
4. Certification(s) by coating manufacturer(s) that all coatings are suitable for service
intended as stated on each coating system sheet. If manufacturer has an equivalent
product as that specified, and it is suitable for the intended purpose, Contractor shall
submit the recommended product for approval at no increase in cost, and state reasons for
substitution.
5. Contractor shall certify in writing to the Engineer/Architect that applicators have
previously applied all the systems in this Specification and have the ability and
equipment to prepare the surfaces and apply the coatings correctly.
C. Design/Shop Drawings
1. Contractor shall submit shop drawings of the coating scheme in a three-dimensional
rendering for approval by the Owner.
D. Submittals for industrial maintenance coatings shall be prepared by, or have assistance in
preparation of, a corrosion engineer or industrial coatings technical representative of the
coating manufacturer.
1.04 QUALITY ASSURANCE:
A. Certification: Coating work shall be performed by an S SPC certified contractor.
B. Include on label of container:
1. Manufacturer's name, product name, and number.
2. Type of paint and generic name.
3. Color name and number.
4. Storage and temperature limits.
5. Mixing and application instructions, including requirements for precautions which must
be taken.
6. Drying, recoat, or curing time.
C. A coating report shall be completed daily by Contractor at each phase of the coating system
starting with surface preparation. These shall be submitted on the form attached at end of this
Section.
D. In the event a problem occurs with coating system, surface preparation, or application,
Contractor shall require coating applicator and coating manufacturer's technical representative
to promptly investigate the problem and submit results to Engineer/Architect.
E. Specified VOC shall mean unthinned maximum VOC certified by manufacturer. VOC content
as a result of thinning shall not exceed that allowed by federal or local environmental
regulations.
1.05 GUARANTEE:
A. The Contractor shall protect and be responsible for their work at all times and shall perform
any touch-up work as required by these specifications and as directed by the Owner.
Workmanship and materials shall be guaranteed for one year after the date of final Owner
acceptance.
B. Any defective work shall be documented and the Contractor shall be notified of necessary
repair (method and extent). The cost of warranty inspection by the Engineer will be the
responsibility of the Owner.
1.06 DELIVERY, STORAGE, AND HANDLING:
A. Delivery of Materials:
Village of Mount Prospect 099000-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS: continued
1. Deliver in sealed containers with labels and information legible and intact. Containers
shall also have correct labels with required information.
2. Allow sufficient time for testing if required.
B. Storage of Materials:
1. Store only acceptable materials on Project Site.
2. Provide separate area and suitable containers for storage of coatings and related coating
equipment.
3. Dispose of used or leftover containers, thinners, rags, brushes, and rollers in accordance
with applicable regulations.
1.07 REGULATORY REQUIREMENTS:
A. In addition to requirements specified elsewhere for environmental protection, provide coating
materials that conform to the restrictions of the U.S. EPA and the local and regional
jurisdictions. Notify Engineer/Architect of any coating specified herein that fails to conform to
the requirements for the location of the Project or location of application.
B. Lead Content: Use only coatings that are totally lead free.
C. Chromate Content: Do not use coatings containing zinc -chromate or strontium chromate.
D. Asbestos Content: Materials shall not contain asbestos.
E. Mercury Content: Materials shall not contain mercury or mercury compounds.
F. Exterior coating to be removed during the surface preparation procedures on this project have
been assessed in accordance with State and Federal standards and may contain lead and
chromium contents above the Federal Action Level. Lead and chromium containing paint may
be present on additional structures and other sources not identified by the primary screening
procedures. The contractor shall be responsible to protect his workers, the Owner, and other
project personnel from exposure to lead and chromium resulting from work on the project.
G. Interior coating to be removed during surface preparation procedures on this project have been
assessed in accordance with State and Federal standards. Coating on the tank interior may
contain lead above the Federal Action Level. Lead and chromium containing paint may be
present on additional structures and other sources not identified by the primary screening
procedures. The contractor shall be responsible to protect his workers, the Owner, and other
project personnel from exposure to lead and chromium resulting from work on the project.
H. The Contractor shall be responsible for worker and environmental controls for lead and
chromium paint removal and disposal in accordance with the OSHA construction standard 29
CFR 1926.62 and the most recent applicable federal, state, and local regulations.
I. The Contractor shall not endanger any work by blasting or alter the work of any other trade
save with the consent of the Owner. Any cost caused by defective or ill-timed work shall be
borne by the party responsible.
J. Handling, Disposal and Analysis of Blasting Debris is the responsibility of the Contractor, who
shall provide a written plan that addresses the handling and site storage of lead containing
debris in accordance with the requirements of 40 CFR 262 and 40 CFR 265. The Contractor
shall provide the storage containers, EPA identification number, transportation and disposal of
the debris.
1.08 PROJECT CONDITIONS:
A. This Project contains some structures of a height in which drifting coatings, if spray -applied,
could contaminate adjacent building surfaces or vehicles on nearby roadways. All containment
precautions and application methods shall be taken into consideration and implemented to
prevent the above from occurring.
Village of Mount Prospect 099000-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS: continued
PART 2 - PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS:
A. Proprietary names and product numbers are specified in most systems for material
identification from these manufacturers:
1. Tnemec Company, Inc.
2. PPG Industries, Inc.
3. Sherwin-Williams
2.02 GENERAL:
A. Materials furnished for each coating system must be compatible to the substrate.
B. When unprimed surfaces are to be coated, entire coating system shall be by the same coating
manufacturer to assure compatibility of coatings.
C. When shop -painted surfaces are to be coated, ascertain whether finish materials will be
compatible with shop coating. Inform Engineer/Architect of any unsuitable substrate or
coating conditions.
2.03 COATING SYSTEMS:
A. System D-3:
1. Tank Interior (Base Bid Item Na 2).
B. System A-3.1:
1. Tank Exterior (Base Bid Item No. 3).
C. System A-3.2:
1. Tank Exterior (Alternate Bid Item No. La).
PART 3 - EXECUTION
3.01 SURFACE PREPARATION:
A. Prepare surfaces for each coating system conforming to S SPC or ASTM surface preparation
specifications listed.
1. If grease or oils are present, SSPC-SP1 shall precede any other method specified for
metal substrates.
2. Remove surface irregularities such as weld spatter, burrs, or sharp edges prior to
specified surface preparation.
3. Thoroughly abrade any area where new coating will overlap tightly adhered existing
coating.
B. Depth of profile will be as specified or as recommended by the manufacturer for each system,
but in no instance shall it exceed one-third of the total dry film thickness of complete system.
C. Prepare only those areas which will receive the first coat of the system on the same day.
1. On steel substrates, apply coating before rust bloom forms.
D. Concrete and masonry surfaces shall be adequately cured prior to coating application.
1. Use surface cleaning methods, followed by mechanical or chemical surface preparation
as specified in S SPC SP 13 .
a. Acid etching (ASTM D 4260) shall not be used for vertical surfaces.
b. Acid etching shall only be used where:
(1) Procedures are in place for removal of acid residues and the handling,
containment, and disposal of hazardous materials.
(2) Measures for protection of worker health and safety are provided.
Village of Mount Prospect 099000-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS: continued
3.02 APPLICATION:
A. Apply coatings in accordance with coating manufacturer's recommendations.
B. Use properly designed brushes, rollers, and spray equipment for all applications.
C. On unprimed surfaces apply first coat of the system the same day as surface preparation.
D. Dry film thickness of each system shall meet the minimum specified. Maximum dry film
thickness shall not exceed the minimum more than 20% or coating manufacturer's
requirements if less. Where a dry film thickness range is specified, the range shall not be less
than or exceeded.
E. Shop and field painting shall remain 3 inches away from unprepared surface of any substrate
such as areas to be welded or bolted.
F. Environmental Conditions:
1. Atmospheric temperature must be 50°F or higher during application, unless otherwise
approved by coating manufacturer. Do not apply coatings when inclement weather or
freezing temperature may occur within coating recoat cure times.
2. Wind velocities for exterior applications shall be at a minimum to prevent overspray or
fallout and not greater than coating manufacturer's limits.
3. Relative humidity must be less than 85%. The ambient temperature and the temperature
of the surface to be painted must be at least 5°F above the dew point.
4. Provide adequate ventilation in all areas of application to ensure that at no time does the
content of air exceed the Threshold Limit Value given on the manufacturer's Material
Safety Data Sheets for the specific coatings being applied.
G. Recoat Time: In the event a coating, such as an epoxy, has exceeded its recoat time limit,
prepare the applied coating in accordance with manufacturer's recommendations.
H. Protection:
1. Cover or otherwise protect surfaces not to be painted. Remove protective materials when
appropriate.
2. Mask, remove, or otherwise protect finish hardware, machined surfaces, grilles, lighting
fixtures, and prefinished units as necessary.
3. Provide cover or shields to prevent surface preparation media and coatings from entering
orifices in electrical or mechanical Equipment. Where ventilation systems must be kept
in operation at time of surface preparation, take precautions to shield intakes and exhausts
to prevent the materials from entering system or being dispersed.
4. Provide signs to indicate fresh paint areas.
5. Provide daily cleanup of both storage and working areas and removal of all paint refuse,
trash, rags, and thinners. Dispose of leftover containers, thinners, rags, brushes, and
rollers which cannot be reused in accordance with applicable regulations.
6. Do not remove or paint over Equipment data plates, code stamps on piping, or UL fire -
rating labels.
3.03 INSPECTION
A. Contractor shall provide and use wet film gauges to check each application approximately
every 15 minutes in order to immediately correct film thickness under or over that specified.
B. Contractor shall provide and use a dry film gauge to check each coat mil thickness when dry,
and the total system mil thickness when completed.
C. Use holiday or pinhole detector on systems over metal substrates to detect and correct voids
when indicated on system sheet.
D. Furnish a sling psychrometer and perform periodic checks on both relative humidity and
temperature limits.
Village of Mount Prospect 099000-6 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 099000 - PROTECTIVE COATINGS: continued
E. Check air temperature and temperature of the substrate at regular intervals to be certain surface
is 5°F or more above the dew point.
3.04 CLEANING AND REPAIRS:
A. Remove spilled, dripped, or splattered paint from surfaces.
B. Touch up and restore damaged finishes to original condition. This includes surface preparation
and application of coatings specified.
3.05 EXTERIOR SURFACES
A. Exterior Coating with Spot Repair and Power Wash - All exterior surfaces of Tank 5E shall be
properly prepared by power wash and spot clean and over -coated as described below:
1. All surfaces shall be clean and free of al dust, dirt, grease, oil and foreign matter prior to
painting.
2. Power wash all surfaces to SSPC-SP12 using a solution of one part household bleach to
three parts water to kill all mold and mildew present on the surface.
3. Rinse all surfaces with clean water prior to power tool cleaning.
4. Spot power tool clean to SSPC-SP3 all rusted, flaking, or failed areas.
5. Apply spot prime and appropriate coating system as selected by Owner in accordance
with coating manufacturer's recommendations.
3.06 WET INTERIOR SURFACES
A. Interior Wet Coating with Full Blast - All wet interior surfaces of Tank 5E shall be properly
prepared by full blast and re -coated as described below:
1. Full blast clean all surfaces to SPPC-SP10.
2. Apply coating system as selected by the Owner in accordance with coating
manufacturer's recommendations.
3. Dispose of the spent abrasive per S SPC -Guide 7 if lead is detected in the existing coating.
4. Perform sterilization per AWWA C652 — Method 3 with sampling by the Owner.
3.07 ALTERNATE ITEMS
A. Exterior Coating with Full Blast — all exterior surfaces of Tank 5E shall be properly prepared
by full blast and re -coated as described below:
1. Full blast clean all surfaces to SSPC-SP10.
2. Apply coating system as selected by the Owner in accordance with coating
manufacturer's recommendations.
3. Dispose of the spent abrasive per S SPC -Guide 7 if lead is detected in the existing coating.
3.08 WELDED AREAS
A. Areas that are impacted by welding shall be power tool cleaned to bare metal per SSPC-SP 11.
B. All remaining areas shall be brush-off blasted to SSPC-SP7.
C. Spot coat the impacted areas with the appropriate coating system selected by the Owner.
END OF SECTION 099000
Village of Mount Prospect 099000-7 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Base Bid Pay Item No.
S''Mc..DONNELL
PROTECTIVE COATING SYSTEM
BURNS,
System: D=3
SERVICE: Steel & Iron - Potable Water Immersion, Normal Service.
Interior of Tank or Basin. Exterior of Steel Piping, or Equipment in Tank or
Basin.
Surface Preparation: Shop or Field First Coat: SPPC-SP10 and profile depth 1.5 to 2.5 mils
(38 to 63 microns) or as recommended by the manufacturer.
Field Touch Up (of Shop -applied first coat): Same as for first coat.
First (prime) Coat: Shop or Field: Moisture -cured urethane, zinc -rich primer with minimum
80% zinc in the dry film and approved service with potable water,
meeting NSF Standard 61. Apply at 3.0 to 5.0 mils (75 to 125) dry film
thickness or as recommended by the manufacturer.
Field: Touch-up same as first coat.
Second Coat: High solids amine, polyamide, or polyamidoamine epoxy with a minimum
98% solids by volume and be for use with potable water, meeting NSF
Standard 61. Apply at a minimum of 20.0 mils (510 microns) dry film
thickness or as recommended by the manufacturer.
Third Coat: Same as second coat, as needed.
System Total: Minimum 23.0 mils (585 microns) dry film thickness.
Volatile Organic Content: Maximum 2.8 Ib/gal (340 g/L).
COATING
PRODUCT DESIGNATION
MANUFACTURER
FIRST COAT
TOUCH UP
SECOND COAT
THIRD COAT
Tnemec
Hydro -Zinc Series
Same as first coat
Epoxoline
Same as second
91 -H2O
Series 22
coat
Carboline
Carbozinc 8703
Same as first
Phenoline Tank
Same as second
coat
Shield
coat
Sherwin-Williams
Corothane I Galvapac
Same as first
DuraPlate UHS
Same as second
1 K Zinc Primer
coat
Epoxy Tank Lining
coat
B65G 11
Village of Mount Prospect 099000-8 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Base Bid Pay Item No.
S''MCM.DONNELL,
PROTECTIVE COATING SYSTEM
BURNS, &�
System: A=3m 1
SERVICE: Steel — Severe Exposure (Nonimmersion)
Exterior or Interior
Surface Preparation: Shop or Field First Coat: Power wash to SSPC-SP12 as specified.
Field Touch -Up: Spot power tool clean to SSPC-SP3 all rusted, flaking, or
failed areas.
First (Prime) Coat: Moisture -cure urethane organic zinc -rich primer with minimum 80% zinc by
weight in dry film. Apply at 2.0 to 4.0 mils (50 to 100 microns) dry film
thickness or as recommended by the manufacturer.
Second Coat: High -Build polyimide epoxy with minimum 65% solids by volume. Apply at
4.0 to 6.0 mils (100 to 150 microns) dry film thickness or as recommended
by the manufacturer.
Third Coat (Exterior): High solids aliphatic acrylic polyurethane gloss enamel with minimum 65%
solids by volume. Apply at 3.0 to 5.0 mils (75 to 125 microns) dry film
thickness or as recommended by the manufacturer.
System Total: Minimum 9.0 mils (225 microns) dry film thickness (Exterior).
Minimum 6.0 mils (150 microns) dry film thickness (Interior).
Volatile Organic Content: Maximum 2.8 Ib/gal (340 g/L).
COATING
MANUFACTURER
PRODUCT DESIGNATION
FIRST COAT
TOUCH UP
SECOND COAT
THIRD COAT
Tnemec
Series 135 Chembuild
Same as First Coat
Series 27 F.C.
Series 1074 Endura-
Typoxy
Shield II
Carboline
Carboguard 890
Same as First Coat
Same as First Coat
Carbothane 134HG
Sherwin-Williams
Macropoxy 646 Fast
Same as First Coat
Same as First Coat
Acrolon Ultra
Cure Epoxy
Village of Mount Prospect 099000-9 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Alternate Bid Pay Item La
S
PROTECTIVE COATING SYSTEM
BURNS, mcn.DONNELL, &�
System: A=3m2
SERVICE: Steel — Severe Exposure (Nonimmersion)
Exterior or Interior
Surface Preparation: Shop or Field First Coat: SSPC-SP10 and profile depth 1.5 to 2.5 mils (38
to 63 microns).
Field Touch -Up: SSPC-SP11 and profile depth 1.0 to 1.5 mils (25 to 38
microns).
First (Prime) Coat: Moisture -cure urethane organic zinc -rich primer with minimum 80% zinc by
weight in dry film. Apply at 2.0 to 4.0 mils (50 to 100 microns) dry film
thickness or as recommended by manufacturer.
Second Coat: High -Build polyimide epoxy with minimum 65% solids by volume. Apply at
4.0 to 6.0 mils (100 to 150 microns) dry film thickness or as recommended
by manufacturer.
Third Coat (Exterior): High solids aliphatic acrylic polyurethane gloss enamel with minimum 65%
solids by volume. Apply at 3.0 to 5.0 mils (75 to 125 microns) dry film
thickness or as recommended by manufacturer.
System Total: Minimum 9.0 mils (225 microns) dry film thickness (Exterior).
Minimum 6.0 mils (150 microns) dry film thickness (Interior).
Volatile Organic Content: Maximum 2.8 Ib/gal (340 g/L).
COATING
PRODUCT DESIGNATION
MANUFACTURER
FIRST COAT
TOUCH UP
SECOND COAT
THIRD COAT
Tnemec
Hydro -Zinc Series
Same as First Coat
Endura -Shield
Hyrdoflon
91 -H2O
Series 73
Series 700
Carboline
Carbozinc 621
Same as First Coat
Carbothane 133
Carboxane 950 VOC
Series
Sherwin-Williams
Corothane 1 Galvapac
Same as First Coat
Acrolon 218 HS
Fluorokem HS
1 K Zinc Primer
B65G 11
Village of Mount Prospect 099000-10 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS
PART 1 - GENERAL
1.01 SUMMARY:
A. This Section includes the following areas of Work:
1. Preparation of lawn areas.
2. Seeding.
3. Mulching.
4. Fertilizing of lawn areas.
5. Maintenance.
1.02 REFERENCES:
A. Applicable Standards:
1. American Society for Testing and Materials (ASTM) -Equivalent AASHTO standards
may be substituted as approved:
a. D977 -Emulsified Asphalt.
B. Illinois Department of Transportation (IDOT) Standard Specifications for Road and Bridge
Construction, Adopted April 1, 2016.
1.03 DEFINITIONS
A. Finish Grade: Elevation of finished surface of planting soil.
B. Pesticide: A substance or mixture intended for preventing, destroying, repelling, or mitigating
a pest. Pesticides include insecticides, miticides, herbicides, fungicides, rodenticides, and
molluscicides. They also includes substances or mixtures intended for use as a plant regulator,
defoliant, or desiccant.
C. Pests: Living organisms that occur where they are not desired or that cause damage to plants,
animals, or people. Pests include insects, mites, grubs, mollusks (snails and slugs), rodents
(gophers, moles, and mice), unwanted plants (weeds), fungi, bacteria, and viruses.
D. Planting Soil: Existing, on-site soil; imported soil; or manufactured soil that has been modified
with soil amendments and perhaps fertilizers to produce a soil mixture best for plant growth.
E. Subgrade: The surface or elevation of subsoil remaining after excavation is complete, or the
top surface of a fill or backfill before planting soil is placed.
1.04 SUBMITTALS:
A. Qualification Data: For landscape Installer.
B. Certification of Grass Seed: From seed vendor for each grass -seed monostand or mixture,
stating the botanical and common name, percentage by weight of each species and variety, and
percentage of purity, germination, and weed seed. Include the year of production and date of
packaging.
C. Product Certificates: For fertilizers, from manufacturer.
D. Pesticides and Herbicides: Product label and manufacturer's application instructions specific to
Proj ect.
1.05 DELIVERY, STORAGE, AND HANDLING
A. Seed and Other Packaged Materials: Deliver packaged materials in original, unopened
containers showing weight, certified analysis, name and address of manufacturer, and
indication of compliance with state and Federal laws, as applicable.
B. Bulk Materials:
1. Do not dump or store bulk materials near structures, utilities, walkways and pavements,
or on existing turf areas or plants.
Village of Mount Prospect 329200-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS: continued
2. Provide erosion -control measures to prevent erosion or displacement of bulk materials;
discharge of soil -bearing water runoff; and airborne dust reaching adjacent properties,
water conveyance systems, or walkways.
3. Accompany each delivery of bulk materials with appropriate certificates.
1.06 FIELD CONDITIONS
A. Planting Restrictions: Plant during one of the following periods. Coordinate planting periods
with initial maintenance periods to provide required maintenance from date of planting
completion.
B. October 16 to January 31.
1. Contractor shall post a warranty bond for all seeding done during this timeframe.
C. February 1 to October 15.
D. Weather Limitations: Proceed with planting only when existing and forecasted weather
conditions permit planting to be performed when beneficial and optimum results may be
obtained. Apply products during favorable weather conditions according to manufacturer's
written instructions.
PART 2 - PRODUCTS
2.01 TOPSOIL:
A. Materials suitable shall be free of debris, roots, organic matter, and frozen matter; and free of
stone having any dimension greater than 2 inches in areas requiring a high degree of
compaction or 4 inches in other embankment and fill areas:
B. Topsoil shall be a fertile, friable, and loamy soil of uniform quality, free from materials such as
hard clods, stiff clay, stone with any dimension greater than 1 inch, and similar impurities.
Relatively free from grass, roots, weeds, and other objectionable plant material.
C. Materials unsuitable for use include all material that contains debris, roots, organic matter,
frozen matter, gravel, stone, or shale particles (with any dimension greater than 2 inches in
areas requiring a high degree of compaction or 4 inches in other embankment and fill areas), or
other materials that are determined by Engineer to be too wet or otherwise unsuitable for
providing a stable subgrade or stable foundation for structures.
D. Material shall be subject to approval of Engineer.
E. Borrow areas shall be as follows:
1. As indicated.
2. Provided by Owner.
3. Arranged for by Contractor at no additional cost to Owner.
4. Subject to approval of Engineer.
2.02 GRASS SEED:
A. Provide fresh, clean, new crop seed complying with tolerance for purity and germination
established by Official Seed Analysts of North America and as required below.
B. Be labeled according to the U.S. Department of Agriculture Federal Seed Act and shall be
furnished in containers with tags showing seed mixture, purity, germination, weed content,
name of seller, and date on which seed was tested:
1. Seed Mixture:
a. Meet the requirements of the Illinois Department of Transportation (IDOT) Seed
Mix No. 2A, as specified in the Standard Specifications for Road and Bridge
Construction.
2. Moldy seed or seed that has been damaged in storage shall not be used.
Village of Mount Prospect 329200-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS: continued
2.03 MULCH:
A. Straw Mulch: Provide air-dry, clean, mildew- and seed -free, salt hay or threshed straw of
wheat, rye, oats, or barley.
B. Tackifiers:
1. Asphalt Emulsion: Conform to ASTM D977, Type SS -1; nontoxic and free of plant -
growth or germination inhibitors.
2. Nonasphaltic Tackifier: Colloidal tackifier recommended by fiber -mulch manufacturer
for slurry application; nontoxic and free of plant -growth or germination inhibitors.
2.04 FERTILIZER:
A. Commercial fertilizer of neutral character, with some elements derived from organic sources,
containing not less than 12% phosphoric acid, 12% potassium, and 12% nitrogen.
B. Deliver to site in labeled bags or containers.
2.05 EROSION -CONTROL MATERIALS:
A. Erosion -Control Blankets: Biodegradable wood excelsior, straw, or coconut -fiber mat enclosed
in a photodegradable plastic mesh. Include manufacturer's recommended steel wire staples, 6
inches long.
PART 3 - EXECUTION
3.01 EXAMINATION:
A. Examine areas to be planted for compliance with requirements and other conditions affecting
installation and performance of the Work.
1. Verify that no foreign or deleterious material or liquid such as paint, paint washout,
concrete slurry, concrete layers or chunks, cement, plaster, oils, gasoline, diesel fuel,
paint thinner, turpentine, tar, roofing compound, or acid has been deposited in soil within
a planting area.
2. Suspend planting operations during periods of excessive soil moisture until the moisture
content reaches acceptable levels to attain the required results.
3. Uniformly moisten excessively dry soil that is not workable or which is dusty.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
C. If contamination by foreign or deleterious material or liquid is present in soil within a planting
area, remove the soil and contamination as directed by Engineer and replace with new planting
soil.
3.02 PREPARATION:
A. Protect structures; utilities; sidewalks; pavements; and other facilities, trees, shrubs, and
plantings from damage caused by planting operations.
1. Protect grade stakes set by others until directed to remove them.
B. Install erosion -control measures to prevent erosion or displacement of soils and discharge of
soil -bearing water runoff or airborne dust to adjacent properties and walkways.
3.03 SOIL PREPARATION:
A. Dispose of any growth, rocks, or other obstructions which might interfere with tilling, seeding,
sodding, or later maintenance operations. Remove stones over 1-1/2 inches in any dimension
and sticks, roots, rubbish, and other extraneous matter.
B. Thoroughly loosen and pulverize topsoil to a depth of at least 4 inches.
Village of Mount Prospect 329200-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS: continued
C. Grade lawn areas to a smooth, even surface with loose, uniformly fine texture. Roll and rake,
remove ridges and fill depressions to meet finish grades. Limit fine grading to areas which can
be planted within immediate future.
D. Moisten prepared lawn areas before planting if soil is dry. Water thoroughly and allow surface
to dry off before planting of lawns. Do not create a muddy soil condition.
E. Restore prepared areas to specified condition if eroded or otherwise disturbed after fine
grading and prior to planting.
F. Spread planting soil mixture to depth required to meet thickness, grades, and elevations
indicated after light rolling and natural settlement.
G. Preparation of Unchanged Grades:
1. Where lawns are to be planted in areas that have not been altered or disturbed by
excavating, grading, or stripping operations, prepare soil for lawn planting as follows:
a. Till to a depth of not less than 6 inches.
b. Apply soil amendments and initial fertilizers.
C. Remove high areas and fill in depressions.
d. Till soil to a homogeneous mixture of fine texture, free of lumps, clods, stones,
roots, and other extraneous matter.
3.04 FERTILIZING:
A. Apply fertilizer at the rate of 400 pounds per acre to prepared seedbeds and sodbeds.
B. Incorporate fertilizer into the soil to a depth of at least 2 inches by discing, harrowing, or
raking, except where applied hydraulically on slopes steeper than 2 horizontal to 1 vertical.
3.05 SEEDING NEW LAWNS:
A. Sow seed with spreader or seeding machine. Do not broadcast or drop seed when wind velocity
exceeds 5 mph.
1. Evenly distribute seed by sowing equal quantities in two directions at right angles to each
other.
2. Do not use wet seed or seed which is moldy or otherwise damaged.
3. Do not seed against existing trees. Limit extent of seed to outside edge of planting saucer.
B. Sow not less than a rate of 80 pounds per acre.
C. Rake seed lightly into top 1/4 -inch of soil, roll lightly, and water with fine spray.
D. Protect all seeded areas with erosion -control blankets installed and stapled according to
manufacturer's written instructions.
E. Methods of Application:
1. Dry Seeding: Spreader or seeding machine.
2. Hydroseeding: Mix seed, fertilizer and pulverized mulch with water and constantly
agitate. Do not add seed to water more than 4 hours before application:
a. On slopes of 2 horizontal to 1 vertical or flatter, apply seed separately from
fertilizer. Cover seed with soil to an average depth of 1/2 -inch by raking or other
approved methods.
b. On slopes steeper than 2 horizontal to 1 vertical, seed and fertilizer may be applied
in a single operation. Incorporation into the soil will not be required.
3.06 MULCHING:
A. Apply a mulch covering to all seeded areas.
B. Vegetative Mulch with Asphalt Emulsion:
1. Apply vegetative mulch at the rate of 2-1/2 tons per acre.
2. Apply asphalt emulsion at the rate of 250 gallons per acre.
Village of Mount Prospect 329200-4 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS: continued
3. Mulching machine shall inject emulsified asphalt at the proper rate directly into the air
stream carrying the straw.
C. Immediately following the application of the mulch, water the seeded area in one watering, in
sufficient amount to penetrate the seedbed to a minimum depth of 2 inches. Perform so as not
to cause erosion or damage to the seeded surface.
D. Protect seeded areas against hot, dry weather or drying winds by applying mulch not more than
24 hours after completion of seeding operations.
3.07 HYDROSEEDING:
A. Hydroseeding: Mix specified seed, fertilizer, and fiber mulch in water, using equipment
specifically designed for hydroseed application. Continue mixing until uniformly blended into
homogeneous slurry suitable for hydraulic application.
B. Mix slurry with fiber -mulch manufacturer's recommended tackifier.
C. Spray -apply slurry uniformly to all areas to be seeded in a one-step process. Apply slurry at a
rate so that mulch component is deposited at not less than 1500-1b/acre dry weight, and seed
component is deposited at not less than the specified seed -sowing rate.
D. Spray -apply slurry uniformly to all areas to be seeded in a two-step process. Apply first slurry
coat at a rate so that mulch component is deposited at not less than 500-1b/acre dry weight, and
seed component is deposited at not less than the specified seed -sowing rate. Apply slurry cover
coat of fiber mulch (hydromulching) at a rate of 1000 lb/acre.
3.08 NETTING:
A. Install netting where indicated and immediately following mulching operations.
B. Roll netting loosely over the required areas. Lifting and stretching of the material will not be
permitted.
C. Secure netting by staples spaced every 1 to 2 feet apart along top and bottom ends and no more
than 4 feet apart along sides and across remaining unanchored netting forming an "X" pattern.
D. Lap joints in the direction of water flow with at least a 2 -inch overlap.
E. After the netting is secured in place by staples, press firmly against the surface of the soil by
tamping or by rolling with an approved smooth -wheel hand roller.
F. Repair any seeded or mulched areas disturbed by the installation of the netting.
3.09 TURF RENOVATION:
A. Renovate existing turf where indicated.
B. Renovate turf damaged by Contractor's operations, such as storage of materials or equipment
and movement of vehicles.
1. Reestablish turf where settlement or washouts occur or where minor regrading is
required.
2. Install new planting soil as required.
C. Remove sod and vegetation from diseased or unsatisfactory turf areas; do not bury in soil.
D. Remove topsoil containing foreign materials, such as oil drippings, fuel spills, stones, gravel,
and other construction materials resulting from Contractor's operations, and replace with new
planting soil.
E. Mow, dethatch, core aerate, and rake existing turf.
F. Remove weeds before seeding. Where weeds are extensive, apply selective herbicides as
required. Do not use pre -emergence herbicides.
G. Remove waste and foreign materials, including weeds, soil cores, grass, vegetation, and turf,
and legally dispose of them off Owner's property.
H. Till stripped, bare, and compacted areas thoroughly to a soil depth of 6 inches.
Village of Mount Prospect 329200-5 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS: continued
I. Apply initial fertilizer required for establishing new turf and mix thoroughly into top 4 inches
of existing soil. Install new planting soil to fill low spots and meet finish grades.
J. Apply seed and protect with straw mulch as required for new turf.
K. Water newly planted areas and keep moist until new turf is established.
3.10 PROTECTION:
A. Erect barricades and warning signs as required to protect newly planted areas from traffic.
Maintain barricades throughout maintenance period until lawn is established.
3.11 TURF MAINTENANCE:
A. General: Maintain and establish turf by watering, fertilizing, weeding, mowing, trimming,
replanting, and performing other operations as required to establish healthy, viable turf. Roll,
regrade, and replant bare or eroded areas and remulch to produce a uniformly smooth turf.
Provide materials and installation the same as those used in the original installation.
1. Fill in as necessary soil subsidence that may occur because of settling or other processes.
Replace materials and turf damaged or lost in areas of subsidence.
2. In areas where mulch has been disturbed by wind or maintenance operations, add new
mulch and anchor as required to prevent displacement.
3. Apply treatments as required to keep turf and soil free of pests and pathogens or disease.
Use integrated pest management practices whenever possible to minimize the use of
pesticides and reduce hazards.
B. Watering: Install and maintain temporary piping, hoses, and turf -watering equipment to convey
water from sources and to keep turf uniformly moist to a depth of 4 inches.
1. Schedule watering to prevent wilting, puddling, erosion, and displacement of seed or
mulch. Lay out temporary watering system to avoid walking over muddy or newly
planted areas.
2. Water turf with fine spray at a minimum rate of 1 inch (25 mm) per week unless rainfall
precipitation is adequate.
C. Mow turf as soon as top growth is tall enough to cut. Repeat mowing to maintain specified
height without cutting more than one-third of grass height. Remove no more than one-third of
grass -leaf growth in initial or subsequent mowings. Do not delay mowing until grass blades
bend over and become matted. Do not mow when grass is wet. Schedule initial and subsequent
mowings to maintain the following grass height:
1. Mow grass to a height of 2 inches as soon as there is enough top growth to cut with
mower.
2. Remove no more than 40% of grass leaf growth in initial or subsequent mowings.
3. Do not delay mowing until grass blades bend over and become matted.
D. Remove weeds by pulling or chemical treatment.
E. Seeded Areas:
1. Water as required by good practice and as necessary to obtain a flourishing cover.
2. Repair any portion of the seeded surface which becomes gullied or otherwise damaged,
or the seeding becomes damaged or destroyed.
F. Turf Post fertilization: Apply second fertilizer application after first mowing and when grass is
dry.
1. Use fertilizer that provides actual nitrogen of at least 0.45 pounds per 1,000 square feet of
lawn area.
Village of Mount Prospect 329200-6 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 329200 - LAWNS: continued
3.12 ACCEPTANCE OF LAWNS:
A. When lawn Work is Substantially Complete, including maintenance, Engineer and Owner will,
upon request, make an inspection to determine acceptability:
1. Lawn Work may be inspected for acceptance in parts agreeable to Owner, provided Work
offered for inspection is complete, including maintenance.
B. Satisfactory Seeded Turf: At end of maintenance period, a healthy, uniform, close stand of
grass has been established, free of weeds and surface irregularities, with coverage exceeding
95 percent over any 10 sq. ft. and bare spots not exceeding 5 by 5 inches.
C. Use specified materials to reestablish turf that does not comply with requirements, and
continue maintenance until turf is satisfactory.
3.13 CLEANUP:
A. Promptly remove soil and debris created by turf work from paved areas. Clean wheels of
vehicles before leaving site to avoid tracking soil onto roads, walks, or other paved areas.
B. Remove surplus soil and waste material, including excess subsoil, unsuitable soil, trash, and
debris, and legally dispose of them off Owner's property.
C. Erect temporary fencing or barricades and warning signs as required to protect newly planted
areas from traffic. Maintain fencing and barricades throughout initial maintenance period and
remove after plantings are established.
D. Remove nondegradable erosion -control measures after grass establishment period.
END OF SECTION 329200
Village of Mount Prospect 329200-7 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 331313 - WATER STORAGE TANK DISINFECTION
PART 1 GENERAL
1.1 SUMMARY
A. Section Includes:
1. Water tank disinfection.
2. Bacteriological testing.
B. Related Requirements:
1. Section 099000 — Protective Coatings.
1.2 REFERENCE STANDARDS
A. American Water Works Association:
1. AWWA C652 - Disinfection of Water Storage Facilities.
1.3 SUBMITTALS
A. Section 013300 - Submittal Procedures: Requirements for submittals.
B. Disinfection Procedure:
1. Submit description of procedure, including type of disinfectant and calculations indicating
quantities of disinfectants required to produce specified chlorine concentration.
2. Comply with Sections 3 and 4 of AWWA C652.
C. Certify that disinfectants meet or exceed AWWA C652 requirements.
D. Test and Evaluation Reports: Indicate results of bacteriological and residual chlorine laboratory
test reports.
E. Field Quality -Control Submittals: Indicate results of Contractor -furnished tests and inspections.
F. Qualifications Statement:
1. Submit qualifications for applicator.
1.4 QUALITY ASSURANCE
A. Perform Work in compliance with AWWA C652.
B. Perform Work according to State of Illinois Environmental Protection Agency standards.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Section 016000 — Equipment and Materials: Requirements for transporting, handling, storing, and
protecting products.
B. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.
Village of Mount Prospect 331313-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 331313 — WATER STORAGE TANK DISINFECTION: continued
C. Store disinfectants according to manufacturer's recommendations and in a cool, dry place away
from combustibles such as wood, rags, oils, and greases.
D. Handle disinfectants according to manufacturer's safety precautions.
PART 2 PRODUCTS
2.1 DISINFECTANTS
A. Chlorine Forms: According to AWWA C652, Section 4.
PART 3 EXECUTION
3.1 EXAMINATION
A. Inspection:
1. Conduct inspection of tank interior before beginning disinfection.
2. Verify that tank is clean and free of polluting materials.
3. Verify that tank pipe and vent connections are properly made and clear of obstructions.
4. Verify that paint is thoroughly cured according to paint manufacturer's instructions.
3.2 PREPARATION
A. Furnish personnel working inside tank during disinfection with equipment to comply with Federal
and State regulations for Work conducted in a hazardous atmosphere.
B. Protect aquatic life and vegetation from damage from disinfectant solution purged from tank.
3.3 APPLICATION
A. Use any one or combination of three methods for disinfecting tank in Section 4 of AWWA C652:
1. Chlorination Method 1.
2. Chlorination Method 2.
3. Chlorination Method 3.
B. Disposal:
1. Neutralize disinfectant solution before disposal.
2. Legally dispose of disinfection solution off Proj ect Site.
C. Repair damage caused by disinfectant solution and disinfection procedures.
3.4 FIELD QUALITY CONTROL
A. Sampling:
1. Collect samples of water from filled tank for bacteriological analysis according to Section 5
of AWWA C652.
2. Take inlet and outlet water samples.
Village of Mount Prospect 331313-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 331313 — WATER STORAGE TANK DISINFECTION: continued
B. Test water samples for bacterial contamination, residual chlorine, and others as required by to
State Health Standards for potable water.
C. When water samples fail to meet State Health Standards for potable water, perform following
corrective measures until water quality conforms to State Health Standards:
1. Inlet and Outlet Water Sample Failure: Eliminate source of contamination in water supply,
repeat disinfection, and retest water quality.
2. Outlet Water Sample Failure: Repeat disinfection and retest water quality.
END OF SECTION
Village of Mount Prospect 331313-3 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
APPENDIX A - ELECTRICAL DETAILS
Section 004005
BID FORM
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Village of Mount Prospect
Department of Public Works
FROM:
(hereinafter called "Bidder")
TO: Office of the Village Manager, 3rd Floor
50 South Emerson Street
Mount Prospect, Illinois 60056
(hereinafter called "Village" or "Village of Mount Prospect")
Bid For: Rehabilitation of 1000 200, qalion Station SE Ground'Stooge Tank
The bidders have familiarized themselves with the work and probable work conditions required
under this Bid affecting the cost of the work and with the Bid Documents which include:
Notice to Bidders
Table of Contents
Instructions for Bidders
General Conditions and Special Provisions
Specifications
Bid Form
Affidavit — Bid Certification Form
Bid Security
Bid Sheet — Rehabilitation of L000,000 Gallon Station 5E Storage Tank
Contract Document
Labor and Materials Payment bond form
Performance Bond Form
Therefore, the Bidder hereby proposes to furnish all supervision, technical personnel, labor,
materials, tools appurtenances, equipment, and services (including all utility and transportation
services) required to construct and complete the Work, all in accordance with the above listed
documents.
Bidder agrees to perform all of the Work and provide the equipment and materials described in
the Bid Documents, as follows:
Bidder has bid on all items and has provided a price for all items.
The Bidder will complete and provide all labor, equipment, materials and mobilization (if
applicable) to perform the Work as incidental to the fixed item price for each item proposed.
Village of Mount Prospect Section 004005 April 2019
Rehabilitation of 1,000, 00 Gallon Station 5E,
Ground Storage Tank Page I of 3
SECTION 004005 — BID FORM: continued
In submitting this bid, the Bidder understands that the Village of Mount Prospect reserves the
right to add to or subtract from the estimated quantities.
The Village of Mount Prospect intends to award one (1) contract (if at all) for the items bid. If
written notice of award of this bid is mailed, emailed or otherwise delivered to the Bidder at any
time before this bid is withdrawn, the Bidder agrees to execute and deliver the contract in the
4-11
prescribedi
form and furnish payment and performance bonds, or letter of credit, and the
insurance certificates required by the Bid Documents to the Village within ten (10) days after
receipt.
The Bidder, and as successful bidder/Contractor upon award of the Contract understands and
agrees to the following:
1) The Contractor agrees to provide all Work and items and material to the Village as noted in
the Bid Documents and comply with the requirements of the Bid Documents.
2) The Contractor agrees to comply with all applicable state and federal laws, rules and
regulations, and county and municipal ordinances, as described in the General Conditions.
All Addenda pertaining to this project shall be acknowledged by the Bidder in the spaces
provided below:
Addendum Addendum Acknowledgement by Bidder or Date
No. Date Authorized Representative Acknowledged
Ap��-29PoItpl, Y�?S6C 1"4 LA -0 per L 2 1Y, 2- 0 1v9
7
2 May7, 2Q/q llwseel M*OV1.A::)
��. 7, 20.9
Failure to acknowledge receipt, as provided above, may be considered sufficient grounds for
disqualification of the bidder and rejection of his/her bid submittal. A record of all Addenda and
copies of same will be available to all qualified bidders from the Village of Mount Prospect
Public Works Department, 1700 West Central Road, Mount Prospect, Illinois two (2) days prior
to the letting. It shall be the bidder's responsibility to become fully advised of all Addenda prior
to submitting its bid.
Upon award the contract the Village will send Notice of Award to the successful bidder, the
bidder must then execute the contract and provide the required bonds or letter of credit and
certificate of insurance to the Village within ten (10) days. The Village will then issue a written
Notice to Proceed which starts the performance period. The contractor shall reach substantial
Village of Mount Prospect Section 004005 April 2019
Rehabilitation of 1,,000,000 Gallon Station 5E
Ground Storage Tank Page 2 of 3
completion by 60 catend4r da�vs, after the, d,ate of fli,eNotw"e,, to ProceW with fin,al COMPlet,100
00 000, 001
b 75 calendar dgn,after, the date of the'Notice to Pr-ote;ed'. Substantial completion shall be
0,00 MOON*#
defined as the completion of all work except for site restoration. Failure to complete the work in
the designated time frame may result in the Director of Public Works withholding compensation
due the contractor for failure to complete the said work in the designated time frame, calling the
bonds, or taking such other action as may be available.
Security in the sum of ten (10%) percent of the amount bid in form of (check one):
I I *d Bond
d Cert*fieCheck
Bi Bank Cashier's Check
�ts attached, hereto in accordance with the "Instructions for Bidders".
1) Bid Form
2) Affidavit — Bid Certification Form
3) Bid Security
4) Bid Sheet(s) — Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
Name of Firrn/ffidder: VJr T7 pATn Tj176_,f /_ LC
--A .... ... . . ......
tle.
A
04 z
Official Address: ...........
Z.
. .. . .......... . . . . . .....
OF
IMF
Telephone: 2ZI9—zo��7=_
op,
Emai ,,Valn �4!!7,4ne - tr VlAe
ONE (1) SIGNED COPY OF THIS BID FORM AND BID SHEETS ALONG WITH THE
AFFIDAVIT —BID CERTIFCATION FORM, AND BID SECURITY SHALL BE
SUBMITTED IN A SEALED MARKED ENVELOPE.VILLAGE OF MOUNT
Village of Mount Prospect Section 004005 April 2019
Rehabilitation of 11,000,,000 Gallon Station 5E
Ground Storage Tank Page 3 of 3
Section 004015
BID SHEET
of 1&003000 Gx�allon S-tafl'on 5E C -agx
.1,.roundStot g-1gok
IL IT PRICES: For providing, performing, and completing all work, the sum of the products
resulting from multiplying the number of acceptable units by price per Unit.
WAM
Item
Approx.
No.
Description
Unit
Qty. of Price Per Unit
Extension
Units
I
Mobilization
L. Sum
1 4?01000
120, t 0 0 `�'
2
Interior Coating Rehabilitation
L. Sum
I I Coo
2 6/ 404040
3
Exterior Coating Rehabilitation
L. Sum
1
/0401 oat�",
4
Steel Work & Miscellaneous Repairs
L. Sum
I 22tOc
2)
5
Electrical Work
L. Sum
4. ,C"�
''
6
Tank Disinfection
. .................
L. Sum
I
7 Site Restoration L. Sum I
F
8 Contingency —flan Hours for Additional Work Hour 40 e6
P A
Total Bid= 00
L The Owner has the ability to add any or all of the following alternates to the Total
Bid, or each Bid Item independently. Complete Alternate Bid Items Table as
Indicated:
ItemApprox.
No. Item & Description 'Unit QtY. of Price Per Unit Extension
Units
j
Exterior Coating w/ Full Blast: add or deduct
L Sum
LA from Base Bid Item 3
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,1000 Gallon Station 5E
Ground StorageTank Page 1 of 4
TOTAL BASE BID
TOTAL BASE BID PRICE (the sum of extensions of the Bid Sheet):
ge, acurge�N�,��t�^r0) rs, and -C Cents
(In writing) (In writing)
�It�l �+�� Dollars and Cents
(In figure) (In figure)
TOTAL ALTERNATE BID
TOTAL ALTERNATE BID PRICE (the sum of extensions of the Bid Sheet),,-,
ewe Dollars and
221!2
( In writing) &-r"
e-1
.4Z Q �� ��� Dollars and
(In figure)
Cents
(In writing)
AO Cents
(In figure)
Village of Mount Prospect Section. 00401.5 April 2019
Rehabilitation of 11,000,1000 Gallon Station 5E
Ground Storage Tank Page 2 of 4
Itis expressly understood and agreed that:
1. The approximate quantities set forth in this Bid Sheet for each Unit Price Item are Owner's
estimate only, that Owner reserves the right to increase or decrease such quantities, and that
payment for each Unit Price Item shall be made only on the actual number of acceptable
units of such. Unit Price Item installed complete in place, measured on the basis defined in
the Contract.
2. Owner is not subject to state or local sales, use and excise taxes and no such taxes are
included in this Bid Sheet.
Specific cash allowances, if any, are included in the price set forth above and have been computed in
accordA nce with paragraph 11. 02 of the General Conditions.
BIDDER agrees that the Work will be Substantially Completed in 60 c tis,ecut ive calendar days from the
date of "Notice to Proceed" and Finally Completed in 15 calendar days thereafter.
BIDDER accepts the provisions of the Agreement as to liquidated damages in the event of failure to
complete the Work within the times speed in the Agreement.
(a) Required bid security in the amount of ten percent (10%) of the Bid in the fon-n of a bid
bond, cash, certified check, cashiers check or bank money order as stipulated in the
Advertisement for Bids.
(b) A tabulation of subcontractors, suppliers and other persons and organizations required to be
identified in this Bid.
(c) Required BIDDER's Qualification Statement with supporting data.
Written communications concerning this Bid shall be addressed to:
Village Of Mount Prospect Section 00401.5 April 2019
Rehabilitation of 1.0005000 Gallon Station 5E
Ground Storage Tank. Page 3 of 4
The terms used in this Bid which are defined in the General and Supplementary Conditions of the
Construction Contract, included as part of the Contract Documents, have the meanings assigned to them
in the General and Supplementary Conditions.
A
Submitted on , M AVOOOP 201
State Contractor License Number (IM
10;'iITIIIIIJ�111 A
I FIIIkIIIWII
/S
Address:
Telephone:
-
01-M Arm
Village of Mount Prospect Section 004015 April 2019
Rehabilitation of 1,000,,000 Gallon Station 5E
Ground Storage Tank Page 4 of 4
Section 001.1-53
BIDDER'S QUALIFICATION STATEMENT
Pro ect Name: Rehabilitation of 1000 000 Gallon Station 5E Ground Storage Tank
RUMINNIN
Village of Mount Prospect
Village Manager's Office, Third Floor
Emerson
Mount Prospect, IL 60056-2229
SUBMI"I'TED, BY;,
Company F C;
41-r-I� I L�'
Name VAS051 �}'l�Li��
Address
<.#,$$� [�rPRlt7�•�'�y�T-
Principal Office o¢s,e e _ /1�
Corporation, partnership,, individual, joint venture, other
L L � -
Contractarlicense number and state
EXPERIENCE STATEMENT
I - Bidder has been engaged as a General Contractor in construction for - 1-7--, years and
has performed work of the nature and magnitude of this Contract for, 1 -07 years.
Bidder has been 'in business under its present name for / -7 years.
2. Bidder now has the following bonded projects under contract: On a separate sheet, list
project name, owner, engineer/architect, amount of contract, surety, and estimated
completion date.
3. Bidder has completed the following three (3) contracts consisting of work similar to that
proposed by this Contract: On a separate sheet,list project name, owner,
engineer/architect, amount of contract, surety, and date of completion and percentage of
the cost of the Work performed with Bidder's own forces.
4. Has Bidder ever failed to complete any project? If so, state when, where, and why. All -10
5. Bidder normally performs the following work with his own forces:
6. Construction experience of key individuals in the organization Is as follows (continued on
attached sheets if needed):
7. In the event the Contract is awarded to Bidder, the required surety Bonds will be
furnished by the following surety company including name and address of agent:
Village of Mount Prospect Section 001153 April 2019
Rehabilitation of 1,10 0,000 Gallon Station 5E
Ground Storage Tank Page 1. of 2
INN:
FINANCIAL STATEMENT
Bidder possesses adequate financial resources as indicated by the following:
a. Assets and Liabilities: Attach a financial statement, audited if available, including
Bidder's latest balance sheet and income statements showing the following items:
(1) Current assets (cash, joint venture accounts, accounts receivable, notes
receivable, accrued income, deposits, materials inventory, and prepaid
expenses).
(2) Net fixed assets.
(3) Other assets.
(4) Current liabilities (accounts payable, notes payable, accrued expenses,
provision for income taxes, advances, accrued salaries, and accrued payroll
taxes).
(5) Other liabilities (capital, capital stock, authorized and outstanding shares par
values, earned surplus, and retained earnings).
(6) Name of firm preparing financial statement and date thereof:
If financial statement is not for identical organization named herein, explain relationship and financial
'bility of the organization furnished.
responst 1
8. Current Judgments: The following judgments are outstanding against Bidder:
Jud&Yment Crcdi.,torsWhere Docketed and DateAmount
a.
b.
Bidder hereby represents and warrants that all statements set forth herein are true and correct.
(OFFICIAL SEAL)
Name of Organization:
(If Bidder is a partnership, the partnership name shall be signed, followed by the signature of at least one
of the partners. If Bidder is a corporation, the corporate name shall. be signed, followed by the signature
of a duly -authorized officer and with the corporate seal affixed).
END OF SECTION 001153
If,
Village of Mount Prospect Section 001153 April 2019
Rehabilitation of 15000,000 Gallon Station SE
Ground Storage Tank Page 2 of 2
V & T
29585 Gramercy Court* Farmington Hills, Michigan 48336
Phone: (248) 497-1494 0 Fax: (248) 426-9147'8 E -Mail: vandfpainting@aol.com
V & T Painting, L.L.C. was founded in February of 2002. It specializes in heavy industrial rehabilitation of
elevated and ground wafer storage tanks, stadiums,, and water treatment plans, along with other
miscellaneous structures. The company has over 14 years of experience in sandblasting, welding, pit filling,
priming, and painting of steel and other materials.
Southwest Regional District
Blasting interior and Exterior of a 300..000 g Multi Legged tank with Containment. Minor metal Repair
Southwest Regional DistricY
Neil bond
265=0
Town Of Flora, IN
Interior and Exterior Blasting/ Repainting one 200,000 9 Multi- legged tank. Interior blasting/ repaint and exterior
overcoat of one 150,000 9 spheroid. Installation of two solarbee mixing system. Metal Repairs
Wayne Boyer
(317) 694-2585
Commonwealth engineering
391,000
Borough of Pottstown, PA
interior and Exterior Blasting and Repainting of 200,000 g Multi legged tank. Metal Repair
Alan Wong
(610) 313-3100
BCM Engineers
Jobs previously Done In wisconsin in 2018
Kaukauna, Wisconsin
Sandblasting interior and exterior of 500,000 gal Hydropillar Tank With Containment. Misc Metal repair
(Lead Abatement)
Project pricing $464,000
McMahon Enciineering
Jeffery A. Kellner, P.E. (920) 428-7845
Chilton, Wisconsin
Sandblasting interior and exterior of 200,000 gal spheroid with Containment. Misc metal repair. (Lead
Abatement) Project Pricing $260,000
McMahon Engineering
Jeffery A. Kellner, P.E. (920) 428-7845
Fox Crossing, Wisconsin
Sandblasting Interior and Exterior Repaint of 300,000 gal Spheroid Water tank. M11sc metal repair
Project pricing 198,000
McMahon Engineering
Jeffery A. Kellner.. P.E. (920) 428-7845
Experience
Danville Municipal Water Authority 2015
interior and exterior blast ing/repoli ntin g of (2) 1.5mg ground storage water tanks with containment. Coatings
contained lead. Installed and furnished 2 Solar Bee mixing systems, as well as the installation of underground
piping and electrical work. Projectis located in Danville, PA.
Gannett and Fleming, Inc.
David Averso, P.E. (717) 645-6771
I U*M-74 I a I - - I
KITP
Interior and exterior blasting/re-painting of (2) 1 mg ground storage water tanks with containment. Included
miscellaneous metal repairs. Project is located in Tamaqua, PA.
Gannett and Fleming, Inc.
David Averso, P.E. (717) 645-6776�
Town of Bargersville
interior and exterior blast i ng/re-pai ntin g of a 500,000g multi -legged elevated water tank with containment.
Included miscellaneous metal repairs, Project 'is located in Bargersville,, IN.
Strand & Associates
Ryon Mackos, P.E. (812) 372-991
HME611111 MO,
2015
interior and exterior blasting/re-painting of a 30O.-OOOg elevated spheroid water tank with containment.,
Coatings contained lead. Included miscellaneous metal repairs. Project is located in Chilton, WI.
McMahon Engineering & Architects
Jeffery A. Kellner, P.E. (920) 428-7845
Southwest Cambria County Water Authority 2015
Interior and exterior blasting/re-pal"nting of a 300,000g ground storage water tank and a 170,000g ground
storage water tank with containment. Coatings contained lead. Included miscellaneous metal repairs. Project
is located in Johnstown, PA.
The EADS Group
Mark J. Muir (814) 535-5389
,IT# Me IV -
2015
Interior and exterior blasting/re-painting of a 300..000g elevated spheroid water tank with containment.
Included miscellaneous metal repairs. Project is located in Elkhart Lake, Wl.
Kapur & Associates, Inc.
Donald P. Albright, P.E. (414) 351-6669,
Downingtown Municipal Water Authority 2015
Interior blasting/re-painting and exterior re-painfing of a 2mg ground storage water tank. Installed and
furnished a mixing system. Coatings contained lead. Projectis located in Downingtown, PA.
ATC Group Services, L.L.C.
Charlie Liu., P.E. (610) 313-3100 ext. 307
Southwest Regional Water District 2014/2015
Interior and exterior blasting/re-painting of a 250,000g multi -legged & a 150,000 multi -legged elevated water
storage tanks. Included miscellaneous metal repairs. Projects are located in Oxford and Hamilton, OH.
Southwest Regional Water District
Norma T. Pennock, P.E. (513) 461-3483
wiMIF1,11 M&I Irm
2014
interior blasting/re-painting of (2) 500,000g multi -legged elevated water tank. Included miscellaneous metal
repairs. Project is located in Monticello, IN.
Monticello Water Superintendent
Rod Pool (574) 583-2334
Hampton -Shaler Water Authority 2014
Interior and exterior blasting/re-painting of a 400,000g elevated water tank with containment. Also, interior
blasting/re-painting and exterior re -painting of a 200,,000g stand pipe. Lastly, interior blasting/repainting and
exterior re -painting of a 300,,000g ground storage water tank. All included miscellaneous metal repairs. Project is
located in Allison Park, PA.
KLH Engineers, Inc.
Robert Horvat,, P.E. (412) 494-0510 ext. 149
City of Sandusky
2014
Interior and exterior blasting/re-painting of a 300,000g multi -legged elevated water tank with containment.
Included miscellaneous metal repairs. Project is located in Sandusky, Mi.
Townley Engineering, L.L.C.
Christopher Townley,, P.E. (810) 404-2266
City of New Lothrop
2014
Interior and exterior blasting/re-painting of a 300,000g multi -legged elevated water tank with containment,.,
Included miscellaneous metal repairs. Project is located in New Lothrop, Mi.
Spicer Group,, Inc.
John E. Olson, P.E. (989) 754-4717
Town of Pierceton
2013
Interior and exterior blasting/re-painting of a 200,000g multi -legged elevated water tank with containment.
Included miscellaneous metal repairs. Project is located in Pierceton, IN.
GRW Engineering, Inc.
Alex White, P.E. (317) 347-3650
City of Monticello
2013
Interior and exterior blasting/re-painting of a 500,000g multi -legged elevated water storage tank. Coatings
contained lead. Included miscellaneous metal repairs. Also, furnished and 'Installed valve house and
underground pipe work. Project is located in Monticello, IN.
Monticello Water Superintendent
Rod Pool (574) 583-2334
Town of Bargersville
2013
Interior and exterior blasting/re-painting of a 500,000g multi -legged elevated water tank with containment.
Included miscellaneous metal repairs. Project is located in Bargersville, IN.
Strand & Associates
Ryon Mackos, P.E. (812) 372-9911
M
Southwest Water Regional District 2013
Interior and exterior blasting/re-painfing of a 300,000g, ground storage water tank with containment. Included
miscellaneous metal repairs. Project is located in Millville, OH.
Southwest Regional Water District
Norma T. Pennock, P.E. (513) 461-3483
2013
Interiorand exterior blasting/re-painting of a 400,000g, hydro -pillar elevated water storage tank with
containment. Coatings contained lead. Included ext,ens"We metal repairs (i.e. $90k in total repairs). Project is
located in Wadsworth, OH.
City of Wadsworth
James M. Bozigar, P.E. (330) 335-2738
Board of County Commissioners of Lake County 2013
Interior and exterior blasting/re-painting of a 750,000g elevated spheroid water storage tank with containmen
Included miscellaneous metal repairs. Project located in Lake County, OH. I
Burgess & Niple, Inc.
Jeffrey Marnicio, P.E. (440) 354-9700 ext. 3295
QID
Interior and exterior blasting/re-painting of a 200,000g multi -legged elevated water storage tank with
containment. Included extensive metal repairs. Project located in Oakland County, MI.
Oakland County, MI
Carmelo Moyet, Jr., P.E. (248) 452-2031
City of Menomonee Falls
2012
interior and exterior blasting/re-painting of a I mg multi -legged elevated water storage tank with containment.
included miscellaneous metal repairs. Project located in Menomonee Falls, WI.
Strand Associates
Steven B. Kluesner, P.E. (608) 251-4843
Bucks County Water Authority 2012
Interior and exterior blasting/re-painting of a 500..000g elevated spheroid water storage tank with containmen
Included miscellaneous metal repairs. Project located in Bucks County, PA. I
Carrol Engineering
V
Lane Badley (215) 343-5700 ext. 307
City of Patriot 2012
interior and exterior blasting/re-painting of a 200,0009 stand pipe with containment. Included miscellaneous
Metal repairs. Project located in Patriot, IN.
Strand Associates
Bruce Rape (608) 347-2607
City of Reynoldsburg
2010
interior and exterior blasting/re-painting of a I mg, elevated hydro -pillar water storage tank with containment.
Included miscellaneous metal repairs. Project located in Reynoldsburg, OH.
Strand Associates
Sean Halyard, P.E. (614) 835-0460 ext. 5028
City of Green Bay
2010
Interior and exterior blasting/re-painting of a 750.,000g elevated spheroid water storage tank with containment.
Included miscellaneous metal repairs. Project located in Green Bay, W1.
McMahon Engineering
Jeffery A. Kellner, P.E. (920) 428-7845
North Wales Water Authority
2010
Interior and exterior blasting/re-painting of a 2mg 95 -foot high stand pipe with containment. Coatings
contained lead. Included miscellaneous metal repairs. Project located in North Wales, PA.
Carrol Engineering
Brad Fisher (215) 343-5700 ext. 303
Southwest Regional Water District 2008-2011
Five separa,te multi -legged elevated water tanks. All required interior and exterior blasting/re-painting with
containmr nt and some open blast without containment. All included miscellaneous metal repairs. Projects
located throughout the Southwest Regional Water District in Ohio.
Southwest Regional Water District
Norma T. Pennock, P.E. (513) 461-3483
Please Inquire If Interested in seeing a list of the more dated projects
Autos, Building & Equipment
* Two stake trucks
o Ford F-450
o GMC 8500
o Fleet of eight pickup trucks
Fork Lifts
* Two 60001b. rough train
* One 5000 shop fork lift
7000 square -foot warehouse. Includes garage and office space with fenced in storage yardV
24061 W. Eight Mile Rd.,, Southfield MI
* Three 8 -ton pots with accessories
01 Two welding machines
o Big Blue Miller 400p
o Tri -Blazer with LIP gas
o, Three trailers
o 30 foot box trailer
o Two 24 -foot box trailer
o Two 24 -foot flat beds; 24,000 lb. GVW
* Three 1600 CFM air compressors with moisture separators and aftercoolers
* Three air compressors
* 375 CMF
* 750 CMF
* 900 CMF
0 16 spider baskets (ST -17)
Two Bossun chairs
Two sets of containment for 1 million gallon elevated water tanks
Four "air stage" pneumatic motors
Four "electric stage" motors
Two 40,000 CFM dust collectors
Eight 10 -foot rigging stages
Eight fold over 10 -foot stages
Exterior rigging for three 1 -million gallon tanks
Three sets of tools for three crews of 6 men each
Ile Two steel grit recycling machines
Three air to winches
Six heavy duty Super Kings spray pumps
All necessary safety equipment and rigging for three crews of 6 men each
Additional rental equipment available if necessary for back up
0
Key Personal
Vasel Malai is the owner -member of V 8x T Painting, L.L.C., which was established in February of 2002. He
is a licensed CDL driver, as well as a licensed and certified welder. He has over 20 years of experience within
the industrial coatings field,
Poulin Vukaj is also a licensed CDL driver and a Schoolcraft College licensed welder. He has over 14
years of experience in all operations of painting and sandblasting.
M
RMUN MIMI
Date: May 7, 2019
Project Name: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank Project
Project No.: 114311
This Addendum forms a part of the Contract described above. The original Contract Documents and an
prior Addenda remain in full force and effect except as modified by the following which shall take pree
dence over any contrary provisions in the prior documents.
1. Contractor to relocate Automatic Meter Reading (AMR) antenna on tank prior to construction.
lead present in current coating system?
Page 3 of TIC -s report details the results of the heavy metal tests. TIC 's testing determined the
exterior coating system contains 817 mglkg, or 0. 0 817% of lead.
3. What is the size and configuration of the inner roof beams.?
Beam quantity and sizing is listed on pages 4 and 5 of TIC's report.
4. What is required for partial beam replacement? Can it be bid as a unit price item?
$ection 012000 states what is requiredfor partial beam replacement. These requirements have
hqen updated as stated below. The pay item will not be bid as unitprice and will remain as a
lump sum item.
SPECIFICATIONS:
1. 012000 Measurement and Payment; Section 1.03 Part B: Partial Beam Replacement— Pay Item
Ao. LB
f
a. Update requirements listed under Partial Beam Replacement to include the following:
i. Center support ring
ii. 20 inner roof beams
20 outer beam ends
iv. Caulk all joints 1/2" or smaller between the roof and beams with Sika Flex 11
b. Remove requirement for replacement of 24 inner roof perlins.
Each Bidder shall acknowledge receipt of this Addendum by affixing their signature below, by noting this
Addendum on their Bid Form, and by attaching this Addendum to their Bid.
Bums & McDonnell Engineering Company, Inc.
1431 Opus Place, Suite 400
Downers Grove, Illinois 60515
Village of Mount Prospect 009100-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
00'91 00 —ADDENDUM NO. 2: continued
ACKNOWLEDGEMENT
The undersigned acknowledges receipt of this Addendum and the Bid submitted is in accordance with in-
formation,, instructions and stipulations set forth herein.
0"
Bidder: V17:)CV11�1i /.7 140f
tri
ate: 7,o
END OF 00 9100
Village of Mount Prospect 009100-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
00 9100 — ADDENDUM NO. 1
Issued to All Bid Document Holders of Record
Date: April 29, 2019
Project Name: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank Project
Project No.: 114311
This Addendum forms a part of the Contract described above. The original Contract Documents and any
prior Addenda remain in full force and effect except as modified by the following which shall take prece-
dence over any contrary provisions in the prior documents.
ADDITIONAL INFORMATION:
1. Update Evaluation of the 1,000,000 Gallon Steel Ground Storage Tank "Tank 5E (South Tank) "
Mt. Prospect, Illinois by Tank Industry Consultants on September 13, 2017
Each Bidder shall acknowledge receipt of this Addendum by affixing their signature below, by noting this
Addendum on their Bid Form, and by attaching this Addendum to their Bid.
Burns & McDonnell Engineering Company, Inc.
1431 Opus Place, Suite 400
Downers Grove, Illinois 60515
ACKNOWLEDGEMENT
The undersigned acknowledges receipt of this Addendum and the Bid submitted is in accordance with in-
formation, instructions and stipulations set forth herein.
Bidder:
ME
Date:
END OF 00 91 00
Village of Mount Prospect 0091 00- 1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
UPDATE EVALUATION OF THE
1,1000,000 GALLON STEEL GROUND STORAGE TANK
,September 13,1 20,17
17.105,5.H373.006
rN
ct'r 6
T'l
i
TANK
SUBJECTO
bMUSTRYThe
.
subjectCONSULTANTS f report is the update field evaluation the 1,31000 � gallon.
steel r� t r g t t. Pros t 1 i. T.e t f was owned by Mt.
Prospect Public Works was knows as the "'Tank 5 (South, Tank)." e
field evaluation .s performed September 13 , 2 ' y Gregory P. Cannon,
7740 '
Indiana Indiana 46214
ACE Certified Coating Inspector Level 3 C rt1 at N'. 10339 and Jamie
317 / 271 -3 100 - PhoneL.
St NAGE CoatingInspector Level. 1 Garb � rtincat No. 64809.
.:: 317 271-3300 - FAX,
The Owner's representati,ve on the site at the time of the Feld evaluation was
Jay Gomez. The tank was previously evaluated by Tank Industry Consultants
on November, 25 and 26 2013. Tank Industry Cronsultants prepared. a Request
for Proposfor replacement oftbe roof stiffener across the rood center hub I ,
2014. dome roof tank was, welded steel construction. According t
Sacramento California
information on the tank nameplate,the, tank was construicted 'in 1966 b
916 717-3608 -3608
Chicago Bn*dge & Iron Company under contract number -4105. The tank
nameplate .l ' indicated the tank. was - ft in diameter and had a, height of
Plainfield, Iffinois
3 2: ft.
8,1 556-8335
Pittsburgh, yt , .i
OBJECTIVE,
12 262-1586
The purpose of tb,is wash.out and updateevaluation was to determine.
El Paso, Texas
changes in the condition of the tarok inten*.or, exterior, visible foundation, and
915 790-0,790,
.
site the time the last evaluation,., The purposthis repoit '
t resent the findings of the evaluation and t .ke recommendations fog°
Houston, Texas
recon inn, repairing, corrosion protection, and maintenance. Budget estimates
281 3,67-3511
for the work, anticipated life of the coating the structare,and the
replacement ent cost of to tank arealso included.
AUTHORIZATION,
I , washoutt, evaluation, disinfection, and report were authorized the.
Village of Mount Prospect Purchase Order 2017-00000218 .ted February 13,
2 1 .
EXECUTIVE
The e t rl oar coating system appeared to fair to good ovr ll condition as
isolated areas of peeledtop'coating and corrosion were noted. The exterior
surfaces should not need to be r t.t within the: next 3 to 5 years tom
corrosion standpoint. The exterior should be re-evaluated in 3 to 5 years i
accordance with MWA recommendations to determine a more precise
recoating schedule.interior suifaces of the tank should be repainted
within the next 2 to 3 years due to rafter corrosion corrosion above the
high water level.
dn Employee- Owned Company
11 000, 000 Galn Ground Storage Tank, "Tw7k 5E (South. Ta7lk) Page 2
Mt. Pros
pect Public Works, Mt. Pct, 111111015 I 7,055.H3 73.006
ANS1/0SHA iand Safety -Related Deficien,cies: There were OSHA and safety-related deficiencies
observed on this tank'. These deficiencies included,,. -
the n"cal equipment in ine valve vault did not appear to include ground fault interrupt circuit,
the exterior ladder width was too small (29 CFR 1910.23(b)(4)),
the sa,fe-climbing device on. the exterior ladder was cracked (29 CFR 1910.29(i)(6)),
Cne safe -climbing device, did, not extend over the entire length, of the ladder (29 CFR
1910.28(b)(9)(il)(A))
the roof safety raiii ng was not, equipped with a self-closing gate (29 CFR 1910.28(b)(3)(Iv)),,
0 the gaps between the toe 'bar and roof exceeded the m,axiallowed 1/4 in (29 CFR
1910.29(k)(1)(iii)), and
0 the roof safety railing handrail did not meet OSHA loading requirements, (29, CFR 1910.29(b)(3)).
If the Owner wishes to ffilly comply with, OSHA and safety-related standards,,,recormended tbat
UL
these deficiencies be rectIfied.
AWWA Sanitary, and Operational Defiel"ency: There was an AWWA sanitary, and operating
deency observed on this tank as well..
iv, there was an approximate 1/2 in. wide gap between the overflow pipe and flap gate.
This deficiency should be corrected.
The safety-related, sanitary, and, operafing deficiencies listed aboveare not 'intended to be a complete
list of deficiencies on this tank. The Owner should refer to the complete report text of the previous
report, this report., and accompanying
photographs for a complete account of al,l observed defici,encies.
This evaluation and the ire portin,g the condition. of this tank, do not warrant the original structural,
condition of the, tank or any ofthe original desi,gnfor seismic loadings, Likewise, recommendations
for this tank do not incl.de modifications which may be required for coinliance with present sru
tctural
p
codes.
Color ' ' aphs were taken of the visilble portions of"the foundation, the tank interior, and eXterio
pnotogr
and are included as a part of this report.,
A 'I"
Will
Warniba: Some appurtenances on thlk tank may be referred to as erection or riggm"g
attachmentsl lug,s, or brackets,. This does not mean that they are safe for r1*ggM"g,. Each
attachment for each tank should be evaluated on an M*dl*vl*dua,l. basisby a structural englinter or
i a b�efore bem*g� used., These deAces may have been M*tended for onl the
an experienced riggex y
origm*.al erectors and painters use with specialized e,qul*pmen,t.
1, 000, 000 Gallen Ground Storage Tan,lf, ft Tank 5,E (South Tank) Page,3
Alt. Prect Public Works, Mt. Prop pecl, Illinois I 7.055-H3,73. 00'6
All adhesion tests performed during this evaluation were done'in general, accordance with ASTM
D3359. The esult's are reported herein using the ASTM. scale., The ASTM scale is a relative scale to
rate a from 10 to 5 with 5, being the best. A table of adhesion test result's classification is
included with this.
Samples of' the exterior and Interior coating systems, were YAM to a laboratory flor atomic absorption
Iff . 0 1
-ious evama,no .
analyses atthe time of the prev" n Th e test results were as follows:
_1_g�rcent W
<0.0025%
'I L
<0.025%
Tank hidustry Consultants performs, this test only to determine if there is lead, cadmium) or, chromium
present in the coating samples. To limit damage to the e,xisting Coating, only small areas were tested.
'The small. number of samples taken and the difficulty of retrieving all primer from the steel profile may
cause the tests performed to, not accurately represent the total'. coating system. Variations in thickness,
types, of coatings applied, and the interim cleaning and painting operations will also, affect the actual
readings. The reliability of the results is also dependent on, the amount of' primer included in the
sample. Additional testing to determine the amount of leaebable contaminants present in the spent
cleaning debris will need to be performed following cleaning operations at the time of repainting.
T'he condition of the items not referred to in the OBSERVATIONS section of this �report appeared to bi
in pproximately the same condition a,s, they were at the time ofth e last evaluation I
a
"T,; and Site
The tank site, 'surrounding area, and valve vault were in similar condition as was observed at th
previous evaluati,on. The condition of the foundation hiad worsened, s1ightly, as additional cracking wa
observed., Coating oversprayand mildew were observed on, t,he foundation. Widespread cracking an
0
di,sloanci I ing were observed 'in the sealant at the foundation -to -bottom plate interface.
1P OOOP 000 Gallon Ground Storage Tank, "Tank 5E (South Tank) Page 4'
mt. ecPublic Works, Mt. Prospect, Illinois I 7.055.,H373.006
ffl,
I I GSm"
.................
EXTERIOR COATING AND METAL, CONDITION (changes.froin the, previous report ar�e bolded)'
... . ........
Adbesion 5 (very good) T = Topcoat to, Underlyinting Neg. __ negligible
4 (good)
3 (fair) S = Primer to, Steel
2 (poor)
I (very poor)
0, (very poor)
w 0 d
9P
dip
C. Interior Surfaces
ROOF SUPPORT STRUCTURE:
Stiffeners:
Outer: 3 3
Inner: 20
Size: 3-1/2 in. x 3 In. x 1/4 in., angle
Center Hub.:
Constructiom approx., 6 in. x 4 in., x 3/8 in., angle
Diameten ap
prox., 1.5 ft
Circ -um ferential Stiffener-. 6, in. x 4 in., x 1/4 in. angle
Coat1�g Tbickness
�tpp,rox. % Failure to Metal Loss
I
Range Typical
Underlyfiig Adhesion
Rust i Typical Deepest
Coating
Shell
.5 mils, to, 17 mils 10 mils
/2%
< 1/2% 5 SNerr. Neg.
5
Ro,of
10 mils to 23 mils
1,4 mils
Neg.
< 1, /2 4 S Neg,. Neg.
... . ........
Adbesion 5 (very good) T = Topcoat to, Underlyinting Neg. __ negligible
4 (good)
3 (fair) S = Primer to, Steel
2 (poor)
I (very poor)
0, (very poor)
w 0 d
9P
dip
C. Interior Surfaces
ROOF SUPPORT STRUCTURE:
Stiffeners:
Outer: 3 3
Inner: 20
Size: 3-1/2 in. x 3 In. x 1/4 in., angle
Center Hub.:
Constructiom approx., 6 in. x 4 in., x 3/8 in., angle
Diameten ap
prox., 1.5 ft
Circ -um ferential Stiffener-. 6, in. x 4 in., x 1/4 in. angle
Ix 0100Y 000 Gallon Ground Storage Tank, "'Tank 5E (South Tank) Page 5
Mt. ProTeet Public Works, Mt, Pr� ect, Illinois I 7055.H3 3.X06
CATHODIC PROTECTION.-
Anode
Type.- submerged wire w/ floats
Nurnber: I
Reference Electrode:
Nr: I
Location-. west perimeter
INTERIOR PIPING:
Ifflet/outlet Pipe:
Size: 16 in. diameter
Projection: 6 in. above floor
Reinforcing Pad: 26 in. diameter x 0,343 in. to 0.346 in. thick
Protective Coven none
6
Pipep
Size: 30 in. diameter
Projection.- 4, in. above floor
Reinforcing Pads 3 0 in.diam, eter x 0.355 in. to 0.358 in. lick
Protective Cover: none
Sum �
P.
Size: 24 in. diameter
flanged
Size: 32 in. diameter x 0.,543 in. to 0.548 in. thick
Depth: 9 in.
INTERIOR COATING AND METAL CONDITION (additioninforination from the pr,evious report
i,s bolded):
Key, toTable
Adhesion 5 (very good) T — Topcoat to Underlying Coating Neg., = negligible
4 (good),
31 (fair) S imer to Steel
2 (poor)
I (very poor)
0 (very poor)
The previous evaluation of the tank interior below water level was performed using an ROV, and the
roof support structure was evaluated using a raft. Therefore, additional dimensions 5 infonnation, and
,'I
data concerning tne condition of tie surfaces below the water level, reviously available, are
included, in. tis report.
Coating'Thickness
RAB, MMdml!1�111I
Wn
9
Metal -, Loss,
12 mi'"Is to 26.5 mils
Im
Key, toTable
Adhesion 5 (very good) T — Topcoat to Underlying Coating Neg., = negligible
4 (good),
31 (fair) S imer to Steel
2 (poor)
I (very poor)
0 (very poor)
The previous evaluation of the tank interior below water level was performed using an ROV, and the
roof support structure was evaluated using a raft. Therefore, additional dimensions 5 infonnation, and
,'I
data concerning tne condition of tie surfaces below the water level, reviously available, are
included, in. tis report.
17 000, 000 Gallon Ground Storage Tank, "Tank 5E (South Tank) Page 6
Mt, Prospect Public Works, Mt. Pro�pect, I1117701S 17.055. H3 73'. 006
SIRMINI
IT I
7.
TX� , TMFL
ob
'M; Foundation and Sits
1. Site Maintenance - The site should be regraded so that the top of the foundation, projects a
minimum of 6 in. to, a maximum of 1.2 in. above grade and so that proper drainage away from the
foundation continues. Site maintenance should be performed w'th, the mower discha�rge directed away
-Erom. the ba,se of the tank to prevent rock chips in the co,atm"g and the: accumulation of grass on the
foundation and bottom plate.
2. Tank and Site Security: 'Water tanks have been defined by some courts under, certain
circumstances as attractive nuisances,. As such,, there may be a significant ial liability to the
Owner for injury to persons on the to and tank site, even if access is not authorized. Recent events
have prompted the entire water industry to consider measures that inhibit intentional acts that, could
threaten the water supply. A review ofthe security requirements for tie tank and site is recommended
For their
to corm that the exi,sting measures, are consistent with the Owner's security requirements f
water system. P,rimary tank and site security should be faed on eliminating, preventing, and,
detecting unauthorized access to the tank. Such security measures might include routinely and
periodically verifying all manholes and gates are locked, and all exterior access points have suitable
deterrents. Other security measures might include installing site ligbtl,ng', alarms on manholes and
gates, motion detectors, and surveillance cameras, and arranging more Sequent site visits by law
enforcement agencies,.
I Foundafi*an: When. the tank exten'or "is, repam,ted, any unsound concrete should be chipped
to, sound material and tibe concrete should be brush-off blasted. Any deteriorated areas, or voids found
11P 000, 000 Gallon Ground Storage Tank "Tank 5E (South Tank) Page 7
M. Prublic Works, Mt. Prospect, Illinois I 7.055,H3 73. 006
should have a bonding agent and, a vinyl emollient moed concrete patching mortar applied to build
up the surface to its Id should then be painted with a concrete sealer.
4. Sealant Mam''tenance': Wben the exten'or repainting is performed, the existing sealant
long the bottom plate-to-foundafion interface, should be removed and replaced with a flexible
located a 1,
polyuretbane sealant
5. Overhead Power Lm*esl: All overhead power lines within 40 ft ofthe tank should be
relocated underground M' order to prevent potential electrical shock to personnel wor g on the
tank. The relocation of the power lines sbould be performed m" accordance with the Natlonal. Electric
Code (NEC) guidelines.
I . Life of the Exterior Coating.- The ext nor coating system. appeared to be in fair to good
overall condition with additional areas of peeled topcoating and corrosion. noted. The exterior surfaces
should not need to be repainted within the next 3 to 5 years fi-om a corrosion standpoint. However, the
exterior, should be re-evaluated in 3 to 5 years in accordance with AWWA recomn'lendations to
determine a more precise recoating schedule. Due to the good to very good adhesion of the existing
coating system, spot, cleaning, and topcoating may be a feasible option,., 'fhe cite coating system.
should be evaluated, immediately prior, to preparing specifications to determine if the coating adhesion
is still adequate to accept a topcoat. Due to the extent of corrosion around one of the shell manholes it
is recommended this area be spot cleaned and spot coated within the next year.,
2. Coating Testing: Prior to preparation of specifications for the cleaning and coating of the
exterior ofthe tank, samples of the exterior coating system should be subjected to laboratory analysis to,
test for Ingredients which may at that time be subj'ect tegulations conn erru'ng their handling and
disposal.
3. Cleaning: Due to the fact that the present exterior coatings appear to contain lead, coating
I to the
�removal, should be performed in accordance with 'local, state, and �fe�deral, regulations, relative
removal of heavy-metal based coatings. When the exterior is to be cleaned, all varietiesof containment
sbould be investigated. Containment of the wind-bilown debn's, willbe required and containment of
paint, droplets may berequired due to the *mty of the adjacent residences.
proxi 1
Je.) Recommended Coating System-.
a. Spot Clean and Topcoat: If the exterior 'i's to be repainted within the next few
years, then spot cleaning and topcoatffig the tank appears to be the recommended option. The
11 000'. 000 Gallon Ground Storage Tank "Tank 5E (South, Tank) Page 8
Mt. Prospect Public Works, Prospect, Illinois J 7. 0'55.H3,73.006
typical, life, of a spot cleaned, and topcoated system is approximately 7 to 8 years, but is highly
dependent on previous surface preparafton and the condition of the underlying coating system, .
MARIA
Iml my 11; 1 xpcl -tai I
I I U0,01 r'! I U0061WO, I WMIP M U EIRM oll mw 11 11
walm XARIJIN, I I I I
5. Alternative Coating System. -
b., Coatm*g Appfication: The entire tan]k exterior should, be cleaneld to the equivalent
of an SSPC-�SP 6, Commercial Blast Cleaning and have an epoxy -primed, epoxy intermediate
and polyurethane finish coating system applied. However) care must be taken during the
application of this particular coating system, because this coating does have poor dry -fall
characteristics, and poten�tial damage to the surrounding property must be taken into
consideration. The polyurethane coatings also, require close moniton'ng of temperature and
humidity during application.
4,
7. Other Systems-, With air emisswn volatile or1ganic, compounds (VOC) restn,*ctions being
1 A alternative coating systems may become available which would be
put in place arounci the nation',
viable options for this tank. The Owner should review the available systems pnor to prepanng
specifications for the recoating project.
8. Coating Curm*g* It would be more economical to; paint,the tank exterior at the sametime
the interior is painted, since the tank, must be drained while the ex,ten"'or is painted, and the applied
coatings curie. This will also reduce mobilization and observation costs. I?
1 1 f ) P
1, 0001 P 000 Gallon, Grotina Storage Tank, Tank 5E (South Tank) Page 9
-Mt* ]�•Sp 17.055',H3 73.006
9., Rebabilikation Schedule: To obtain the lowest possible prices f6r the work outlined in t'nre
recommendations, the Owner should have the specifications prepared and the work bid in the sprIng,
with'the work scheduled to start in early summer (if possible).
10., Electrical Apparatus- All, unused, electtical, condult, antennas,, fixtures, electncal,
Metenng equi ment cathodic protection apparatus) and control cabinets should be removed from the:
p
tank and tank-. site. All required equipment should be repaired and maintained in raccordance with the
National Electric Code (NEC).
10
I L Grmding and Bracket Removal.- Any unused brackets or erection lugs should, be
removed prior to the exterior repainting. Any weld burrs, weld spatter,, or crection scars should be
ground.offto provide a smooth surface for the application of the coating.
12. Nameplate: The tank nameplate should be remove`or the c1u'ng and coating of the
tank,. The nameplate should be cleaned and reattached to the tank using the existing bracket.
13. Existing Shell, Manholes-. At the time of recoating and re airs, the gaskets for the shell
p
illanboles should ble replaced,., '.rbe covers should be equipped with hinged support arms located on the
extla--ior i*f the tart -1.
mi r a LIUVIS EM I I �� ITLA
15. Roof Safety Railing. Ibe toe, bar should be replaced with a new toe: bar which is, at least
31-11/2 in. tall, and allows a gap 1/4 in., or less between. it, and the r�oof The access opem'ngshould be
equipped with a self-closing gate.
16. Clog -Resistant Vent& The proper operation of the vent should be pen*odically ven'fied.
2. Coating Testm*g: Prior to preparation of specifications for the cleaning and coating of the
i� "
interior of the tank, samples of'the interior coating system should be subjected to laboratory analysis to
test for ingredients which may at that time be subject to regulations concenung their handling, and
disposal.
11 000, 000 Gallon, Ground Storage Tank "Tank 5E i(Sou�th Tank) Page J 0
Mt. Prospect Public Works, Mt. ProVect, Illinois 17. 055.H3 73.10061
3. Recommended Inte,rior Coating System:
a. Epoxy Coating, System: The optimum, long -life coating system presently availabl.
for the interior of'water tanks is a two -component epoxy coating system. A three -coat epox
system is recommended for the: interior of this tank. This coating system should meet th
certification criteria of ANSINSF 61 and state department ofihealth regul,at�ions.,
b. Coathag Applicafion: When the 'interior 'i's to be repaintea, the entire tank interior
should be cleaned to the equivalent of an DSPC -SP 10, Near -White Blast, Cleaning and, an epoxy
coating system, applied.
C. S,em*ce Life-. The typical life of a properly formulated and applied epoxy coating
system is approximately 12, to 15 years in immersion service. Tank Industry Consultants defines,
the H6 of a coating as the expected service life before repainting becomes necessary due to
coating failure and corrosion.
4�. Cathodic Protection-. The cathodic protection system should be evaluated and adjusted by
the manufacturer,, and then properly maintained.
5'. Pilt Weldm'g and Pit Filling: after inti al. cleaning, all significant pitting which is f6und
should be welded, and all pitting, with rougla edges that would make the pitting difficult. to coat properly
should be filled with a solventless epoxy scam sealer.
6. Rough Edges.- All unused, brackets should be removed -from the interior and exterior
surfaces at the time of the ne�xt recoating. Any weld burrs, spatter,, scars or rough edges in the steel
should be ground smooth to provide a better surface for coating.
7. Roof Support Structure: After abrasive blast cleaning, the roof support structure should
be carefully evaluated as e,ta'l loss repairs may be necessary at areas where the metal loss was, not
previous visible.At this time, there was no signifficant metal loss, observed, and all of the connections
appeared to be in adequate condition. However, with the existing coating failure and corrosi.,
structurally significant metal loss will likely occur within the next 3 to 5 years.
it 000, 000 Gallon, Grow nd'St07-age Tank,, "Tank 5E (South, Tank) Page]]
Mt. Prect Public Works, Mt.,Pr ct,, 111hiois 17 055.H3 73.006
a
ECONONHC FACTORS.
Item, Cost Life in Years
Replacem, ent of tank with a new one $ 29200)0001 75+
,The following is, a complete list of repairs and estimated costs for their respective recommendations
found 'in, the RECOMMENDATION section of this report.,
I . tem
Sanitary & Sa
Scheduled
Mam"tenance
Repairs
Clean and Paint Exterior.
Spat Rair and T
$160PO
Containment
SP 6, qqTplete Clean, Epoxy/Polyurethane System
Sealant Repair
903000
250,000
Containment
110 �1000
Clean and Pat Interior.
�Replace �Roof Safety Railing Toe Bar
SPI 10, 3 -Coat EpoxXSy§tem
.
3,8031 000
Foundation Repair
Sealant RepaIT
ncy Items
ContingeYYF
- 3,00
2P0
Chipping and Grinding
21,000
-Miscellaneous
e Exterior Ladder
Rce Roof Safety Railing Toe Bar
$51000
1,000
Install S,elf-Closing Gate on Roof Safety Railing
3,
Shell Manhole Davits, P)
51000
Contmigency Items
8p000
1,05000
Estimates are bel,,Ieved to be a high, average of bids that would be received in 2017.
The rqplacemeat esti Mate includes costs associated with new tank fabrication and crection, foundation, painting, and engins ng. The
budget estimate given does not include costs associated with tank dei-nolition, site acquisition, and distiibution, interruptions.
The follo,wing economic factors ineWde only those work, items that the Engineer believes, to be the
minimum to properly maintain, tinis tank from an operational standpoint. Other items related to safety
and risk management should be evaluated by the Owner.
.. ... . . .. ...
can and Paint Extenior:
Spot Xepair and, Topcoat,
. .. . .... ...... . . . . . .......
Clean and Paint Intenior:
SP I 10�3 -Coat LEpoxy System
Foundation e i
pair
Sealant Repair
Miscellaneous CluppTg-and Grind ing
Rq lace Extenoir Ladder
�Replace �Roof Safety Railing Toe Bar
Install Self-Clofs,ffig Gate on Xqof Safety Railing . .... .. ...
.
ncy Items
ContingeYYF
Total ofEn �er, s, Aecommendations
-11
1, 00 0,X0'0 Ga 110ii, Ground Storage Tank, "'Tan 5E (South Tank) Page 12
Mt. Prospect Public Works, Mt. Prospect, Illinois I 7055.H373. 006'
Due to, the numerous potential scopes of,wiork which exist, the Owner should obtain an, updated budget
estimate once the fuial sciope of work has been determined. This would enable: the Owner to accurately
budget monles for additional mobilization costs and damaged coating rehabilitation costs.
En,gineiefing and resident observation costs are not included, in the Total, of the En "neer"s
91
Recommendations, because these fees are dependent upon, the scope of work to be performed. Tanl<.
Industry Consultants performs all facets: of the engineering services which would be required f6r this
project. Estimated fees for engineering and resident observation will be fumished upon request.
r Vii,
IS
a a,
Ell
ILI
11 111 PIR! I I I Uld I w I I valwegave Emmilw
a N-1 4 1 111 ei
Contractor Selection:. The work should be, performed by a competent bonded contractior,, chose�n fxm
competitive bids taken on complete and concise specifications., The coatingsused, should be farnishe
by an expefienced water tan1c coating manufacturer, supplying the field servi i ce required for applicatio,
of technical coatings.
Standards for Repalirs and Coatings. All work done and coatings applied should be applied in
I , SF Standard 61 the:
et
manufacturr's recommendaion AWWA D 100
accordance w'th NACE, ANSI/N I I I
and A,NMA D'102 (latest revisions), and the SSPC-.Society for Protective Coatings.
#
]1 000, 000 Gallon Ground Storage Tank, "Tank 5E (South Tat7k) Page 13
Alt. Pro ect Public Works, Mt. ectflhnois 17.055. H3 73.006'
Anniversary and Mam*tenanee Evaluations': An. anniversary, evaluation should be conducted pfiior to
the end, of the one year bonded guarantee. Washouts and coating, structural, sanitary; s�afety, and
C01TOsion evaluations should be conducted not less than every 3 to 5 years.
Time Frame*. If the work is not perfonned within the next 24 months, the: structure should be
reevaluated piri,or to the preparation of specifications and solicitation of bidis.
MAN
Liennitations of Evaluation: It 'is believed that the conditions reported herein reflect the condition of
the: tank as, observed on the date of the evaluation,- using reasonable care in, making the observations,
aU. F
and safety in gairfing access to the tnk. Sho Id latent defects bd
e discovered ufing the clearnng of the
stracture, they should bebrought to the attention of the Owner and the Engineer.
lip
117 000, 000 Galloti. Grow & Storage,Tw7,k, "Tank 5E (South Tat?k) Page 14
Alft". Prospect Public fforlu ) M. t. Pi:2,spest, Illinois 17, 055113 73. 0,06
Please contact Tankustry Consultwits if you have any questmns'oar comments.,
Respeaffilly submitted,
Tank Ind -as try Consultants,
C-Vk-
Penra' Snodgrass
Technical Ed"tor -P
4WO
4
R
E
Gregory'E 1
Manan al OF
Coppight @ 2,017", U., 011SUItants
All lU 7ed
Ulassincation of Adhes 10,nl
Test Results
Mei hod A — X Cut Tape Test
Approx. 1.5 in. long cuts at 30 de'g. to 4-5 deg. opart.
Surface
Clo,sSification
No, peeling or rieren- -avol.
Trace peeling or removal obare ig, incisions.
V/
A
4
Jagged removal along gra cIsions up to 1/16 in.
(1-6mm) on elther side.
3
Jogged removal along most of incisions up to 1/8 in.,
(3.2mm�) on elther side.
2
Removal from Mt of t�he area X under thie
tape,
Removal beyond the area of the X.
L
Methc)d B Lattice Cut Tope Test
'mixporollel cuts ot, 2mm opart.,
Surfacie
Classification
'The edges of t,he cuts are r-DrnpletCly' smoc)th;
none of the squores of the lottice are, detached,.,
No Failure,
5
Small flakes of the coating are detached at
w
-j-LL1L1-
intersec t�ion,s; less thon S%, of the lattice is
4
of Ifec t ed'.
Small flf the coating are, detachield along
edges and at inter-seCtIbris of cuts. The oreo
3
affected is 5% to 15% Df the lattice,.
The cE)otlng has fl along: Lhe edges rand on
AM11
ports c>f the square`s. The oreo offected is
to, .357 of the lattice.
The cDating hos flaked ol'ong the edges, D�f cuts
lin large ribbons and of squores hove detalched,
a
The, area affected is 5% to 657 of the lottlee.
. . . . . . . . . .
I I
Flaking and detachment, worse than grade 1.
0
ASTM! 3359 Stondfar d Test Methods for Meosarin g Adhesion
by Tope Test
Tan k I n.d u s txy Consultants
7West New York Street
Telephone —
317/271-3100,
Indianapolis, Indiana 462,14
FAX —
317/2,71-33,00
I ., Tank and site.
2. Tank and sit.
Mt. Prospect Public Works "Tank 5E (Sh Tank)" Mt. Prospect, Illinois
17.055.H373 .006
I Surrounding area,,.
4,. Surrounding area.,
MI, Prospect Public Works "Tank 5E (South Tank)," Mt. Prospect, Illinois
17,055.H373.006
5 Sutwunding area.
6. Surrounding area.
Mt. Prospect Public Works "Tank 5E (South Tank)"' Mt. Prospect,, Illinois
17.055A373,006
7. Building on tank site.
8. Tank site access.
Mt. Pt Public Works "'I"aDk 5E (South. Tank) Mt. Prospect, Illinois
1.,55.3.6
n - 4,
v. Crack and exposed aggregate In to foundation.
10. Crack and exposed aggregate in tank foundation.
Mt. Prospect PUblic Works "Tank 5E (South,'Tank,)" Mt. Prospect, Illinois
1..6
1, L, Valve vault access.,
12., Valve vault access ladder and safe-
ch,mbing device extension,
Mt, Prospect Public Works "Tank- 5E (South Tank)' Mt. Prospect, Illinois
17,055.H373.0,06
Ij
1H
12., Valve vault access ladder and safe-
ch,mbing device extension,
Mt, Prospect Public Works "Tank- 5E (South Tank)' Mt. Prospect, Illinois
17,055.H373.0,06
13. Piping and valves in vault.
14. Overflow pipe and brackets.
Mt. Prospect Public Works "Tank 5E (South Tank)" Mt. Prospect, Illin.0i's
17.055.H3,73.006
15. Overflow pipe discharge, flap gate, and basin.
"AM,
16. Overflow pipe flap, gate screen.
Mt. Prospect PUblic Wo�rks "Tank 5E (South Tank)" Mt. Prospect, Illinois
17,.055,.H373.006
17. GAP between overflow pipe aid flap gate,
,I S. Pipe projection in shell, conduft, and Junction box..
Mt. Prospect Public 'Works "Tank 5E South Tank)" Mt. P,rospcct, Illinois
17.055.H373.006,
19. Shell marffiole and tank namepl-ate.
W
VIA o!"
/*
zaF 1"o,
0 -A� Awk
We
o .4
IF
vvg",
z %a m
Oz
AX
20. Taft nameplatc.
Mt. Prospect.public Works, "Tank 5E (South Tank)" Mt. Prospect, Illinois
17.055.H373.006
21. Coatingfallurc, corrosion, and rust staining on shell manhol,e reinforcing pad.
22. Conduit extendi'ng'up Shell.
Mt, Prospect Public Works "Tank 5E (South, Tank)" Mt. Prospect, Illinois
1,55..6
iii
21. Coatingfallurc, corrosion, and rust staining on shell manhol,e reinforcing pad.
22. Conduit extendi'ng'up Shell.
Mt, Prospect Public Works "Tank 5E (South, Tank)" Mt. Prospect, Illinois
1,55..6
-Ilk
21. Coatingfallurc, corrosion, and rust staining on shell manhol,e reinforcing pad.
22. Conduit extendi'ng'up Shell.
Mt, Prospect Public Works "Tank 5E (South, Tank)" Mt. Prospect, Illinois
1,55..6
23. Exten'or ladder, safie-climbing device,
and vandal deterrent
. ... . ... 114 ......... .
24,. Coating iale and. corr�osion on exten-or ladder side rall and bracket.
Mt. Prospect PUblic Works "Tank 5E (South'i'ank)"
17.05,.5'.H373,,006
Mt. Nospect, Illinois,
25. She. coating.
26. Spot coating failures and corn on shell.
Mt. Prospect Public'Works ",I * ank 5E (South Tank)" Mt. Prospect, Illinois
ITO'55E373.006
28. Pecled topcoat on, shell..
Mt. Prospect Public Works, "TSouth Tank)" Mt. Prospect, Illinois
17.055.H373.006
29., Crcked safe climbing device tube at, r .
30. Gap between roof safety railing toe bar and roof.
Mt. Prospect Pullblic Works, "Tank 5E (South Tank)" Mt. Prospect, Illinois
17,055B373.006
3 1. Closure chains on roof safety rading access.
Mt. Prospect Public Works "Tank 5E (South Tank)" Mt. Prospect, Iffirlois
17.055.H373.0016
of
3 2 . Roof safety railing access.
Mt. Prospect Public Works "Tank 5E (South Tank)" Mt. Prospect, Iffirlois
17.055.H373.0016
A
r
�AA
j
if
. . . . . . . . . .... .. -_0
33., Exterior ladder, safe- clim.bing dcvice, and roof safety railing.
34., Extelior ladder, safe -climbing clevicell,
and roof safcty railing. Note that saf6-
climbing device terminates below top
r -ung.,
Mt�. Ptublic Works "Tan -k, 5E, (South Tank)" Mt. Prospect, Illinois
17.0,55.H373.0106
"g, ",r—1 41
ly
MINOR",
011
'Y"
A It, 4.
;..,,, friar
M®RM
..,, , , o..... / .. � i / / f
A
r
�AA
j
if
. . . . . . . . . .... .. -_0
33., Exterior ladder, safe- clim.bing dcvice, and roof safety railing.
34., Extelior ladder, safe -climbing clevicell,
and roof safcty railing. Note that saf6-
climbing device terminates below top
r -ung.,
Mt�. Ptublic Works "Tan -k, 5E, (South Tank)" Mt. Prospect, Illinois
17.0,55.H373.0106
36. Corrosion on extenor ladder brackets.
Mt,. Prospect Public Works "Tank 5E (South'Taiik)" Mt. Prospect, Illinois
IT055.H373.006
Conduit that extends across roof.
3 8. Exterior ladder, safe -climbing device, roof vent, and antennas �mounted on roof.
Mt. Prospect Public Works "Tank 5E (South Tank)," Mt., Prospect,, Illinois
17.055,14371006
Mt. Prospect I '% 7,)' P Public Works C,C Tank 5E (South TaIIK) Mt. Pros ect, Illinois
17.055.H373.0,06
/Jy
of
vgii
... ... .. . . .
56,
ON/
N Al,
401, Coating failure and cot-rosi,on at roof wcId scam.
Mt. Prospect I '% 7,)' P Public Works C,C Tank 5E (South TaIIK) Mt. Pros ect, Illinois
17.055.H373.0,06
Mt., Prospect Public Works "Tank. 5E (South Tank)" Mt. Prospect, Illinois
17.055.H373.006
43, Antetmas on. mast mounted, to roof.
4Antenna wire clamped to roof vent flange,
Mt, Prospect Public Works "Tank 5E (South Tank)" Mt. Prospect, Illinois
17.055.H373.006
45. Clog -resistant roof vent,.,
46. Roof vent Pallet.
Mt. Pr Public Works 'f.Tank 5E (South Tank)" Mt. Prospect, Illinois
17.055A373.006
4T Roof manhole ancover.,
48. Interior roof and roof support structurc.
Mt. Prospect Public Works "Tank 5E (South 'Tank)" MI. Prospect,, Illinois
17.055.373.006
49. Intenor roof and roofsupport structure.
50. hiterior roof and, roof support structure.
Mt. Prospect Public Works "'Tank 5E (South Tank) Mt. Prospect, Illinois
17.055.H373.006
00 9100 — ADDENDUM NO. 2
Issued to All Bid Document Holders of Record
Date: May 7, 2019
Project Name: Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank Project
Project No.: 114311
This Addendum forms a part of the Contract described above. The original Contract Documents and any
prior Addenda remain in full force and effect except as modified by the following which shall take prece-
dence over any contrary provisions in the prior documents.
QUESTIONS/COMMENTS FROM PRE-BID MEETING:
1. Contractor to relocate Automatic Meter Reading (AMR) antenna on tank prior to construction.
2. Is lead present in current coating system?
Page 3 of TICS report details the results of the heavy metal tests. TIC 's testing determined the
exterior coating system contains 817 mg/kg, or 0.0817% of lead.
3. What is the size and configuration of the inner roof beams?
Beam quantity and sizing is listed on pages 4 and S of TICS report.
4. What is required for partial beam replacement? Can it be bid as a unit price item?
Section 012000 states what is required for partial beam replacement. These requirements have
been updated as stated below. The pay item will not be bid as unit price and will remain as a
lump sum item.
SPECIFICATIONS:
1. 012000 Measurement and Payment; Section 1.03 Part B: Partial Beam Replacement— Pay Item
No. 1.13
a. Update requirements listed under Partial Beam Replacement to include the following:
i. Center support ring
ii. 20 inner roof beams
iii. 20 outer beam ends
iv. Caulk all joints V2" or smaller between the roof and beams with Sika Flex 1 A
b. Remove requirement for replacement of 24 inner roof perlins.
Each Bidder shall acknowledge receipt of this Addendum by affixing their signature below, by noting this
Addendum on their Bid Form, and by attaching this Addendum to their Bid.
Burns & McDonnell Engineering Company, Inc.
1431 Opus Place, Suite 400
Downers Grove, Illinois 60515
Village of Mount Prospect 009100-1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
00 9100 — ADDENDUM NO. 2: continued
ACKNOWLEDGEMENT
The undersigned acknowledges receipt of this Addendum and the Bid submitted is in accordance with in-
formation, instructions and stipulations set forth herein.
Bidder:
Do
Date:
END OF 00 9100
Village of Mount Prospect 009100-2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E
Ground Storage Tank
SECTION 012000 — MEASUREMENT AND PAYMENT
PART 1 - GENERAL INFORMATION
1.01 MEASUREMENT AND PAYMENT:
A. This Section describes the measurement and payment for the Work to be done under the items
included in this Contract.
B. Each unit or lump -sum price stated in the Bid shall constitute full compensation as herein
specified for each item of work completed in accordance with the Contract Documents. The
price shall be full compensation for furnishing all materials and for all labor, equipment, fees,
tools and incidentals necessary to complete the item as included in the Contract Documents.
C. No separate measurement and payment shall be made for Work not specifically listed in this
Section. It shall be understood that all Work necessary to complete the Contract as included in
the Contract Documents shall be included in cost of the unit and lump sum items included in
the Contract.
D. Pay Items 2 & 3 of the Schedule of Values Section 004015 includes all work to be completed
for the Tank 5E one -million gallon ground storage tank. Alternate bid items are included in the
Bid Form and may be added to the bid by the Owner. Descriptions of sub -pay items and
alternates are provided below.
1.02 BASE BID PAY ITEMS:
A. Mobilization Pay Item No. 1
1. Mobilization will be paid for at the contract lump sum price for the mobilization and
demobilization of all equipment to and from the site in accordance with Article 671 of the
IDOT Standard Specifications for Road and Bridge Construction and the restoration of
the project site. The unit price for this item shall constitute full compensation for all
equipment, materials, labor, fees, tools and incidentals necessary to complete this item.
No additional compensation will be given for re -mobilization to and from the site due to
any reason.
B. Interior Coating Rehabilitation — Pay Item No. 2
1. Interior Coating will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools and incidentals required to complete the
appropriate surface preparation and re -coat the tank interior.
C. Exterior Coating Rehabilitation — Pay Item No. 3
1. Exterior Coating Rehabilitation will be paid for at the contract lump sum price. This work
shall include all equipment, materials, labor, fees, tools and incidentals required to
complete the proper surface preparation, spot prime, and over -coat the tank exterior.
D. Steel Work & Miscellaneous Repairs — Pay Item No. 4
1. Steel Work & Miscellaneous Repairs will be paid for at the contract lump sum price. This
work shall include all equipment, materials, labor, fees, tools and incidentals required to
complete the structural work and miscellaneous work as specified. This work includes
but is not limited to the following:
a. Miscellaneous chipping and grinding
b. Seam sealing
C. Sealant repair
d. Foundation repair
e. Removal and replacement of the existing wet interior ladder with a fall prevention
device.
£ Removal and replacement of the existing exterior ladder with a fall prevention
device.
g. Installation of shell manhole davits (2)
Village of Mount Prospect Section 012000 - 1 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank
SECTION 012000 — MEASUREMENT AND PAYMENT: continued
h. Installation of a self-closing gate on the existing roof safety railing
i. Replacement of the existing roof safety railing toe bar
j. Installation of mud guards (2): Install a removable mud guard on the inlet/outlet
pipe and the drain pipe.
E. Electrical Work — Pay Item No. 5
1. Electrical Work will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools, and incidentals required to remove and replace
the existing breaker in the electrical vault.
F. Tank Disinfection — Pay Item No. 6
1. Tank Disinfection will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools and incidentals required to disinfect and test
the tank as specified.
G. Site Restoration — Pay Item No. 7
1. Site Restoration will be paid for at the contract lump sum price. This work shall include
all equipment, materials, labor, fees, tools, and incidentals required to restore any
disturbed areas of the site as specified.
H. Contingency — Man Hours for Additional Work — Pay Item No. 8
1. Contingency will be paid for at the contract price per man-hour. This work shall include
all equipment, materials, labor, fees, tools, and incidentals required to complete the work
as specified and as requested by the Village.
1.03 ALTERNATE BID PAY ITEMS
A. Exterior Coating w/ Full Blast Pay Item No. LA
1. Exterior Coating w/ Full Blast will be paid for at the contract lump sum price as an
addition or deduction to the cost of Bid Item 3. This work shall include all equipment,
materials, labor, fees, tools and incidentals required to complete the appropriate surface
preparation and re -coat of the tank exterior.
B. Partial Beam Replacement — Pay Item No. 1.13
1. Partial Beam Replacement includes removal and replacement of the center support ring,
2-4-20 inner roof beams, r � , and outer beam ends. Partial Beam
Replacement also includes material and labor to caulk all joints 1/2" or smaller between
the roof and beams with Sika Flex IA. This work shall include all equipment, materials,
labor, fees, tools and incidentals required to complete the items listed above. Work shall
be paid at the contract lump sum price for Partial Beam Replacement.
C. Complete Beam Replacement — Pay Item No. 1.0
1. Complete Beam Replacement includes removal and replacement of the center support
ring, roof beams, and roof perlins. Complete Beam Replacement also includes material
and labor to caulk all joints 1/2" or smaller between the roof and beams with Sika Flex IA.
This work shall include all equipment, materials, labor, fees, tools and incidentals
required to complete the items listed above. Work shall be paid at the contract lump sum
price for Complete Beam Replacement.
END OF SECTION 012000
Village of Mount Prospect Section 012000 - 2 April 2019
Rehabilitation of 1,000,000 Gallon Station 5E Ground Storage Tank